Plan Review Details - Permit 01050955
Plan Review Stops For Permit 01050955
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-05 Cont ID  
Sent By jwitmer Date 2001-07-05 Time 11:24 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By jwitmer Date 2001-06-07 Time 13:04 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-07 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01050955
 301 N DIXIE
 H. A. CONTRACTING CORP.
 (305) 591- 9212
  
 1)- FL S. S. 481.221(1) (A) FAILURE OF
 THE ARCHITECT TO DATE PLANS.
 2)- FL S. S. 481.221 (2) FAILURE OF THE
 ARCHITECT TO SIGN & SEAL PLANS.
 3)- SBC 903.1 APPROVED SPRINKLER PLANS
 WILL BE REQUIRED.
 4)- SBC TABLE 803.3 REFRENCES THE
 MINIMUM INTERIOR FINISH CLASSIFICATION.
  
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-06-24 Cont ID  
Sent By dpalmer Date 2001-06-24 Time 15:26 Rev Time 0.00
Received By dpalmer Date 2001-06-24 Time 15:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By dpalmer Date 2001-06-07 Time 18:06 Rev Time 0.00
Received By dpalmer Date 2001-06-07 Time 18:06 Sent To  
Notes
2001-06-07 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT UNDER F.A.C
 F.S. 481.221 AND 471.025 ALL PLANS THAT
 ARE DONE BY AN ARCH/ENGINEER ARE TO BE
 SIGNED. DATED AND SEALED.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-22 Cont ID  
Sent By mcarsill Date 2001-06-22 Time 12:20 Rev Time 0.00
Received By mcarsill Date 2001-06-22 Time 12:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-22 Cont ID  
Sent By mcarsill Date 2001-05-22 Time 15:41 Rev Time 0.00
Received By mcarsill Date 2001-05-22 Time 15:41 Sent To  
Notes
2001-05-22 00:00:001) PLANS NOT SIGNED AND SEALED BY
 ARCHITECT AS NOTED BY JIM WHITMER OF
 CONSTRUCTION SERVICES.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-26 Cont ID  
Sent By pkrauss Date 2001-06-26 Time 13:45 Rev Time 0.25
Received By pkrauss Date 2001-06-26 Time 13:40 Sent To  
Notes
2001-06-26 00:00:00 
  
 PRIOR TO CONNECTING TO ANY EXISTING DUCT
 WORK, CALL FOR AN INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-08 Cont ID  
Sent By pkrauss Date 2001-06-08 Time 09:38 Rev Time 0.30
Received By pkrauss Date 2001-06-08 Time 09:38 Sent To  
Notes
2001-06-08 00:00:00********************DENIED**************
  
 REFERENCE BUILDING COMMENTS (DATED,
 SIGNED & SEALED DRAWINGS).
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK, CALL FOR AN INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-31 Cont ID  
Sent By pschmitz Date 2001-05-31 Time 14:53 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-31 00:00:00PLUMBING PLAN REVIEW, NO PLBG SHOWN.