Plan Review Details - Permit 01050516
Plan Review Stops For Permit 01050516
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-30 Cont ID  
Sent By jwitmer Date 2001-07-30 Time 12:56 Rev Time 1.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-30 00:00:00PROVISO:
 1)- TO COUNTY FOR IMPACT FEES
 2)- RADON FEES $2.44

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-05 Cont ID  
Sent By hpiskura Date 2001-06-05 Time 14:15 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
2001-06-05 00:00:00THE MIAMI DADE PRODUCT ACCEPTANCE #
 99-0716.03 (ROOF TILES) EXPIRED 1/22/01
  
 THE "FLORIDA QUALITY TRUSS" LAYOUT CITES
 110 MPH.WEST PALM BEACH IVOKES ASCE
 7-95 THROUGH THE SBC, WHICH PLACES THE
 CITY IN AN 145 MPH ZONE. REVISE AS
 NECESSARY.
  
 SHOW THE DESIGN LOADS FOR THE FLOOR
 TRUSSES.SEE SBC 1603 & 1604.
  
 WILL THE FLOOR TRUSSES BE TOP CHORD
 BEARING ON THE 2 X 6 LEDGER SUPPORTED
 BY 1/4" TAPCONS 2' O.C.?IF SO PROVIDE
 A STRESS ANALYSIS.SEE SBC 104.2
  
 THE HC RAMP REQUIRES HANDRAILS ON EACH
 SIDE.EDGE PROTECTION.SEE 4.8 OF THE
 FACBC
  
 SHOW THE SAFETY GLAZING IN TH AREA OF
 THE DOOR IN ACCORDANCE WITH SBC
 2405.2.1.
  
 THE DRESSING ROOM IS REQUIRED TO BE HC
 ACCESSIBLE.SEE 4.35 OF THE FACBC
  
 THE OFFICE IS REQUIRED TO BE ON AN
 ACCESSIBLE ROUTE.SEE 4.1.6 (B) FACBC
  
 A PORTION OF THE COUNTER IS REQUIRED TO
 BE ACCESSIBLE. SEE 7.2 (1) FACBC

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-08-07 Cont ID  
Sent By dpalmer Date 2001-08-07 Time 10:18 Rev Time 0.00
Received By dpalmer Date 2001-08-07 Time 10:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-07-31 Cont ID  
Sent By dpalmer Date 2001-07-31 Time 12:03 Rev Time 0.00
Received By dpalmer Date 2001-07-31 Time 12:03 Sent To Z
Notes
2001-07-31 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOTES FROM
 FIRST REVIEW WERE NOT ADDRESSED?
 PLEASE NOTE THAT NO INFORMATION WAS
 SUBMITTED FOR PANEL AND IF EXISTING?
 NEW?
 PLEASE NOTE THAT NO OUTLETS ARE SHOWN
 PER LOCAL AMENDMENTS /PRO SHOP AREA?
 ARE THEY EXSITING?
 IS OUTLET FOR A/C COND UNIT EXISTING?
 309.1 MECH CODE.
  
 PLEASE ADDRESS COMMENTS FROM FIRST AND
 SECOND REVIEWS>
 PLEASE SUBMIT FOR REVIEW AND IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-15 Cont ID  
Sent By dpalmer Date 2001-05-15 Time 19:43 Rev Time 0.00
Received By dpalmer Date 2001-05-15 Time 19:43 Sent To  
Notes
2001-05-15 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE PLANS NEED TO HAVE
 BRANCH CIRCUIT #`S SHOWN AND CORRELATE
 WITH SUBMITTED PANEL SCHEDULE.
  
 2)NOTE: PLEASE SHOW CLARIFICATION ON
 SIZE OF PANEL? EXSITING?
  
