Plan Review Stops For Permit 01061331 |
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2001-07-03 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-03 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-03 |
Time |
16:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FS |
|
Rev No |
1 |
Status |
P |
Date |
2001-07-03 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-03 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-03 |
Time |
16:39 |
Sent To |
|
|
Notes |
2001-07-03 00:00:00 | 1) CHECK VALVES REQUIRED FOR ALL FIRE | | DEPARTMENT CONNECTIONS SHOWN ON THE | | DRAWINGS. | | 2) IT APPEARS THAT SOME PORTIONS OF THE | | FIRE MAIN RUN UNDERNEATH THE BUILDINGS. | | NFPA 24, SECTION 8-3.1 INDICATES THAT | | " PIPE SHALL NOT RUN UNDER BUILDINGS". | | NFPA 24 HAS AN EXCEPTION TO THIS | | REQUIREMENT WHICH INDICATES "WHEN | | ABSOLUTELY NECESSARY TO RUN PIPE UNDER | | BUILDINGS, SPECIAL PRECAUTIONS SHALL BE | | TAKEN WHICH INCLUDE ARCHING THE | | FOUNDATION WALLS OVER THE PIPE, RUNING | | PIPE IN COVERED TRENCHES, AND PROVIDING | | VALVES TO ISOLATE SECTIONS OF PIPE | | UNDER BUILDINGS". | | | | PLEASE SUBMIT REVISED PLANS. | | | | APPROVED PROVISO: | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
|