Plan Review Details - Permit 01060536
Plan Review Stops For Permit 01060536
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-13 Cont ID  
Sent By dpalmer Date 2001-08-13 Time 08:06 Rev Time 0.00
Received By dpalmer Date 2001-08-13 Time 08:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-19 Cont ID  
Sent By dpalmer Date 2001-06-19 Time 07:02 Rev Time 0.00
Received By dpalmer Date 2001-06-19 Time 07:02 Sent To  
Notes
2001-06-19 00:00:00****************** UNSAT ***************
  
  
 1) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE NOTE NUMEROUS ROOMS MISSING
 EGRESS LIGHTING.
  
 2)NOTE: PLEASE NOTE THAT ELECTRICAL NOTE
 -S ON PLANS REFERENCE ART 251-22 FOR
 GROUNDING. PLEASE NOTE THAT THIS MUST BE
 A MISPRINT. PLEASE CHANGES THE ART IS
 250-122 NEC.
  
 3)NOTE: PLEASE NOTE PANEL SCHEDULE "A"
 PLEASE NOTE THAT OCP/BRKR AND WIRE
 SIZES NEED TO CORRELATE. PLEASE NOTE
 THAT YOU SHOW 30A OCP W/ 7000W LOAD?
 AND 50A OCP ON 5000W LOAD? PLEASE ALSO
 NOTE THAT 1- 20A OCP W/ 8OOOW LOAD.
 PLEASE CORRECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-01-15 Cont ID  
Sent By pkrauss Date 2002-01-15 Time 09:29 Rev Time 0.40
Received By pkrauss Date 2002-01-15 Time 09:29 Sent To  
Notes
2002-01-15 00:00:00MECHANICAL PERMIT 01060567

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-12-19 Cont ID  
Sent By pkrauss Date 2001-12-19 Time 10:37 Rev Time 0.30
Received By pkrauss Date 2001-12-19 Time 10:21 Sent To  
Notes
2001-12-19 00:00:00MECH REV 01060567

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-19 Cont ID  
Sent By hmoser Date 2001-06-19 Time 18:36 Rev Time 0.33
Received By hmoser Date 2001-06-19 Time 18:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-03-29 Cont ID  
Sent By kstevens Date 2002-03-29 Time 10:14 Rev Time 0.00
Received By kstevens Date 2002-03-29 Time 10:14 Sent To  
Notes
2002-03-29 00:00:00REVISION OK - SANT RISER DIAGRAM - RE-
 MOVED 1 W/C M/BATH.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-06-15 Cont ID  
Sent By kstevens Date 2001-06-15 Time 16:40 Rev Time 0.33
Received By kstevens Date 2001-06-15 Time 16:40 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-08-14 Cont ID  
Sent By lhatten Date 2001-08-14 Time 20:23 Rev Time 4.00
Received By lhatten Date 2001-07-08 Time 20:22 Sent To  
Notes
2001-08-14 00:00:00REVIEW & STAMPED PLANS 07/08/2001
 CALC. FEES & PRINT CARDS 08/14/2001

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-15 Cont ID  
Sent By sgraham Date 2001-06-15 Time 07:55 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved