Plan Review Details - Permit 01070176
Plan Review Stops For Permit 01070176
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-08-14 Cont ID  
Sent By jwitmer Date 2001-08-14 Time 17:14 Rev Time 0.75
Received By jwitmer Date 2001-08-14 Time 17:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-17 Cont ID  
Sent By jwitmer Date 2001-07-17 Time 19:58 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-17 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070176
 400 COLUMBIA DR SUITE 111
 CONT : CATALFUMO
 PHONE: 694-3000 X 256
  
 1)- SBC 1004.1.4 ARRANGEMENTS OF EXITS:
 WHERE 2 OR MORE EXITS OR EXIT ACCESS
 DOORS ARE REQUIRED, THE DOORS SHALL BE
 PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN ONE HALF OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF
 THE BUILDING OR SPACE. FROM DOOR 103A TO
 DOOR 110B THIS MEASUREMENT MEETS THIS
 CRITERIA BUT SBC 1001.1.3 WILL NOT ALLOW
 A MEANS OF EGRESS TO GO THROUGH KITCHENS
 CLOSETS,(STORAGE ROOMS) NOR RESTROOMS.
  
 2)- DOOR 101C DOESN'T MEET THE MANEUVER-
 ING CLEARENCES AT DOORS FL ACCES CODE
 4.13.6 SEE ATTACHMENT.
  
 3)- ROOMS 110/111 SBC 1204.2 THE WALLS
 AND FLOORS OF ALL PUBLIC RESTROOMS SHALL
 BE LINED WITH AN NONABSORBENT MATERIAL
 TO A HEIGTH OF 4'-0" ABOVE THE FLOOR.
  
 4)- FL ACCES CODE 4.5 FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES AND IN ACCESSIBL
 E ROOMS AND SPACES INCLUDING FLOORS,
 WALKS AND RAMPS SHALL BE STABLE, FIRM &
 SLIP-RESISTANT. ADDAAG A-5. A STATIC
 COEFFICIENT OF FRICTION OF 0.6 IS
 RECOMMENDED FOR ACCESSIBLE ROUTES &
 0.8 FOR RAMPS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-14 Cont ID  
Sent By dpalmer Date 2001-08-14 Time 20:07 Rev Time 0.00
Received By dpalmer Date 2001-08-14 Time 20:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-07-30 Cont ID  
Sent By dpalmer Date 2001-07-30 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2001-07-30 Time 20:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-08-17 Cont ID  
Sent By mcarsill Date 2001-08-17 Time 14:09 Rev Time 0.00
Received By mcarsill Date 2001-08-17 Time 14:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-07-05 Cont ID  
Sent By mcarsill Date 2001-07-05 Time 18:55 Rev Time 0.00
Received By mcarsill Date 2001-07-05 Time 18:55 Sent To  
Notes
2001-07-05 00:00:001) PLEASE EXPLAIN EXITING ARRANGEMENT
 TO THIS OFFICE. IT APPEARS THAT TWO
 EXITS ARE AVAILABLE FROM THE WAITING
 AND CONFERENCE AREA. THERE APPEARS TO
 BE EXIT SIGNS LOCATED NEAR THE STORAGE
 ROOM. IS THIS AREA PROVIDED FOR THE
 SECOND MEANS OF EGRESS SINCE THE OTHER
 TWO DO NOT SEEM SEPARATED FROM ONE
 ANOTHER BY 1/2 THE DIAGONAL DISTANCE
 RULE. EXITING INTO STOREROOMS NOT NORMAL
 2) ADDITIONAL EMERGENCY LIGHTING
 EQUIPMENT NEEDED IN LARGE OPEN AREA
 OF THE TENANT SPACE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-16 Cont ID  
Sent By pkrauss Date 2001-08-16 Time 12:32 Rev Time 0.35
Received By pkrauss Date 2001-08-16 Time 12:11 Sent To  
Notes
2001-08-16 00:00:00*******************PROVISO**************
  
 NO COMBUSTIBLES ABOVE THE CEILING IN
 THE RETURN AIR PLENUM AS PER 1997 SMC
 601.1.1.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-07-24 Cont ID  
Sent By pkrauss Date 2001-07-24 Time 12:52 Rev Time 0.45
Received By pkrauss Date 2001-07-24 Time 12:32 Sent To  
Notes
2001-07-24 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
  
 IS DUCTWORK BEING REPLACED, ADDED TO
 MODIFIED?PROVIDE DUCT SIZE.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 REQUIRED AS PER 1997 SMC 406 WITH
 NOTIFICATION TO ALARM/STROBE AS PER
 NFPA 90A 4-4.4.3.
  
 NOTE:PRIOR TO CONNECTING TO ANY
 EXISTING DUCTWORK, PLEASE CALL
 FOR AN INSPECTION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-08-16 Cont ID  
Sent By lsmith Date 2001-08-16 Time 12:06 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***