2001-06-13 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PERMIT APPL | | SAYS INSTALLING NEW ELEC TO GUEST HOUSE? | | PLEASE CLARIFY. PLANS SHOW NEW ELEC IN | | GUEST HOUSE? PLEASE CLARIFY. | | | | 2)NOTE: PLEASE NOTE THAT SMOKE DETECTORS | | ARE REQ`D INSIDE AND OUTSIDE BEDROOM | | PER NFPA-72 2-2.1.1.1 | | | | 3) PLEASE NOTE EITHER MISSING EGRESS | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | PER 210-70 OF THE NEC. MAIN ROOM SHOWS | | FAN AND NO LIGHT? PLEASE NOTE ALSO FOR | | EXITING. | | | | 4)NOTE: PLEASE CLARIFY PANEL? SHOWN AS | | NEW.? PLEASE SHOW WHERE PANEL IS BEING | | FED FROM AND HOW PANEL IS BEING FED. | | WIRE SIZES ETC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
|