Plan Review Details - Permit 01050998
Plan Review Stops For Permit 01050998
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-07-19 Cont ID  
Sent By dpalmer Date 2001-07-19 Time 13:09 Rev Time 0.00
Received By dpalmer Date 2001-07-19 Time 13:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-06-27 Cont ID  
Sent By dpalmer Date 2001-06-27 Time 17:28 Rev Time 0.00
Received By dpalmer Date 2001-06-27 Time 17:28 Sent To  
Notes
2001-06-27 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOW
 BEING SUBMITTED SHOWING NEW MAIN DISC0-
 -NNECT AT HOUSE. PLEASE NOTE THAT AIC
 RATINGS OF ALL NEW EQUIPMENT IS REQ`D
 PER 110-9 AND 215-5.
  
 2)NOTE: PLEASE NOTE THAT PLANS DO NOT
 SHOW EQUIPMENT GROUNDING CONDUCTOR FROM
 HOUSE TO DETACHED STRCTURE PER 250-32.
  
 3)NOTE: PLEASE CLARIFY MAIN DISCONNECT
 BEING SHOWN AT 75AMPS. THIS IS NOT A
 STANDARD EQUIPMNET SIZE. IS THIS100A
 EQUIPMENT W/ 75A FUSES? PLEASE VERFIY
 EQUIPMENT AT HOUSE AND DETACHED STRUC.
  
 4)NOTE: PLEASE NOTE THAT LOADS SHOWN FOR
 BOTH PANELS EXCEED EXISTING 200A METER.
 PLEASE NOTE THAT LOAD CALCULATIONS CAN
 BE ADDED AND FIGURED THAT WAY. THIS IS
 AFTER LOADS ARE FIGURED FOR EACH PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-11 Cont ID  
Sent By dpalmer Date 2001-06-11 Time 09:45 Rev Time 0.00
Received By dpalmer Date 2001-06-11 Time 09:45 Sent To  
Notes
2001-06-11 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE CALRIFY EQUIPMENT AND
 OCP AT DETACHED BLDG? PANEL SCHEDULE
 SHOWS 100A MAIN AND RISER SHOWS 75A
 MAINALSO SHOWS 1/0 WIRE FOR 150A FEED?
  
  
 2)NOTE: PLEASE NOTE THAT LOADS SHOWN
 FOR EXISTING 200A MAIN AND NEW LOAD
 BEING ADDED EXCEEDS RATING OF MAIN.
 PLEASE NOTE THAT LOAD ADDS UP TO 203.2
 AMPS.
 ALSO PLEASE NOTE THAT MAIN PANEL
 SCHEDULE DOES NOT LIST ANY BRKR FEEDING
 DETACHED BLDG.?
  
 3)NOTE: PLEASE CLARIFY APPLIANCE CIRCUIT
 BEING SHOWN AT 15A FOR DETEACHED BLDG.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5)NOTE: PLEASE CLARIFY IF BOTH MAINS
 AT DETACHED BLDG IS BEING INSTALLED.
 PLANS SHOW MCB AND DISCONNECT ON THE OUT
 SIDE OF STRUCTURE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-06-28 Cont ID  
Sent By pkrauss Date 2001-06-28 Time 08:11 Rev Time 0.25
Received By pkrauss Date 2001-06-28 Time 08:02 Sent To  
Notes
2001-06-28 00:00:00RESUB - NO MECHANCIAL PLANS SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-06-07 Cont ID  
Sent By hmoser Date 2001-06-07 Time 19:12 Rev Time 0.33
Received By hmoser Date 2001-06-07 Time 19:08 Sent To  
Notes
2001-06-07 00:00:00NO MECHANICAL PLANS,OR ENERGY CALC.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-06-07 Cont ID  
Sent By kstevens Date 2001-06-07 Time 17:09 Rev Time 0.33
Received By kstevens Date 2001-06-07 Time 17:09 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-07-19 Cont ID  
Sent By jgomez Date 2001-07-19 Time 17:45 Rev Time 0.50
Received By jgomez Date 2001-07-19 Time 17:45 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-07-02 Cont ID  
Sent By jgomez Date 2001-07-02 Time 13:19 Rev Time 2.00
Received By jgomez Date 2001-07-02 Time 13:19 Sent To  
Notes
2001-07-02 00:00:00CHECKLIST:
  
 1-STORM SHUTTERS INSTALLATION SCHEDULE
 IS NOT LEGIBLE.
 2-ENERGY CALCULATIONS TO BE ON FORM
 600A-97 NOT 93.
 -ALSO, REVISE DUCTWORK INSULATION. SEE
 SECTION 610 OF FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997.
 -SPECIFY CEILING FANS ON PLANS AS
 AS REQUIRED BY CREDIT TAKEN ON THE
 ENERGY CALCULATIONS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-06-14 Cont ID  
Sent By jgomez Date 2001-06-14 Time 18:40 Rev Time 1.00
Received By jgomez Date 2001-06-14 Time 18:40 Sent To  
Notes
2001-06-14 00:00:00CHECKLIST:
 1-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS: PRODUCT APPROVAL,
 DRAWINGS, KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE. SEE SAMPLE.
 2-SIZE OF BEDROOM WINDOW DOESN'T COMPLY
 WITH THE EGRESS REQUIREMENTS OF SEC.
 1005.4 SBC 1997.
 3-SPECIFY SIZE OF ATTIC ACCESS. 22"X36"
 MIN. AS PER SEC. 2309.6 SBC 1997.
 4-REVISE THE DESIGN CERTIFICATION FOR
 BUILDIONG CODE COMPLIANCE FORM.
 IF USING ASCE 7-95 AS DESIGN CRITERIA,
 THEN, THE WIND SPEED IS 145MPH.
 5-REVISE ENERGY CALCULATIONS. NEED TO
 COMPLETE FORM 600A. THIS IS A NEW
 SMALL BUILDING NOT AN ADDITION TO
 EXISTING BUILDING.
 6-PROVIDE PRODUCT APPROVALS FOR:
 A)SLIDING GLASS DOORS.
 B)SINGLE HUNG WINDOWS.
 C)ROOF SHINGLES.
 7-BRING DRAWINGS TO PALM BEACH COUNTY
 TO VERIFY IF IMPACT FEES ARE DUE.
 BRING STAMPED DRAWINGS AND RECEIPT.
  
  
 NOTES:
 -SEE PLANS FOR ADDITIONAL COMMENTS
 INCLUDING THOSE BY THE OTHER TRADES.
 -CONTRACTOR TO UPDATE INSURANCE AS REQ'D

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-30 Cont ID  
Sent By sgraham Date 2001-05-23 Time 08:39 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-05-23 00:00:00NEED SITE PLAN