Plan Review Details - Permit 01050761
Plan Review Stops For Permit 01050761
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 17:53 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 17:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-06-04 Cont ID  
Sent By dpalmer Date 2001-06-04 Time 21:23 Rev Time 0.00
Received By dpalmer Date 2001-06-04 Time 21:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-01-15 Cont ID  
Sent By pkrauss Date 2002-01-15 Time 08:36 Rev Time 0.45
Received By pkrauss Date 2002-01-15 Time 07:36 Sent To  
Notes
2002-01-15 00:00:00MECHANICAL PERMIT 01050816
  
 CFM DISTRIBUTION ON PLAN EXCEEDS WHAT
 THE EQUIPMENT SCHEDULE REFLECTS ON THE
 CAPACITY OF THE UNIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-05-26 Cont ID  
Sent By hmoser Date 2001-05-26 Time 13:02 Rev Time 0.33
Received By hmoser Date 2001-05-26 Time 13:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-04-22 Cont ID  
Sent By kstevens Date 2002-04-22 Time 10:30 Rev Time 0.00
Received By kstevens Date 2002-04-22 Time 10:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-29 Cont ID  
Sent By kstevens Date 2001-05-29 Time 11:05 Rev Time 0.25
Received By kstevens Date 2001-05-29 Time 11:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2001-12-13 Cont ID  
Sent By jgomez Date 2001-12-13 Time 18:56 Rev Time 0.25
Received By jgomez Date 2001-12-13 Time 18:56 Sent To  
Notes
2001-12-13 00:00:00ROOF FRAMING PLAN REVISION.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-08-21 Cont ID  
Sent By jgomez Date 2001-08-21 Time 15:55 Rev Time 3.50
Received By jgomez Date 2001-08-21 Time 15:55 Sent To  
Notes
2001-08-21 00:00:00APPROVED WITH PROVISO:
  
 1-STORM SHUTTERS INFORMATION STILL IS
 INCOMPLETE. MISSING THE PROPER
 INSTALLATION SCHEDULE.
 -APPLY FOR SEPARATE PERMIT.
  
 2-PROVIDE LEGIBLE DRAWINGS FOR
 STRUCTURAL MULLIONS PRODUCT APPROVAL.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-07-13 Cont ID  
Sent By jgomez Date 2001-07-12 Time 17:39 Rev Time 2.50
Received By jgomez Date 2001-07-12 Time 17:39 Sent To  
Notes
2001-07-12 00:00:00SECOND CHECKLIST:
 1-STORM SHUTTERS INFORMATION STILL IS
 INCOMPLETE. MISSING KEY PLAN AND
 PROPER INSTALLATION SCHEDULE.
 -PROVIDE COMPLETE INFORMATION OR APPLY
 UNDER A SEPARATE PERMIT.
 2-PROVIDE NOTICE OF COMMENCEMENT.
 3-OWES $275.92 FOR LOW VALUATION. PLEASE
 PAY ATTACHED RECEIPT.
 4-SEE PLANS FOR COMMENTS AND CORRECT AS
 REQUIRED. PLEASE RETURN REVIEWED SET
 AFTER CORRECTIONS ARE DONE IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.
 5-PROVIDE PRODUCT APPROVAL FOR:
 A)DOUBLE ENTRY DOORS AS SHOWN ON PLANS.
 B)FRENCH DOORS WITH SIDELITES & TRANSOM
 ABOVE SINGLE ASSEMBLY AS SHOWN ON
 PLANS.
 C)FRENCH DOORS W/ TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 D)MULLIONS FOR HORIZONTAL ASSEMBLIES.
 PRODUCT APPROVAL SUBMITTED IS FOR
 VERTICAL APPLICATIONS ONLY.
 E)GARAGE "OUTSWING" SIDE DOORS. PRODUCT
 APPROVAL SUBMITTED IS FOR "INSWING".
  
 NOTE: PRODUCT APPROVAL PACKAGE SUBMITTED
 IS THE SAME THAT WAS SUBMITTED BEFORE.
 COMMENTS FROM MY PREVIOUS CHECKLIST WERE
 NOT ADDRESSED.
  
 6-UPDATE:
 A)RINKER LETTER FOR MASONRY UNITS.
 B)ENGINEERING SPECS FOR PRECAST LINTELS
 SIGNED, SEALED AND DATED AS REQUIRED
 BY CHAPTER 471 OF FLORIDA STATUTES.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-06-22 Cont ID  
Sent By jgomez Date 2001-06-22 Time 13:38 Rev Time 3.00
Received By jgomez Date 2001-06-22 Time 13:38 Sent To  
Notes
2001-06-22 00:00:00CHECKLIST:
 1-PROVIDE NOTICE OF COMMENCEMENT.
 2-SIZE OF ATTIC ACCESS IS 22"X36" MIN.
 SEC. 2309.6 SBC 1997. REVISE NOTE #7
 ON SHEET A-2.
 3-CLEARLY INDICATE SAFETY GLASS WHERE
 REQUIRED. SEE PLANS FOR COMMENTS.
 SEC. 2405.2 SBC 1997.
 4-PROVIDE COMPLETE DETAIL AND SPECS FOR
 FRAMING OF ARCHED OPENINGS. SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 5-OWES $275.92 FOR LOW VALUATION
 DECLARED IN APPLICATION AND RADON FEES
 6-UPDATE ALL DRAWINGS AS REQUIRED. SEE
 COMMENTS ON PLANS.
 7-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS OR APPLY FOR A SEPARATE PERMIT.
 8-PROVIDE PRODUCT APPROVALS FOR:
 A)DOUBLE ENTRY DOORS AS SHOWN ON PLANS.
 B)FRENCH DOORS WITH SIDELITES & TRANSOM
 ABOVE AS A SINGLE ASSEMBLY AS SHOWN ON
 PLANS.
 -FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 C)MULLIONS FOR HORIZONTAL ASSEMBLIES.
 PRODUCT APPROVAL SUBMITTED IS FOR
 VERTICAL APPLICATIONS ONLY.
 D)GARAGE SIDE DOOR.
  
 9)UPDATE:
 A)RINKER LETTER FOR MASONRY UNITS.
 B)ENGINEERING SPECS FOR PRECAST LINTELS
 SIGNED, SEALED AND DATED AS REQUIRED
 BY CHAPTER 471 OF FLORIDA STATUTES.
  
 NOTES:
 -PLEASE RETURN REVIEWED SETS AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.
 -IF YOU HAVE ANY QUESTIONS PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-25 Cont ID  
Sent By sgraham Date 2001-05-25 Time 08:08 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***