Plan Review Details - Permit 01060988
Plan Review Stops For Permit 01060988
Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-12-20 Cont ID  
Sent By pkrauss Date 2001-12-20 Time 08:38 Rev Time 0.30
Received By pkrauss Date 2001-12-20 Time 08:38 Sent To  
Notes
2001-12-20 00:00:00ANCHOR REVISION FOR CONCRETE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-18 Cont ID  
Sent By pkrauss Date 2001-07-18 Time 13:37 Rev Time 0.50
Received By pkrauss Date 2001-07-18 Time 12:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-25 Cont ID  
Sent By pkrauss Date 2001-06-21 Time 09:36 Rev Time 0.35
Received By pkrauss Date 2001-06-21 Time 09:27 Sent To  
Notes
2001-06-21 00:00:00 
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
  
 WILL THIS BE AN EXACT CHANGEOUT OF JUST
 SECTIONS OF DUCTWORK.
  
 FIRE DAMPERS SHALL COMPLY WITH UL 555
 (1997 SMC 610.1.1) PLEASE SUBMIT
 MANUFACTURERS' DETAIL FOR REVIEW.ALL
 FIRE DAMPERS AND DUCT SMOKE DETECTORS
 SHALL BE INDICATED ON PLAN.
  
 IF DUCT ON ROOF IS BEING REPLACED HOW IS
 IT BEING SUPPORTED?
 (SUBMITTAL DATA ON SUPPORTS).
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.