Plan Review Details - Permit 01061337
Plan Review Stops For Permit 01061337
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-07-09 Cont ID  
Sent By hpiskura Date 2001-07-09 Time 16:06 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-17 Cont ID  
Sent By dpalmer Date 2001-07-17 Time 12:57 Rev Time 0.00
Received By dpalmer Date 2001-07-17 Time 12:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-07-05 Cont ID  
Sent By dpalmer Date 2001-07-05 Time 17:13 Rev Time 0.00
Received By dpalmer Date 2001-07-05 Time 17:13 Sent To  
Notes
2001-07-05 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT NO EMERGENCY
 AND/OR EXIT LIGHTING IS SHOWN. PLEASE
 CLARIFY.
  
 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS AND CORRELATE WITH PANEL
 SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-09 Cont ID  
Sent By hpiskura Date 2001-07-09 Time 16:06 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-07-18 Cont ID  
Sent By rturnque Date 2001-07-18 Time 11:28 Rev Time 0.10
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-07-05 Cont ID  
Sent By mcarsill Date 2001-07-05 Time 09:08 Rev Time 0.00
Received By mcarsill Date 2001-07-05 Time 09:08 Sent To  
Notes
2001-07-05 00:00:001) A SINGLE MEANS OF EGRESS FROM THE
 WAREHOUSE IS NOT PERMITTED. DUE TO
 TRAVEL DISTANCES, TWO SEPARATE MEANS
 OF EGRESS ARE REQUIRED.
 2) PLEASE NOTE ON PLANS THE LOCATIONS
 OF EXIT SIGNS AND EMERGENCY LIGHTING
 EQUIPMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-07-09 Cont ID  
Sent By hpiskura Date 2001-07-09 Time 16:06 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-07-07 Cont ID  
Sent By jleech Date 2001-07-07 Time 10:29 Rev Time 0.50
Received By jleech Date 2001-07-07 Time 10:28 Sent To  
Notes
2001-07-07 00:00:00NO PLUMBING WORK.

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-09 Cont ID  
Sent By hpiskura Date 2001-07-09 Time 16:06 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***