Plan Review Details - Permit 01060628
Plan Review Stops For Permit 01060628
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-31 Cont ID  
Sent By jwitmer Date 2001-07-31 Time 18:43 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-03 Cont ID  
Sent By jwitmer Date 2001-07-03 Time 15:17 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-03 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01060628
 400 NORTNPOINT PRKWY/ #409
 BUTTERS CONSTRUCTION
 (954) 570-8111
  
 1)- SBC 1004.1.4 THE 2 EXIT DOORS NEED
 TO BE 1/2 THE DIAGONAL DISTANCE OF THE
 UNIT APART OR 63.5' APART.
  
 2)- DOORS 109A, 103-A ARE 1 1/2 HR."B"
 LABEL DOORS WITH SELF CLOSING DEVISES.
  
 3)- WAREHOUSE STORAGE, WHAT TYPE OF STOR
 AGE IS THIS TO BE CLASSIFIED AS S-1 OR
 S-2? WHAT TYPE OF MATERIALS?
  
 4)- WAREHOUSE STORAGE EXIT, PATH OF
 TRAVEL?
  
 5)- TENANT SEPERATION: 2HRS. SHOW DETAIL
 OF RATING FOR COLUMN IN WALL.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 (561) 659-8096

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-06-15 Cont ID  
Sent By dpalmer Date 2001-06-15 Time 14:20 Rev Time 0.00
Received By dpalmer Date 2001-06-15 Time 14:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-08-14 Cont ID  
Sent By mcarsill Date 2001-08-14 Time 08:33 Rev Time 0.00
Received By mcarsill Date 2001-08-14 Time 08:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-07-26 Cont ID  
Sent By mcarsill Date 2001-07-26 Time 13:33 Rev Time 0.00
Received By mcarsill Date 2001-07-26 Time 13:33 Sent To  
Notes
2001-07-26 00:00:00FIRE ALARM AND FIRE SPRINKLER PLANS HAVE
 BEEN SUBMITTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-20 Cont ID  
Sent By mcarsill Date 2001-06-20 Time 12:56 Rev Time 0.00
Received By mcarsill Date 2001-06-20 Time 12:56 Sent To  
Notes
2001-06-20 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. PLEASE PROVIDE FIRE
 SPRINKLER DRAWINGS WITH PLANS.
 2) NO LOCKS THAT REQUIRE THE USE OF A
 KEY, TOOL OR SPECIAL KNOWLEDGE ARE
 TO BE INSTALLED ON EXIT DOORS 103A AND
 109A.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM EQUIPMENT INSTALLATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-11 Cont ID  
Sent By pkrauss Date 2001-10-11 Time 11:43 Rev Time 0.35
Received By pkrauss Date 2001-10-11 Time 11:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-29 Cont ID  
Sent By pkrauss Date 2001-06-29 Time 08:40 Rev Time 0.40
Received By pkrauss Date 2001-06-29 Time 08:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-10-04 Cont ID  
Sent By jleech Date 2001-10-04 Time 17:24 Rev Time 0.33
Received By jleech Date 2001-10-04 Time 17:24 Sent To  
Notes
2001-10-04 00:00:00LETTER ADDRESSING CHANGES MADE TO
 PLUMBING.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-14 Cont ID  
Sent By lsmith Date 2001-08-14 Time 08:43 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-08-14 00:00:00PER JL 8/2/01 LS

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-23 Cont ID  
Sent By jleech Date 2001-06-23 Time 13:43 Rev Time 0.75
Received By jleech Date 2001-06-23 Time 13:43 Sent To  
Notes
2001-06-23 00:00:00DENIED;
  
 1.SHOW COMPLIANCE TO TABLE 407 IN THE
 94 SPC. REFUR TO 407.1.3 AND 407.3.1.
  
 2.SHOW LOCATION OF WATER HEATER ON PAGE
 A-4.
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8369