Plan Review Details - Permit 01060821
Plan Review Stops For Permit 01060821
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-19 Cont ID  
Sent By pkrauss Date 2001-06-19 Time 08:11 Rev Time 0.30
Received By pkrauss Date 2001-06-19 Time 08:08 Sent To  
Notes
2001-06-19 00:00:00******************PROVISO***************
  
  
 REVIEW COMMENTS DATED 2/24/01 UNDER
 MASTER PERMIT 01011120.
  
  
 1.SHOW SIZE AND LOCATION OF R/A
 (SHOULD BE IN CENTER ROOM).
  
 2.SHOW DUCT SIZE TO DROP IN ROOM THAT
 AIR HANDLER IS IN.
  
 3.SHOW LOCATION OF CONDENSER UNIT.
 CONDENSER SHALL BE ON A SOLID
 CONCRETE SLABE MINIMUM 3" ABOVE
 THE ADJOINING GROUND LEVEL.
  
 NOTE:REVISED DRAWINGS REQUIRED PRIOR
 TO THE ROUGH INSPECTION.
  