Plan Review Details - Permit 01060598
Plan Review Stops For Permit 01060598
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-10-09 Cont ID  
Sent By jwitmer Date 2001-10-09 Time 15:50 Rev Time 1.10
Received By jwitmer Date   Time   Sent To  
Notes
2001-10-09 00:00:00PROVISO: APPROVED WITH EXCEPTION AS PER
 HISTORICS REV OCT. 1/2001

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-08-06 Cont ID  
Sent By jwitmer Date 2001-08-06 Time 07:15 Rev Time 1.00
Received By jwitmer Date 2001-08-06 Time 07:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-19 Cont ID  
Sent By jwitmer Date 2001-07-19 Time 17:30 Rev Time 8.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-19 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01060598
 295 QUEEN CT.
 CONT: BILL FREE & ASSOC. INC.
 (561) 624-0149
  
 1)- FL. ENERGY CALCULATIONS INCLUDING
 MANUAL "J".
 2)- SHEET A-2 :SECTION#2 FRAMING DETAILS
 MISSING CRIPPLE STUDS AT THE END OF HEAD
 ER & CONNECTION TOP PLATE / HEADER.
 3)- SHEET A-5 WEST OR LEFT SIDE DETAIL,
 MISSING INFOR. ON THE WATERPROOFING FOR
 THE BACK PORCH AND FRONT BALCONY.
 4)- SUB SHEATHING NOT TO CODE: SBC 2305.
 2.5 FOLLOWING STANDARDS APA MANUAL PAGE
 33 FIG. 10-13 DEPICTS SHEATHING TO THE
 BOTTOM OF THE RIM BOARD WITH THE WOOD
 SIDING EXTENDING BELOW THAT.
 5)-SBC 2303.3 REQUIRES A MOISTURE
 PROTECTION VAPOR BARRIER.
 6)- SHEET A-2 SEC"A" SHOWS A CLEAR
 SPAN OF 21'-9" OF WINDOW OPENINGS WITH
 OUT ANY SUPPORT. PLEASE INDICATE THE
 LOADING THAT IS IMPOSED UPON THIS BEAM
 GRAVITY LOADS, LIVE / DEAD LOADS OVER
 THE TRIBUTARY AREA.
 7)- THE SOFFIT FACIA DETAIL SECTION A,B,
 & C INDICATE SOFFITS WITH 5/8" PLYWOOD,
 PLEASE INDICATE ROOF VENTING.
 8)- DISCREPANCY: FLOOR TRUSS CANTILEVER
 AS IN ITEM #4 SUB-SHEATHING IS NOT CON-
 TINUED TO THE BOTTOM OF THE FLOOR TRUSS.
 8)- J-BOLT SIZE & SPACING IS NOT INDICA-
 TED ON THE PLAN.
 9)- SBC 2304.2 AMEND. CLEARENCE BETWEEN
 WOOD SIDING & EARTH TO BE A MINIMUM OF
 6".(A-6)
 10)- SHEET S-2 RAILING DETAIL SBC 1015.3
 A SPHERE 4" CAN NOT PASS BETWEEN THE
 BALISTERS.
 11)- PRODUCT APPROVALS: FOR ALL GLAZED
 OPENINGS PRODUCT TESTING IS REQUIRED FOR
 LARGE MISSLE IMPACT RESISTANCE TESTING,
 SBCCI OR DADE COUNTY PRODUCT APPROVAL
 REPORTS ARE ACCEPTED.SBC 1606.4 AMEND./
 1707.4.1 AMEND.
 SBC 1606.2.6.2 COMPONENTS& CLADDING:
 DOORS & GARAGE DOORS ARE REQUIRED TO
 HAVE PRODUCT TESTING ALSO SBCCI OR DADE
 COUNTY REPORT.
 ROOFING SYSTEMS SBC 1503.2. ROOFING ASS-
 EMBLIES ARE TO HAVE PRODUCT TESTING FOR
 A 110 MPH WIND ZONE,1705 CLAY OR CEMENT
 TILE ARE TO BE TESTED FORTHERE MOMENT OF
 OVERTURNING, DAEE OR SBCCI REPORT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-10-09 Cont ID  
Sent By dpalmer Date 2001-10-09 Time 11:41 Rev Time 0.00
Received By dpalmer Date 2001-10-09 Time 11:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-02 Cont ID  
Sent By dpalmer Date 2001-08-02 Time 12:16 Rev Time 0.00
Received By dpalmer Date 2001-08-02 Time 12:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-24 Cont ID  
Sent By dpalmer Date 2001-06-24 Time 13:30 Rev Time 0.00
Received By dpalmer Date 2001-06-24 Time 13:30 Sent To  
Notes
2001-06-24 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE
 SHOWING SM APPLIANCE CIRCUTIS AT 5000W`S
 PLEASE NOTE THAT SM APPL IS REQ`D AT
 1500KW PER CIRCUIT. PLEASE CORRECT
  
 2)NOTE: PLEASE NOTE THAT LOAD SHOWN FOR
 GARAGE DOOR OPENERS EXCEED 80% OF 15A
 BRKR.
  
