Plan Review Details - Permit 01070176
Plan Review Stops For Permit 01070176 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2001-08-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-08-14 |
Time |
17:14 |
Rev Time |
0.75 |
Received By |
jwitmer |
Date |
2001-08-14 |
Time |
17:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-07-17 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-07-17 |
Time |
19:58 |
Rev Time |
0.75 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-07-17 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01070176 | | 400 COLUMBIA DR SUITE 111 | | CONT : CATALFUMO | | PHONE: 694-3000 X 256 | | | | 1)- SBC 1004.1.4 ARRANGEMENTS OF EXITS: | | WHERE 2 OR MORE EXITS OR EXIT ACCESS | | DOORS ARE REQUIRED, THE DOORS SHALL BE | | PLACED A DISTANCE APART EQUAL TO NOT | | LESS THAN ONE HALF OF THE LENGTH OF THE | | MAXIMUM OVERALL DIAGONAL DIMENSION OF | | THE BUILDING OR SPACE. FROM DOOR 103A TO | | DOOR 110B THIS MEASUREMENT MEETS THIS | | CRITERIA BUT SBC 1001.1.3 WILL NOT ALLOW | | A MEANS OF EGRESS TO GO THROUGH KITCHENS | | CLOSETS,(STORAGE ROOMS) NOR RESTROOMS. | | | | 2)- DOOR 101C DOESN'T MEET THE MANEUVER- | | ING CLEARENCES AT DOORS FL ACCES CODE | | 4.13.6 SEE ATTACHMENT. | | | | 3)- ROOMS 110/111 SBC 1204.2 THE WALLS | | AND FLOORS OF ALL PUBLIC RESTROOMS SHALL | | BE LINED WITH AN NONABSORBENT MATERIAL | | TO A HEIGTH OF 4'-0" ABOVE THE FLOOR. | | | | 4)- FL ACCES CODE 4.5 FLOOR SURFACES | | ALONG ACCESSIBLE ROUTES AND IN ACCESSIBL | | E ROOMS AND SPACES INCLUDING FLOORS, | | WALKS AND RAMPS SHALL BE STABLE, FIRM & | | SLIP-RESISTANT. ADDAAG A-5. A STATIC | | COEFFICIENT OF FRICTION OF 0.6 IS | | RECOMMENDED FOR ACCESSIBLE ROUTES & | | 0.8 FOR RAMPS. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 X 8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-08-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-14 |
Time |
20:07 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-14 |
Time |
20:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-07-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-07-30 |
Time |
20:06 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-07-30 |
Time |
20:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-08-17 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-17 |
Time |
14:09 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-17 |
Time |
14:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-07-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-05 |
Time |
18:55 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-05 |
Time |
18:55 |
Sent To |
|
|
Notes |
2001-07-05 00:00:00 | 1) PLEASE EXPLAIN EXITING ARRANGEMENT | | TO THIS OFFICE. IT APPEARS THAT TWO | | EXITS ARE AVAILABLE FROM THE WAITING | | AND CONFERENCE AREA. THERE APPEARS TO | | BE EXIT SIGNS LOCATED NEAR THE STORAGE | | ROOM. IS THIS AREA PROVIDED FOR THE | | SECOND MEANS OF EGRESS SINCE THE OTHER | | TWO DO NOT SEEM SEPARATED FROM ONE | | ANOTHER BY 1/2 THE DIAGONAL DISTANCE | | RULE. EXITING INTO STOREROOMS NOT NORMAL | | 2) ADDITIONAL EMERGENCY LIGHTING | | EQUIPMENT NEEDED IN LARGE OPEN AREA | | OF THE TENANT SPACE. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-08-16 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-16 |
Time |
12:32 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2001-08-16 |
Time |
12:11 |
Sent To |
|
|
Notes |
2001-08-16 00:00:00 | *******************PROVISO************** | | | | NO COMBUSTIBLES ABOVE THE CEILING IN | | THE RETURN AIR PLENUM AS PER 1997 SMC | | 601.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-07-24 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-07-24 |
Time |
12:52 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-07-24 |
Time |
12:32 |
Sent To |
|
|
Notes |
2001-07-24 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | IS DUCTWORK BEING REPLACED, ADDED TO | | MODIFIED?PROVIDE DUCT SIZE. | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | REQUIRED AS PER 1997 SMC 406 WITH | | NOTIFICATION TO ALARM/STROBE AS PER | | NFPA 90A 4-4.4.3. | | | | NOTE:PRIOR TO CONNECTING TO ANY | | EXISTING DUCTWORK, PLEASE CALL | | FOR AN INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2001-08-16 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-08-16 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|