Plan Review Details - Permit 01051213
Plan Review Stops For Permit 01051213
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-06-08 Cont ID  
Sent By jwitmer Date 2001-06-08 Time 10:07 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2002-02-11 Cont ID  
Sent By dpalmer Date 2002-02-11 Time 07:56 Rev Time 0.00
Received By dpalmer Date 2002-02-11 Time 07:56 Sent To  
Notes
2002-02-11 00:00:00NOTES FROM FIRST REVIEW DO NOT APPLY,
 PLANS CAME IN UNDER WRONG #.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-05 Cont ID  
Sent By dpalmer Date 2002-02-05 Time 20:18 Rev Time 0.00
Received By dpalmer Date 2002-02-05 Time 20:18 Sent To  
Notes
2002-02-05 00:00:00********************* UNSAT ************
  
  
 PLEASE NOTE THAT THIS WAS ORIGINALLY A
 PERMIT FOR AN ENTRY ONLY AND DID NOT
 HAVE ANY TRADE REVIEWS DONE(MEP`S).
  
 PLEASE NOTE THAT SEPARATE PERMIT/PLANS
 AND FEES ARE DUE FOR WHAT APPEARS TO BE
 A TENANT FIT UP?
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-01-31 Cont ID  
Sent By mcarsill Date 2002-01-31 Time 15:45 Rev Time 0.00
Received By mcarsill Date 2002-01-31 Time 15:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-05-31 Cont ID  
Sent By mcarsill Date 2001-05-31 Time 16:10 Rev Time 0.00
Received By mcarsill Date 2001-05-31 Time 16:10 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-09-25 Cont ID  
Sent By jwitmer Date 2001-09-25 Time 10:08 Rev Time 1.50
Received By jwitmer Date 2001-09-25 Time 10:08 Sent To  
Notes
2001-09-25 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01051213
 400 NORTHPOINT PARKWAY
 CONT: BUTTER CONST.
 TEL:(954) 570-8111
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= COUNTYWIDE AMENDMENTS TO 1997
 STANDARD BUILDING CODE
  
 1)- THE PERMIT # 01051213 AS STATED ON
 THE PERMIT APPLICATION IS PERMITED ONLY
 FOR" NEW ENTRY INTO EXISTING BUILDING".
 THE SHOP DRAWINGS FOR THE GLAZED UNITS
 WERE SUBMITTED ORIGINALLY, A PROVISO
 WAS PROVIDED TO APPROVE THE PERMIT FOR
 THE ENTRY, THE PRODUCT APPROVAL WAS
 SUBMITTED AND APPROVED.
 NO WHERE DID THE PERMIT APPLICATION
 STATE THAT THIS WAS FOR A TENANT BUILD
 OUT. SBC104.1.5*INFORMATION REQUIRED:
 THE PERMIT APPLICATION,DESCRIBE PROJECT
 IN DETAIL, THE COUNTY AMENDMENT" EACH
 APPLICATION SHALL CONTAIN A GENERAL
 DESCIPTION OF THE PROPOSED WORK AND ITS
 LOCATION.
  
 IF THIS WAS TO BE A TENANT BUILDOUT WE
 WOULD TO HAVE THE PROPOSED OCCUPANCY
 OF THIS SPACE AND THE ADJOINING SPACES.
 THE SECOND ISSUE WOULD HAVE BEEN ELECTRI
 CAL AND PLUMBING FOR THIS SPACE.
  
 A SEPERATE PERMIT WILL BE REQUIRED FOR
 THE TENANT BUILDOUT, (SUITE 401) INDI-
 CATE THE PROPOSED TENANT OCCUPANCY,
 ELECTRICAL, MECHANICAL & PLUMBING. THE
 PLAN INDICATES A DROP CEILING, SHOW SPRI
 NKLER EXTENSIONS, A/C WILL ALSO REQUIRE
 ENERGY CALCULATIONS.
  
 BUILDING PLAN
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-29 Cont ID  
Sent By sgraham Date 2001-05-29 Time 16:02 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***