Plan Review Details - Permit 01060054
Plan Review Stops For Permit 01060054 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-08-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-02 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-02 |
Time |
11:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-07-26 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-26 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-26 |
Time |
11:00 |
Sent To |
|
|
Notes |
2001-07-26 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | CODE 3343-00. | | 2) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | TO,DURING AND AFTER CONSTRUCTION. | | 3) ELECTRIC POWERED SMOKE DETECTORS | | REQUIRED. WHEN ACTIVATED THESE DETECTORS | | ARE TO BE AUDIBLE IN THE SLEEPING ROOMS | | OF THAT UNIT. | | 4) PORTABLE FIRE EXTINGUISHERS WITH | | CURRENT SERVICE TAGS ARE REQUIRED. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-08-04 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2001-08-04 |
Time |
07:06 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2001-08-04 |
Time |
07:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-06-14 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-06-14 |
Time |
10:05 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2001-06-14 |
Time |
10:05 |
Sent To |
|
|
Notes |
2001-06-14 00:00:00 | *******************DENIED*************** | | | | | | ARCHITECT FLOOR PLANS DO NOT MATCH | | MECHANICAL FLOOR PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | HAROLD MOSER AT 659-8096 EXT. 8390 | | | | OR | | | | PATTY KRAUSS 659-8096 EXT.8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-08-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-08-03 |
Time |
13:25 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2001-08-03 |
Time |
13:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-06-08 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-06-08 |
Time |
10:55 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-06-08 |
Time |
10:55 |
Sent To |
|
|
Notes |
2001-06-08 00:00:00 | REVIEW NOTES:FAILED | | | | 1) PAGE 1A & PAGE 2 GENERAL NOTES #11 | | CHANGE TO READ FHA 1998 DESIGN MANUAL. | | | | 2) MODEL 1527 (L) & (R), M/B SHOWS 1'-7" | | TO CENTER OF W/C, AND IT SHOULD BE 1'-6" | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | PAGES 1A & 1B. | | | | 3) IN BATH #2 SHOW CLEAR FLOOR SPACE FOR | | W/C AND LAV. PAGES 1A & 1B. | | | | 4) MODEL 1409 (L) & (R), M/B SHOWS 1'-7" | | TO CENTER OF W/C, AND IT SHOULD BE 1'-6" | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | PAGES 1A & 1B. | | | | 5) BATH #2 SHOWS 2'-8" OPENING FOR W/C. | | 2'-9" MINIMUM SPACE REQUIRED FOR W/C. | | ALSO SHOW CLEAR FLOOR SPACE FOR W/C AND | | LAV. PAGES 1A & 1B. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2001-08-07 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-07-23 |
Time |
13:51 |
Rev Time |
1.00 |
Received By |
aneil |
Date |
2001-07-23 |
Time |
13:51 |
Sent To |
|
|
Notes |
2001-07-23 00:00:00 | CHECKLIST: | | SEE COMMENTS ON PERMIT #01060039. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-06-05 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-06-05 |
Time |
14:23 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|