 3)NOTE: PLEASE NOTE THAT PLANS SHOW WELL
 PUMP AND PANEL SCHEDULE SHOWS SPRINKLER
 VALVE. PLEASE CLARIFY.
  
 4)NOTE: PLEASE NOTE THAT THE GFI NOTE
 ON PLANS IN REF TO GFI`S IN KITCHEN IS
 NO LONGER.(93 NEC). PLEASE NOTE THAT ALL
 RECEPTS SERVING KITCHEN COUNTERSPACE ARE
 TO BE GFI/GFI PROTECTED. PER 210-8-A-6.
  
 5) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7)NOTE: PLEASE NOTE THAT RISER IS SHOWIN
 G AN EQUIPMENT GROUNDING CONDUCTOR
 BETWEEN METER AND FIRST MEANS OF DISCO-
 -NNECT. PLEASE NOTE THAT THIS WOULD BE
 PARALLELING THE NEUTRAL.
  
 8) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 9)NOTE: PLEASE NOTE THAT PLANS ARE SHOW-
 -ING TWO METERS? PLEASE CLARIFY.
 IS SECOND LOCATION OPTIONAL?
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pkrauss Date 2002-01-16 Time 11:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-01-10 Cont ID  
Sent By pkrauss Date 2002-01-10 Time 15:25 Rev Time 0.35
Received By pkrauss Date 2002-01-10 Time 15:25 Sent To  
Notes
2002-01-10 00:00:00REV MECH PERMIT 01060599 -
  
 PLANS WENT TO ZONING...CONTRACTOR IS
 ADDING A KITCHEN EXHAUST THAT IS
 TERMINATING OUTSIDE NEAR WINDOW...PLANS
 ARE NOT CLEAR IF THE WINDOW IS TO BE
 REMOVED OR NOT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-31 Cont ID  
Sent By pkrauss Date 2001-07-31 Time 12:45 Rev Time 0.35
Received By pkrauss Date 2001-07-31 Time 12:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-25 Cont ID  
Sent By pkrauss Date 2001-06-25 Time 09:44 Rev Time 0.40
Received By pkrauss Date 2001-06-25 Time 09:28 Sent To  
Notes
2001-06-25 00:00:00********************DENIED**************
  
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE THE FOLLOWING
 INFORMATION:
  
 1.DUCT LAYOUT OF NEW AHU.
  
 2.SIZE OF GRILLES BEING INSTALLED AS
 WELL AS CFM DISTRIBUTION.
  
 3.PLEASE SUBMIT MANUFACTURER
 INFORMATION ON NEW AHU & CONDENSER.
 (MAKE, MODEL, SEER & HEAT KW)
  
 4.PLEASE INDICATE RETURN AIR ON PLAN.
  
 NOTE:RETURN AIR CANNOT BE AN OPEN AIR
 RETURN.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-04 Cont ID  
Sent By jleech Date 2001-10-04 Time 19:56 Rev Time 0.33
Received By jleech Date 2001-10-04 Time 19:56 Sent To  
Notes
2001-10-04 00:00:00ADDITION OFKITCHEN SINK. REVISED PLAN

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-06-20 Cont ID  
Sent By kstevens Date 2001-06-20 Time 13:01 Rev Time 0.33
Received By kstevens Date 2001-06-20 Time 13:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2001-07-19 Cont ID  
Sent By jwitmer Date 2001-07-19 Time 18:55 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2001-08-06 Cont ID  
Sent By jwitmer Date 2001-08-06 Time 08:03 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-08-06 00:00:00ZONING: PER S. GRAHAM 8/6/01

Review Stop Z ZONING
Rev No 1 Status F Date 2001-06-15 Cont ID  
Sent By sgraham Date 2001-06-15 Time 07:32 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-06-15 00:00:00NEED SURVEY