2001-06-07 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01050665 | | 2000 PALM BEACH LAKES | | SUITE #500 | | LEIGHTON MC GINN | | 863-4455 | | NOTE: | | THE CITY OF WEST PALM BEACH IS CURRENTLY | | USING THE 1997 STANDARD BUILDING CODE. | | FLORIDA STATE LAW WILL MANDATE THE NEW | | FLORIDA CODE WILL GO INTO EFFECT JANUARY | | 1/ 2002. | | | | 1)- SBC 803.3.1 INTERIOR FINISH REQUIRE- | | MENTS BASED ON OCUPANCY, SEE SBC TABLE | | 803.3. FULLY SPRINKLERED BUILDING. | | | | 2)- TYPE II & TYPE I TO BE FULLY SPRINK- | | LERED. SBC 903.1. APPROVED EQUIPMENT & | | LAYOUTARE REQUIRED BEFORE A BUILDING | | PERMIT MAY BE ISSUED. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | 659-8096 EX 8412. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-06-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-06-15 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-06-15 |
Time |
14:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-05-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-05-15 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-05-15 |
Time |
16:55 |
Sent To |
|
|
Notes |
2001-05-15 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE CLARIFY SERVICE. THERE | | ARE PARTS OF RISER DIAGRAM THAT IS | | SHOWN AS EXISTING? METERCAN AND FEEDERS? | | YET PANELS AND TRANSFORMER ?? | | IF NEW EQUIPMENT IS BEING INSTALLED, | | PLEASE CLARIFY. | | PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | IF THE EQUIPMNET IS NEW THEN PLANS MUST | | ALSO BE SIGNED AND SEALED BY AN P.E. | | PER 553-79-6A UNDER THE F.A.C. | | | | 2)NOTE: PLEASE CLARIFY CIRCUIT#`S FOR | | NEW LIGHTING SHOWN? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | CLARIFICATION. IF THERE ARE ANY QUESTION | | -S, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-06-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-06-20 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-06-20 |
Time |
16:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-05-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-05-14 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-05-14 |
Time |
16:25 |
Sent To |
|
|
Notes |
2001-05-14 00:00:00 | 1) IT APPEARS THAT NOT ENOUGH EMERGENCY | | LIGHT FIXTURES ARE PRESENT WITHIN THE | | SPACE. PLEASE PROVIDE ADDITIONAL | | EMERGENCY LIGHT FIXTURES FOR THE TENANT | | SPACE. | | 2) NO INTERIOR FINISH INFORMATION FOR | | WALLS AND CEILINGS PROVIDED WITH PLANS. | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-07-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-07-03 |
Time |
07:39 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2001-07-03 |
Time |
07:39 |
Sent To |
|
|
Notes |
2001-07-03 00:00:00 | | | NOTE:FAN SHUTDOWN WITH NOTIFICATION TO | | ALARM/STROBE OR BUILDING ALARM | | SYSTEM. (NFPA 90A 4-4.4.3 & 4-4.4 | | .2) |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-06-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-06-04 |
Time |
12:57 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2001-06-04 |
Time |
12:56 |
Sent To |
|
|
Notes |
2001-06-04 00:00:00 | *******************DENIED*************** | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | AS PER ASHRAE 62-89. | | | | NO COMBUSTIBLES ABOVE CEILING IN RETURN | | AIR PLENUM (1997 SMC 609.1.1). | | | | FIRE DAMPERS SHALL COMPLY WITH UL 555 | | AND SHALL BEAR LABLE OF APPROVED | | TESTING AGENCY (1997 SMC 610.1.1). | | | | NOTE:PRIOR TO CONNECTING TO ANY | | EXISTING DUCTWORK, CALL FOR AN | | INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-06-30 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-06-30 |
Time |
07:55 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2001-06-30 |
Time |
07:55 |
Sent To |
|
|
Notes |
2001-06-30 00:00:00 | 1.DRAINAGE PIPING SHALL BE CAST IRON OR | | DWV COPPER WITH A MINIMUM OF 1/4" | | PITCH PER FOOT. |
|
|