Plan Review Stops For Permit 01050945 |
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-05-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-05-30 |
Time |
20:00 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2001-05-30 |
Time |
20:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-05-19 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-05-19 |
Time |
12:43 |
Rev Time |
0.75 |
Received By |
kstevens |
Date |
2001-05-19 |
Time |
12:43 |
Sent To |
|
|
Notes |
2001-05-19 00:00:00 | REVIEW NOTES...FAILED.. | | | | 1) CHART FOR CSST PIPE NOT ACCEPTABLE. | | CHART 305.4F OF SGC-97 MUST BE USED. AND | | 80' OF 1" CSST ONLY ALLOWS FOR 132,000 | | BTU'S. | | | | 2) 1/2" GALV. DROP TO RANGE TO BE SIZED | | AT 3/4". 1/2" ONLY ALLOWS FOR 57,000 BTU | | AT 80'. | | | | RESIZE AND RESUBMIT USING APPROIATE | | CHART AND PIPE. | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | EXT. 8377 |
|
|
|