 PLEASE PROVIDE THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-07-05 Cont ID  
Sent By mcarsill Date 2001-07-05 Time 17:53 Rev Time 0.00
Received By mcarsill Date 2001-07-05 Time 17:53 Sent To  
Notes
2001-07-05 00:00:001) EMERGENCY LIGHT FIXTURE NOT NEEDED
 IN OFFICE. EMERGENCY LIGHT REQUIRED
 IN PRO-SHOP AREA. EXIT SIGN IN OFFICE
 NOT NEEDED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-14 Cont ID  
Sent By mcarsill Date 2001-05-14 Time 08:31 Rev Time 0.00
Received By mcarsill Date 2001-05-14 Time 08:31 Sent To  
Notes
2001-05-14 00:00:001) STAIR SECTION INDICATES 10" TREADS.
 PLEASE BE ADVISED 11" TREADS ARE
 REQUIRED.
 2) PLEASE INDICATE THE TYPE OF STORAGE
 THAT WILL OCCUR IN THE POOL STORAGE
 AREA.
 3) ELECTRICAL FLOOR PLAN DOES NOT
 INDICATE EXIT SIGNAGE OR EMERGENCY
 LIGHTING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-01-08 Cont ID  
Sent By pkrauss Date 2002-01-08 Time 16:12 Rev Time 0.30
Received By pkrauss Date 2002-01-08 Time 16:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-01-05 Cont ID  
Sent By pkrauss Date 2002-01-05 Time 11:11 Rev Time 0.40
Received By pkrauss Date 2002-01-05 Time 11:11 Sent To  
Notes
2002-01-05 00:00:00 
 NO CFM DISTRIBUTION INDICATED ON PLAN.
  
 WILL CALL ENGINEER MONDAY 1/7/02.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-06 Cont ID  
Sent By pkrauss Date 2001-07-06 Time 14:38 Rev Time 0.45
Received By pkrauss Date 2001-07-06 Time 14:28 Sent To  
Notes
2001-07-06 00:00:00******************PROVISO***************
  
  
 ADDITIONAL MECHANICAL PERMIT REQUIRED
 FOR WALKIN COOLER.PLEASE PROVIDE
 PLANS AND MANUFACTURER DETAILS WITH
 PERMIT APPLICATION.
  
 THE ABOVE NOTE WAS WRITTEN ON PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-04 Cont ID  
Sent By pkrauss Date 2001-06-04 Time 13:18 Rev Time 0.45
Received By pkrauss Date 2001-06-04 Time 13:18 Sent To  
Notes
2001-06-04 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 CONDENSATE SHALL NOT GO TO SANITARY
 WASTE.UNITS 3 TON AND LARGER SHALL GO
 TO EITHER STORM DRAIN OR APPROVED DRY
 WELL.
  
 IF CEILING IS USED AS RETURN AIR
 PLENUM, NO COMBUSTILBLES SHALL BE IN
 THIS SPACE (1997 609.1.1).
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS
 PER 1997 SMC 406.1, WITH NOTIFICATION
 TO ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS AS PER NFPA 90A 4-4.4.3.
  
 PLEASE PROVIDE INFORMATION AS TO WHAT IS
 BEING STORED IN THE "POOL STORAGE" AREA
 AND IS THERE ANY MEANS OF VENTILATION?
  
 NOTE:SHOULD THE WALK-IN COOLER BE A
 PART OF THE RENOVATION/ADDITION,
 AN ADDITIONAL MECHANICAL PERMIT
 AND PLANS WILL BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-06-06 Cont ID  
Sent By hpiskura Date 2001-06-06 Time 08:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2001-06-05 Cont ID  
Sent By hpiskura Date 2001-06-05 Time 14:14 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2001-08-01 Cont ID  
Sent By lsmith Date 2001-08-01 Time 16:16 Rev Time 0.25
Received By lsmith Date   Time   Sent To  
Notes
2001-08-01 00:00:00FOR INTERIOR REMODEL ONLY/ NO ADDITION

Review Stop Z ZONING
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By dpalmer Date 2001-07-31 Time 12:08 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-06-07 00:00:00NEED MINOR AMENDMENT