Plan Review Details - Permit 01061331
Plan Review Stops For Permit 01061331
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-03 Cont ID  
Sent By mcarsill Date 2001-07-03 Time 16:13 Rev Time 0.00
Received By mcarsill Date 2001-07-03 Time 16:13 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status P Date 2001-07-03 Cont ID  
Sent By mcarsill Date 2001-07-03 Time 16:39 Rev Time 0.00
Received By mcarsill Date 2001-07-03 Time 16:39 Sent To  
Notes
2001-07-03 00:00:001) CHECK VALVES REQUIRED FOR ALL FIRE
 DEPARTMENT CONNECTIONS SHOWN ON THE
 DRAWINGS.
 2) IT APPEARS THAT SOME PORTIONS OF THE
 FIRE MAIN RUN UNDERNEATH THE BUILDINGS.
 NFPA 24, SECTION 8-3.1 INDICATES THAT
 " PIPE SHALL NOT RUN UNDER BUILDINGS".
 NFPA 24 HAS AN EXCEPTION TO THIS
 REQUIREMENT WHICH INDICATES "WHEN
 ABSOLUTELY NECESSARY TO RUN PIPE UNDER
 BUILDINGS, SPECIAL PRECAUTIONS SHALL BE
 TAKEN WHICH INCLUDE ARCHING THE
 FOUNDATION WALLS OVER THE PIPE, RUNING
 PIPE IN COVERED TRENCHES, AND PROVIDING
 VALVES TO ISOLATE SECTIONS OF PIPE
 UNDER BUILDINGS".
  
 PLEASE SUBMIT REVISED PLANS.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910