Plan Review Details - Permit 01050665
Plan Review Stops For Permit 01050665
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-02 Cont ID  
Sent By jwitmer Date 2001-07-02 Time 18:54 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By jwitmer Date 2001-06-07 Time 06:43 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-07 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01050665
 2000 PALM BEACH LAKES
 SUITE #500
 LEIGHTON MC GINN
 863-4455
 NOTE:
 THE CITY OF WEST PALM BEACH IS CURRENTLY
 USING THE 1997 STANDARD BUILDING CODE.
 FLORIDA STATE LAW WILL MANDATE THE NEW
 FLORIDA CODE WILL GO INTO EFFECT JANUARY
 1/ 2002.
  
 1)- SBC 803.3.1 INTERIOR FINISH REQUIRE-
 MENTS BASED ON OCUPANCY, SEE SBC TABLE
 803.3. FULLY SPRINKLERED BUILDING.
  
 2)- TYPE II & TYPE I TO BE FULLY SPRINK-
 LERED. SBC 903.1. APPROVED EQUIPMENT &
 LAYOUTARE REQUIRED BEFORE A BUILDING
 PERMIT MAY BE ISSUED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 659-8096 EX 8412.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-06-15 Cont ID  
Sent By dpalmer Date 2001-06-15 Time 14:51 Rev Time 0.00
Received By dpalmer Date 2001-06-15 Time 14:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-15 Cont ID  
Sent By dpalmer Date 2001-05-15 Time 17:09 Rev Time 0.00
Received By dpalmer Date 2001-05-15 Time 16:55 Sent To  
Notes
2001-05-15 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY SERVICE. THERE
 ARE PARTS OF RISER DIAGRAM THAT IS
 SHOWN AS EXISTING? METERCAN AND FEEDERS?
 YET PANELS AND TRANSFORMER ??
 IF NEW EQUIPMENT IS BEING INSTALLED,
 PLEASE CLARIFY.
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 IF THE EQUIPMNET IS NEW THEN PLANS MUST
 ALSO BE SIGNED AND SEALED BY AN P.E.
 PER 553-79-6A UNDER THE F.A.C.
  
 2)NOTE: PLEASE CLARIFY CIRCUIT#`S FOR
 NEW LIGHTING SHOWN?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 CLARIFICATION. IF THERE ARE ANY QUESTION
 -S, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-20 Cont ID  
Sent By mcarsill Date 2001-06-20 Time 16:38 Rev Time 0.00
Received By mcarsill Date 2001-06-20 Time 16:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-14 Cont ID  
Sent By mcarsill Date 2001-05-14 Time 16:25 Rev Time 0.00
Received By mcarsill Date 2001-05-14 Time 16:25 Sent To  
Notes
2001-05-14 00:00:001) IT APPEARS THAT NOT ENOUGH EMERGENCY
 LIGHT FIXTURES ARE PRESENT WITHIN THE
 SPACE. PLEASE PROVIDE ADDITIONAL
 EMERGENCY LIGHT FIXTURES FOR THE TENANT
 SPACE.
 2) NO INTERIOR FINISH INFORMATION FOR
 WALLS AND CEILINGS PROVIDED WITH PLANS.
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-03 Cont ID  
Sent By pkrauss Date 2001-07-03 Time 07:39 Rev Time 0.30
Received By pkrauss Date 2001-07-03 Time 07:39 Sent To  
Notes
2001-07-03 00:00:00 
 NOTE:FAN SHUTDOWN WITH NOTIFICATION TO
 ALARM/STROBE OR BUILDING ALARM
 SYSTEM. (NFPA 90A 4-4.4.3 & 4-4.4
 .2)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-04 Cont ID  
Sent By pkrauss Date 2001-06-04 Time 12:57 Rev Time 0.35
Received By pkrauss Date 2001-06-04 Time 12:56 Sent To  
Notes
2001-06-04 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 NO COMBUSTIBLES ABOVE CEILING IN RETURN
 AIR PLENUM (1997 SMC 609.1.1).
  
 FIRE DAMPERS SHALL COMPLY WITH UL 555
 AND SHALL BEAR LABLE OF APPROVED
 TESTING AGENCY (1997 SMC 610.1.1).
  
 NOTE:PRIOR TO CONNECTING TO ANY
 EXISTING DUCTWORK, CALL FOR AN
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-30 Cont ID  
Sent By jleech Date 2001-06-30 Time 07:55 Rev Time 0.50
Received By jleech Date 2001-06-30 Time 07:55 Sent To  
Notes
2001-06-30 00:00:001.DRAINAGE PIPING SHALL BE CAST IRON OR
 DWV COPPER WITH A MINIMUM OF 1/4"
 PITCH PER FOOT.