Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-05-22 Cont ID  
Sent By pkrauss Date 2001-05-22 Time 09:19 Rev Time 0.40
Received By pkrauss Date 2001-05-22 Time 09:18 Sent To  
Notes
2001-05-22 00:00:00******************PROVISO***************
  
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS
 PER 1997 SMC 406.1, WITH NOTIFICATION
 TO ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS (NFPA 90A 4-4.4.3).
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.