Plan Review Stops For Permit 01050516 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2001-07-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-07-30 |
Time |
12:56 |
Rev Time |
1.75 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-07-30 00:00:00 | PROVISO: | | 1)- TO COUNTY FOR IMPACT FEES | | 2)- RADON FEES $2.44 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-06-05 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-06-05 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
Z |
|
Notes |
2001-06-05 00:00:00 | THE MIAMI DADE PRODUCT ACCEPTANCE # | | 99-0716.03 (ROOF TILES) EXPIRED 1/22/01 | | | | THE "FLORIDA QUALITY TRUSS" LAYOUT CITES | | 110 MPH.WEST PALM BEACH IVOKES ASCE | | 7-95 THROUGH THE SBC, WHICH PLACES THE | | CITY IN AN 145 MPH ZONE. REVISE AS | | NECESSARY. | | | | SHOW THE DESIGN LOADS FOR THE FLOOR | | TRUSSES.SEE SBC 1603 & 1604. | | | | WILL THE FLOOR TRUSSES BE TOP CHORD | | BEARING ON THE 2 X 6 LEDGER SUPPORTED | | BY 1/4" TAPCONS 2' O.C.?IF SO PROVIDE | | A STRESS ANALYSIS.SEE SBC 104.2 | | | | THE HC RAMP REQUIRES HANDRAILS ON EACH | | SIDE.EDGE PROTECTION.SEE 4.8 OF THE | | FACBC | | | | SHOW THE SAFETY GLAZING IN TH AREA OF | | THE DOOR IN ACCORDANCE WITH SBC | | 2405.2.1. | | | | THE DRESSING ROOM IS REQUIRED TO BE HC | | ACCESSIBLE.SEE 4.35 OF THE FACBC | | | | THE OFFICE IS REQUIRED TO BE ON AN | | ACCESSIBLE ROUTE.SEE 4.1.6 (B) FACBC | | | | A PORTION OF THE COUNTER IS REQUIRED TO | | BE ACCESSIBLE. SEE 7.2 (1) FACBC |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2001-08-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-07 |
Time |
10:18 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-07 |
Time |
10:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2001-07-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-07-31 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-07-31 |
Time |
12:03 |
Sent To |
Z |
|
Notes |
2001-07-31 00:00:00 | ************* UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT NOTES FROM | | FIRST REVIEW WERE NOT ADDRESSED? | | PLEASE NOTE THAT NO INFORMATION WAS | | SUBMITTED FOR PANEL AND IF EXISTING? | | NEW? | | PLEASE NOTE THAT NO OUTLETS ARE SHOWN | | PER LOCAL AMENDMENTS /PRO SHOP AREA? | | ARE THEY EXSITING? | | IS OUTLET FOR A/C COND UNIT EXISTING? | | 309.1 MECH CODE. | | | | PLEASE ADDRESS COMMENTS FROM FIRST AND | | SECOND REVIEWS> | | PLEASE SUBMIT FOR REVIEW AND IF THERE | | ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-05-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-05-15 |
Time |
19:43 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-05-15 |
Time |
19:43 |
Sent To |
|
|
Notes |
2001-05-15 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE PLANS NEED TO HAVE | | BRANCH CIRCUIT #`S SHOWN AND CORRELATE | | WITH SUBMITTED PANEL SCHEDULE. | | | | 2)NOTE: PLEASE SHOW CLARIFICATION ON | | SIZE OF PANEL? EXSITING? | | | | PLEASE PROVIDE THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-07-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-05 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-05 |
Time |
17:53 |
Sent To |
|
|
Notes |
2001-07-05 00:00:00 | 1) EMERGENCY LIGHT FIXTURE NOT NEEDED | | IN OFFICE. EMERGENCY LIGHT REQUIRED | | IN PRO-SHOP AREA. EXIT SIGN IN OFFICE | | NOT NEEDED. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-05-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-05-14 |
Time |
08:31 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-05-14 |
Time |
08:31 |
Sent To |
|
|
Notes |
2001-05-14 00:00:00 | 1) STAIR SECTION INDICATES 10" TREADS. | | PLEASE BE ADVISED 11" TREADS ARE | | REQUIRED. | | 2) PLEASE INDICATE THE TYPE OF STORAGE | | THAT WILL OCCUR IN THE POOL STORAGE | | AREA. | | 3) ELECTRICAL FLOOR PLAN DOES NOT | | INDICATE EXIT SIGNAGE OR EMERGENCY | | LIGHTING. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2002-01-08 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-08 |
Time |
16:12 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2002-01-08 |
Time |
16:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2002-01-05 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-05 |
Time |
11:11 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2002-01-05 |
Time |
11:11 |
Sent To |
|
|
Notes |
2002-01-05 00:00:00 | | | NO CFM DISTRIBUTION INDICATED ON PLAN. | | | | WILL CALL ENGINEER MONDAY 1/7/02. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-07-06 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-07-06 |
Time |
14:38 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-07-06 |
Time |
14:28 |
Sent To |
|
|
Notes |
2001-07-06 00:00:00 | ******************PROVISO*************** | | | | | | ADDITIONAL MECHANICAL PERMIT REQUIRED | | FOR WALKIN COOLER.PLEASE PROVIDE | | PLANS AND MANUFACTURER DETAILS WITH | | PERMIT APPLICATION. | | | | THE ABOVE NOTE WAS WRITTEN ON PLAN. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-06-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-06-04 |
Time |
13:18 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-06-04 |
Time |
13:18 |
Sent To |
|
|
Notes |
2001-06-04 00:00:00 | *******************DENIED*************** | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | AS PER ASHRAE 62-89. | | | | CONDENSATE SHALL NOT GO TO SANITARY | | WASTE.UNITS 3 TON AND LARGER SHALL GO | | TO EITHER STORM DRAIN OR APPROVED DRY | | WELL. | | | | IF CEILING IS USED AS RETURN AIR | | PLENUM, NO COMBUSTILBLES SHALL BE IN | | THIS SPACE (1997 609.1.1). | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS | | PER 1997 SMC 406.1, WITH NOTIFICATION | | TO ALARM/STROBE IN NORMALLY OCCUPIED | | AREAS AS PER NFPA 90A 4-4.4.3. | | | | PLEASE PROVIDE INFORMATION AS TO WHAT IS | | BEING STORED IN THE "POOL STORAGE" AREA | | AND IS THERE ANY MEANS OF VENTILATION? | | | | NOTE:SHOULD THE WALK-IN COOLER BE A | | PART OF THE RENOVATION/ADDITION, | | AN ADDITIONAL MECHANICAL PERMIT | | AND PLANS WILL BE REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2001-06-06 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-06-06 |
Time |
08:28 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
N |
Date |
2001-06-05 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-06-05 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2001-08-01 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-08-01 |
Time |
16:16 |
Rev Time |
0.25 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-08-01 00:00:00 | FOR INTERIOR REMODEL ONLY/ NO ADDITION |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2001-06-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-07-31 |
Time |
12:08 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-06-07 00:00:00 | NEED MINOR AMENDMENT |
|
|