Plan Review Details - Permit 01060332
Plan Review Stops For Permit 01060332
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-06-22 Cont ID  
Sent By hpiskura Date 2001-06-22 Time 13:36 Rev Time 0.00
Received By rturnque Date 2001-07-12 Time 10:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-09 Cont ID  
Sent By dpalmer Date 2001-07-09 Time 13:49 Rev Time 0.00
Received By dpalmer Date 2001-07-09 Time 13:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-13 Cont ID  
Sent By dpalmer Date 2001-06-13 Time 22:15 Rev Time 0.00
Received By dpalmer Date 2001-06-13 Time 22:15 Sent To  
Notes
2001-06-13 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC WAS SUBMITTED FOR
 PANELS BUT NOT FOR MAIN.
  
 2) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF
 DISCONNECTAND PANEL(S). EQUIPMENT
 GROUNDING CONDUCTORS ARE TO BE SIZED BY
 ART 250-122.
  
 3)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED ? PLEASE
 SEE ART;220
 ALSO PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.PER 215-3 AND 230-42
  
 4)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 `#S ON PLANS AND CORRELATE WITH SUBMITT-
 -ED PANEL SCHEDULES.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-10 Cont ID  
Sent By lsmith Date 2001-07-10 Time 16:01 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-07-12 Cont ID  
Sent By rturnque Date 2001-07-12 Time 10:48 Rev Time 0.15
Received By rturnque Date 2001-07-12 Time 10:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-06-12 Cont ID  
Sent By mcarsill Date 2001-06-12 Time 09:21 Rev Time 0.00
Received By mcarsill Date 2001-06-12 Time 09:21 Sent To  
Notes
2001-06-12 00:00:001) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A OR B. INTERIOR FINISH IN
 OTHER AREAS TO BE CLASS A,B,OR C.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-07-12 Cont ID  
Sent By pkrauss Date 2001-06-11 Time 09:50 Rev Time 0.50
Received By pkrauss Date 2001-06-11 Time 09:11 Sent To  
Notes
2001-06-11 00:00:00*******************DENIED***************
  
 PULL MECH FROM MAIN SET, CMI TO SUBMIT
 PLANS
  
 MECHANICAL PERMIT REQUIRED.PLEASE
 SUBMIT THE FOLLOWING INFORMATION FOR
 REVIEW.
  
 MANUFACTURER/ENGINEER DETAIL OF ROOF
 CURBS.
  
 LOCATION AND TERMINATION OF CONDENSATE.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. (1997 SMC 406.1
 AND NFPA 90A 4-4.4.3, RESPECTIVELY)
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 PLANS ARE NOT DATED OR SIGNED AND SEALED
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-07-11 Cont ID  
Sent By jleech Date 2001-07-11 Time 19:52 Rev Time 0.50
Received By jleech Date 2001-07-11 Time 19:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-06-10 Cont ID  
Sent By pschmitz Date 2001-06-10 Time 12:55 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-10 00:00:00PLUMBING PLAN REVIEWPROVISO
 (1) SHT-2, WATER RISER, AIR CHAMBERS TO
 BE ACCESSIBLE,RECHARGEABLE. SPC 94
 SEC 607.8.3
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-10 Cont ID  
Sent By lsmith Date 2001-07-10 Time 16:01 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***