Plan Review Stops For Permit 01061005 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-06-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-06-28 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-06-28 |
Time |
13:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-06-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-06-24 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-06-24 |
Time |
12:59 |
Sent To |
|
|
Notes |
2001-06-24 00:00:00 | ******* UNSAT ****** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | PLEASE SEE LETTER ATTACHED AND SUBMIT TH | | E ABOVE INFORMATION FOR REVIEW. IF THERE | | ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
|