Plan Review Details - Permit 01060373
Plan Review Stops For Permit 01060373
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-08 Cont ID  
Sent By pkrauss Date 2001-06-08 Time 12:24 Rev Time 0.35
Received By pkrauss Date 2001-06-08 Time 12:02 Sent To  
Notes
2001-06-08 00:00:00*****************PROVISO****************
  
 ATTIC INSTALLATION OF AHU SHALL COMPLY
 WITH 1997 SMC 304.4.1, ACCESSIBLE BY AN
 OPENING & PASSAGEWAY LARGE AS THE
 LARGEST PIECE OF EQUIPMENT & IN NO CASE
 LESS THAN 22" X 36".
  
 AMMENDED 1997 SMC 304.4.2, SHALL HAVE AN
 ACCESSIBLE DISCONNECT SWITCH AND A
 110-20 VOLT A/C GROUNDING TYPE
 CONVENIENCE OUTLET & A LIGHT LOCATED ON
 SERVICE SIDE OF TH EQUIPMENT WITH A
 SWITCH LOCATED AT REQUIRED OPENING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.