|
 |
 |
 |
 |
 |
Plan Review Details - Permit 01060066
Plan Review Stops For Permit 01060066 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-06-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-06-13 |
Time |
21:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-06-13 |
Time |
21:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-08-03 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-03 |
Time |
08:31 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-03 |
Time |
08:31 |
Sent To |
|
|
Notes |
2001-08-03 00:00:00 | 1) BUILDING ADDRESSES REQUIRED. | | 2) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | TO, DURING AND AFTER CONSTRUCTION. | | 3) ELECTRIC POWERED SMOKE DETECTORS | | ARE REQUIRED. WHEN ACTIVATED, THESE | | DEVICES ARE TO BE AUDIBLE IN THE | | SLEEPING ROOMS OF THAT UNIT. | | 4) PORTABLE FIRE EXTINGUISHERS ARE | | REQUIRED. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-06-13 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2001-06-13 |
Time |
18:09 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2001-06-13 |
Time |
18:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-08-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-08-03 |
Time |
14:20 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-08-03 |
Time |
14:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-06-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-06-07 |
Time |
18:39 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2001-06-07 |
Time |
18:39 |
Sent To |
|
|
Notes |
2001-06-07 00:00:00 | REVIEW NOTES: FAILED | | | | 1) PAGE 1A & PAGE 2 GENERAL NOTES #11 | | CHANGE TO READ FHA 1998 DESIGN MANUAL. | | | | 2) MODEL 1527 (L) & (R), M/B SHOWS 1'-7" | | TO CENTER OF W/C, AND IT SHOULD BE 1'-6" | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | PAGES 1A & 1B. | | | | 3) IN BATH #2 SHOW CLEAR FLOOR SPACE FOR | | W/C AND LAV. PAGES 1A & 1B. | | | | 4) MODEL 1409 (L) & (R), M/B SHOWS 1'-7" | | TO CENTER OF W/C, AND IT SHOULD BE 1'-6" | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | PAGES 1A & 1B. | | | | 5) BATH #2 SHOWS 2'-8" OPENING FOR W/C. | | 2'-9" MINIMUM SPACE REQUIRED FOR W/C. | | ALSO SHOW CLEAR FLOOR SPACE FOR W/C AND | | LAV. PAGES 1A & 1B. | | | | 6) PLEASE SUBMIT A SANITARY RISER DIA- | | GRAM AS REQUIRED BY SPC-94 SEC.104.2.1 | | AND SEC. 104.3.1 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2001-08-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-08-01 |
Time |
18:06 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2001-08-01 |
Time |
18:06 |
Sent To |
|
|
Notes |
2001-08-01 00:00:00 | APPROVED WITH PROVISO: | | SEE COMMENTS ON PERMIT #01060067. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2001-07-23 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-07-23 |
Time |
10:18 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2001-07-23 |
Time |
10:17 |
Sent To |
|
|
Notes |
2001-07-23 00:00:00 | CHECKLIST: | | SEE COMMENTS ON PERMIT #01060067. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-06-05 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-06-05 |
Time |
13:42 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |