Plan Review Details - Permit 01060347
Plan Review Stops For Permit 01060347
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-07-02 Cont ID  
Sent By dpalmer Date 2001-07-02 Time 16:52 Rev Time 0.00
Received By dpalmer Date 2001-07-02 Time 16:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-06-24 Cont ID  
Sent By dpalmer Date 2001-06-24 Time 09:29 Rev Time 0.00
Received By dpalmer Date 2001-06-24 Time 09:29 Sent To  
Notes
2001-06-24 00:00:00************ UNSAT**********
  
 1)NOTE: PLEASE NOTE THAT SUBMITTING
 THE AVAILABLE FAULT CURRENT FROM FPL
 DOESN'T TELL ME WHAT YOUR EQUIPMENT IS
 GOING TO BE RATED AT? PLEASE NOTE THAT
 I WOULD NEED MORE INFORMATION IN ORDER
 TO COME UP WITH A RATING. PLEASE
 ALSO NOTE IF GOING BY FPL LETTER
 MAINS WOULD BE AT 65,000 AND ALL
 EQUIPMENT AND BRKRS WOULD NEED TO BE
 SERIES RATED. ALL PER 110-9.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE AREA ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-12 Cont ID  
Sent By dpalmer Date 2001-06-12 Time 07:17 Rev Time 0.00
Received By dpalmer Date 2001-06-12 Time 07:17 Sent To  
Notes
2001-06-12 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT UNDER F.S. AND
 F.A.C. ALL PLAN DONE BY AN ARCH/ENGINEER
 MUST BE SIGNED,DATED AND SEALED BY THE
 ARCH/ENG OF RECORD. 471.025 AND 481.221
  
 2)NOTE: PLEASE NOTE LOCATION OD GENERAT-
 -OR NOT SHOWN?
  
 3)NOTE: PLEASE NOTE GROUPING OF DISCONNE
 CTS FOR MAIN AND GENERATOR.230-72 ALSO
 PLEASE NOTE 230-76 AND 230-79.
  
 4) NOTE: PLEASE SHOW CALCULATIONS FOR
 TRACK LIGHTING PER 220-12B.
  
 5) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
  
  
 6)NOTE: PLEASE CLARIFY 8 CIRCUITS SHOWN
 FOR BATTERY CHARGER??
  
 7)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER 220. SQ.FT ETC.
  
 8)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.GROUND ROD AND COLD WATER
 IF BLDG STEEL IS NOT AVAILABLE.
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 11)NOTE: PLEASE NOTE THAT OUTLET SPACING
 NEEDS TO MEET LOCAL CODE 210-50 FOR
 OUTSIDE WALL IN STORAGE AREA
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-08-07 Cont ID  
Sent By mcarsill Date 2001-08-07 Time 09:28 Rev Time 0.00
Received By mcarsill Date 2001-08-07 Time 09:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-06-25 Cont ID  
Sent By mcarsill Date 2001-06-25 Time 08:12 Rev Time 0.00
Received By mcarsill Date 2001-06-25 Time 08:11 Sent To  
Notes
2001-06-25 00:00:001) UNABLE TO LOCATE EMERGENCY LIGHT
 FIXTURES FOR STORAGE AREA. EMERGENCY
 LIGHT FIXTURES ARE REQUIRED.
 2) AFTER PERFORMING EXIT CALCULATIONS A
 SINGLE EXIT IS NOT PERMITTED. TRAVEL
 DISTANCE EXCEEDS 100 FEET WITH THE
 FIRE SPRINKLER PROVISION BEING INCLUDED.
 PLEASE PROVIDE LOCATION OF SECOND MEANS
 OF EGRESS AND EXIT SIGN LOCATION.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR GENERATOR AND ANY FUEL STORAGE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-12 Cont ID  
Sent By mcarsill Date 2001-06-12 Time 08:17 Rev Time 0.00
Received By mcarsill Date 2001-06-12 Time 08:17 Sent To  
Notes
2001-06-12 00:00:001) PLEASE CLEARLY IDENTIFY EXIT SIGN
 AND EMERGENCY LIGHTING EQUIPMENT.
 2) PLEASE PROVIDE SEPARATE PLANS AND
 PERMIT FOR FIRE ALARM EQUIPMENT.
 3) PLEASE PROVIDE MORE DETAILS ON
 GENERATOR INSTALLATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910