Plan Review Details - Permit 01060349
Plan Review Stops For Permit 01060349
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-08-13 Cont ID  
Sent By jwitmer Date 2001-08-13 Time 10:20 Rev Time 1.00
Received By jwitmer Date 2001-08-13 Time 10:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-04 Cont ID  
Sent By jwitmer Date 2001-07-04 Time 12:18 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-04 00:00:00BUILDING PLAN REVIW
 PERMIT # 01060349
 1450 CENTREPARK # 100
 BURKHARDT CONST
 PHONE 659-1400
  
 1)- DOOR 101B DOESN'T INDICATE IF THERE
 IS A RATING ON THIS DOOR, LEADING TO AN
 EXIT ACCESS CORIDOR.
  
 2)- STANDARD BUILDING CODE 1004.1.1:
 WHERE 2 OR MORE EXITS OR EXIT ACCESS
 DOORS ARE REQUIRED, AT LEAST 2 EXIT OR
 EXIT ACCESS DOORS SHALL BE PLACED A DIST
 ANCE APART EQUALL TO NOT LESS THAN ONE
 HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE UNIT.
  
 3)- FLORIDA ACC CODE 1997 EDI. 4.5.1:
 GROUND AND FLOOR SURFACES ALONG ACCESSIB
 LE ROUTES AND IN ACCESSIBLE ROOMS &
 SPACES INCLUDING FLOORS RAMPS STAIRS &
 RAMPS SHALL BE STABLE, SLIP RESISTANT &
 SHALL COMPLY WITH 4.5. (ADDAAG A-5)
 THE RECOMMENDED WALKING SURFACES HAVE A
 STATIC COEFFICIENT OF FRICTION OF 0.6 IS
 FOR ACCESSIBLE ROUTES AND 0.8 FOR RAMPS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-08 Cont ID  
Sent By dpalmer Date 2001-08-08 Time 21:07 Rev Time 0.00
Received By dpalmer Date 2001-08-08 Time 21:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-13 Cont ID  
Sent By dpalmer Date 2001-06-13 Time 20:58 Rev Time 0.00
Received By dpalmer Date 2001-06-13 Time 20:58 Sent To  
Notes
2001-06-13 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATING WAS SUBMITTE
 D FOR PANELS BUT NOT FOR MAIN.
  
 2)NOTE: PLEASE CLARIFY OCP AND WIRE SIZE
 OF #12 AWG FOR TRANSFORMER FEED FROM
 PANEL "HA" TO "TB1".
  
 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 PER 215-3 AND 230-42.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-08-08 Cont ID  
Sent By mcarsill Date 2001-08-08 Time 09:16 Rev Time 0.00
Received By mcarsill Date 2001-08-08 Time 09:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-12 Cont ID  
Sent By mcarsill Date 2001-06-12 Time 07:45 Rev Time 0.00
Received By mcarsill Date 2001-06-12 Time 07:44 Sent To  
Notes
2001-06-12 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-13 Cont ID  
Sent By pkrauss Date 2001-08-13 Time 10:07 Rev Time 0.40
Received By pkrauss Date 2001-08-13 Time 09:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-13 Cont ID  
Sent By pkrauss Date 2001-06-13 Time 12:49 Rev Time 0.40
Received By pkrauss Date 2001-06-13 Time 12:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-09 Cont ID  
Sent By jleech Date 2001-08-09 Time 19:04 Rev Time 1.00
Received By jleech Date 2001-08-09 Time 19:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-06-10 Cont ID  
Sent By pschmitz Date 2001-06-10 Time 13:12 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-10 00:00:00PLUMBING PLAN REVIEW "PASS"PES