Plan Review Stops For Permit 01070113 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-01-07 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-01-07 |
Time |
13:09 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2002-01-07 |
Time |
13:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-07-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-07-18 |
Time |
07:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-07-18 |
Time |
07:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-08-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-20 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-20 |
Time |
09:03 |
Sent To |
|
|
Notes |
2001-08-20 00:00:00 | 1) BUILDING ADDRESSES REQUIRED. | | 2) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | TO, DURING AND AFTER CONSTRUCTION. | | 3) ELECTRIC POWERED SMOKE DETECTORS ARE | | REQUIRED. WHEN ACTIVATED, THESE DEVICES | | ARE TO BE AUDIBLE IN THE SLEEPING ROOMS | | OF THAT UNIT. | | 4) PORTABLE FIRE EXTINGUISHERS ARE | | REQUIRED. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-07-14 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2001-07-14 |
Time |
10:53 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2001-07-14 |
Time |
10:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-08-18 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-08-18 |
Time |
11:31 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2001-08-18 |
Time |
11:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-07-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-07-10 |
Time |
09:44 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-07-10 |
Time |
09:44 |
Sent To |
|
|
Notes |
2001-07-10 00:00:00 | FAILED | | | | 1) PAGES 1A & 2 GENERAL NOTES #11 CHANGE | | TO READ FHA 1998 DESIGN MANUAL. | | | | 2) MODEL 1572 (L) & (R), M/B SHOWS 1'7" | | TO CENTER OF W/C, AND IT SHOULD BE 1'6" | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | | | 3) IN BATH 2 SHOW CLEAR FLOOR SPACE FOR | | W/C AND LAV. PAGES 1A & 1B. | | | | 4) MODEL 1409 (L) & (R), M/B SHOWS 1'7" | | TO CENTER OF W/C, AND IT SHOULD BE 1'6" | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | | | 5) BATH 2 SHOWS 2'8" OPENING FOR W/C. | | 2'9" MINIMUM SPACE REQUIRED FOR W/C. | | ALSO SHOW CLEAR FLOOR SPACE FOR W/C AND | | LAV. PAGES 1A & 1B. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
F |
Date |
2001-09-17 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-09-17 |
Time |
19:02 |
Rev Time |
0.33 |
Received By |
jgomez |
Date |
2001-09-17 |
Time |
19:02 |
Sent To |
|
|
Notes |
2001-09-17 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | | | 1-TRUSS LAYOUT TO HAVE THE ENGINEER'S | | INFORMATION AS REQUIRED BY CHAPTER | | 471 OF FLORIDA STATUTES WHEN SUBMITT'G | | INFORMATION FOR PUBLIC RECORDS. | | | | 2-REVIEW STAMP USED BY PROFESSIONAL | | DESIGNER OF RECORD DOESN'T IDENTIFY | | THE NAME OF THE COMPANY WHO REVIEW | | THE TRUSS DRAWINGS. PROVIDE THIS | | INFORMATION. | | | | 3-TRUSS ENGINEER TO HAVE ORIGINAL | | SIGNATURE AS REQUIRED BY CHAPTER 471 | | OF FLORIDA STATUTES. | | | | 4-PROVIDE TWO PACKAGES OF TRUSS DRAWINGS | | | | | | | | | | | | NOTES: | | -DRAWINGS TO BE FILED UNDER PERMIT # | | 01070113. | | | | -THESE COMMENTS APPLY TO PERMIT #S: | | 01070113, 01070110, 01070104 AND | | 01070106. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2001-08-24 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-08-24 |
Time |
17:56 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2001-08-24 |
Time |
17:56 |
Sent To |
|
|
Notes |
2001-08-24 00:00:00 | APPROVED WITH PROVISO: | | 1-FLOOD ZONE AO. WILL NEED TO PROVIDE | | THE ELEVATION CERTIFICATE. | | 2-STORM SHUTTERS INFORMATION WAS NOT | | PROVIDED. THEREFORE, PROVIDE COMPLETE | | INFORMATION UNDER A SEPARATE PERMIT. | | 3-PROVIDE THE APPROPRIATE PRODUCT | | APPROVAL FOR ANY SELECTED OPTION. | | 4-PRELIMINARY SOIL TEST REPORT | | RECOMMENDS SOIL TEST FOR EACH STRUCTU- | | RE. FOLLOW THESE RECOMMENDATIONS AND | | PROPER PREPARATION OF SOIL. | | 5-PROVIDE THE DESIGN CERTIFICATION FOR | | BUILDING CODE COMPLIANCE FORM. | | | | | | | | | | NOTES: | | -DRAWINGS TO BE FILED UNDER PERMIT # | | 01070113. | | | | -THESE COMMENTS APPLY TO PERMIT #S: | | 01070113, 01070110, 01070104 AND | | 01070106. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2001-07-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-07-25 |
Time |
12:07 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2001-07-25 |
Time |
12:07 |
Sent To |
|
|
Notes |
2001-07-25 00:00:00 | CHECKLIST: | | 1-FAILED BY PLUMBING. SEE COMMENTS. | | 2-FILE NOTICE OF COMMENCEMENT. | | 3-FLOOD ZONE AO. WILL NEED ELEVATION | | CERTIFICATE. | | 4-PROVIDE COMPLETE INFORMATION FOR STORM | | PANELS OR APPLY FOR SEPARATE PERMIT. | | 5-CLEARLY INDICATE ON PLANS WHICH OPTION | | IS GOING TO BE BUILT. CROSS OUT THE | | ONES THAT DON'T APPLY. | | -PROVIDE THE CORRESPONDING PRODUCT | | APPROVALS FOR SELECTED OPTIONS. | | 6-PRELIMINARY SOIL TEST RECOMMENDS SOIL | | TEST FOR EACH STRUCTURE. FOLLOW THESE | | RECOMMENDATIONS AND PROPER PREPARATION | | OF SOIL. | | 7-ENERGY CALCULATIONS AND ARCHITECTURAL | | PLANS DON'T MATCH. HOT WATER HEATER | | CAPACITY IS 40 GALS OR 50 GALS. REVISE | | EITHER ONE TO MATCH. | | 8-PROVIDE THE DESIGN CERTIFICATION FOR | | BUILDING CODE COMPLIANCE FORM. | | 9-DESIGNER OF RECORD TO REVIEW ALL TRUSS | | DRAWINGS (AFTER THEY ARE REVISED FOR | | ASCE 7-95 FOR 145MPH WIND LOAD) AND | | SPECIFY CONNECTORS THAT WILL RESIST | | THE ENGINEERED CALCULATED LOADS FOR | | EACH TRUSS. | | | | | | | | | | NOTES: | | -THESE COMMENTS APPLY FOR PERMIT #S: | | 01070113, 01070110, 01070104 AND | | 01070106. | | -ALL DRAWINGS WILL BE FILED UNDER | | PERMIT #01070113. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-07-10 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-07-10 |
Time |
07:49 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|