Plan Review Details - Permit 01050908
Plan Review Stops For Permit 01050908
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-05-23 Cont ID  
Sent By lsmith Date 2001-05-23 Time 16:09 Rev Time 0.50
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-06-14 Cont ID  
Sent By dpalmer Date 2001-06-14 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2001-06-14 Time 15:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-06-04 Cont ID  
Sent By dpalmer Date 2001-06-04 Time 17:31 Rev Time 0.00
Received By dpalmer Date 2001-06-04 Time 17:31 Sent To  
Notes
2001-06-04 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PER F.S. AND
 F.A.C. ALL CHANGES ON SIGNED AND SEALED
 PLANS, NEED TO BE DONE BY THE ENGINEER
 OF RECORD PER 471.025.
 PLEASE HAVE PLANS RE-PRINTED AND SIGNED
 AND SEALED BY ENG OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. PLEASE ALSO NOTE THAT
 THE ORIGINAL APPLICATION AND PLANS NEED
 TO BE PICKED UP ANDSUBMIT ALL TOGETHER
 .
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-22 Cont ID  
Sent By dpalmer Date 2001-05-22 Time 09:57 Rev Time 0.00
Received By dpalmer Date 2001-05-22 Time 09:57 Sent To  
Notes
2001-05-22 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS WERE
 SUBMITTED FOR HEAT PUMP BEING ADDED BUT
 HEAT PUMP WAS NOT INCLUDED ON WIRING
 DIAGRAM? WIRE SIZES ETC.
 2)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED FOR THE
 ADDITION
 OF THE NEW HEAT PUMP AND POOL EQUIPMENT?
  
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 TO INCLUDE ALL NEW LOADS AND SHOW SIZE
 OF EXSITNG SERVICE. 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR'REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 ALSOPLEASE SUBMIT SPEC SHEET FOR
 HEAT PUMP.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-14 Cont ID  
Sent By kstevens Date 2001-06-14 Time 16:29 Rev Time 0.25
Received By kstevens Date 2001-06-14 Time 16:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-22 Cont ID  
Sent By kstevens Date 2001-05-22 Time 14:03 Rev Time 0.25
Received By kstevens Date 2001-05-22 Time 14:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-21 Cont ID  
Sent By sgraham Date 2001-05-21 Time 13:12 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***