Plan Review Details - Permit 01050329
Plan Review Stops For Permit 01050329 |
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2001-08-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-08-03 |
Time |
07:52 |
Rev Time |
0.25 |
Received By |
kstevens |
Date |
2001-08-03 |
Time |
07:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2001-07-12 |
|
|
Cont ID |
|
Sent By |
sjohnson |
Date |
2001-07-12 |
Time |
11:11 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-07-12 |
Time |
11:08 |
Sent To |
|
|
Notes |
2001-07-12 00:00:00 | APPROVED PER KEN STEVENS |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2001-06-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-06-21 |
Time |
08:51 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-06-21 |
Time |
08:51 |
Sent To |
|
|
Notes |
2001-06-21 00:00:00 | REVIEW NOTES:FAILED | | | | 1) 20 PSI NOT APPROVED IN RESIDENTIAL | | APPLICATION. PLEASE FURNISH DELIVERY | | PRESSURE PER #7 OF THE GAS PERMIT | | APPLICATION REQUIREMENTS. | | | | 2) INFORMATION ON FIREPLACE FROM TWO | | DIFFERENT MANUFACTURES. PLEASE SUPPLY | | COMPLETE INFORMATION FOR FIREPLACE TO BE | | INSTALLED. | | | | 3) PLEASE INDICATE WHICH ROOM THE FIRE- | | PLACE WILL BE LOCATED, AND GIVE COMBUST- | | ION AND VENTILATION AIR CALCULATIONS FOR | | ROOM AS SHOWN ON PAGE 3 OF THE INSTALLA- | | TION INSTRUCTIONS. | | | | 4) PLEASE FURNISH DETAILS OF THE INTEG- | | RAL OUTSIDE AIR INTAKE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2001-06-11 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-06-11 |
Time |
13:17 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-06-11 |
Time |
13:17 |
Sent To |
|
|
Notes |
2001-06-11 00:00:00 | REVIEW NOTES: FAILED | | | | 1) INDICATE NATURAL OR L/P GAS. | | | | 2) PSI INDICATED IS 20 PSI. IF THIS IS | | A 2 PSI SYSTEM, REGULATORS ARE NOT SHOWN | | FOR SECOND STAGE PRESSURE. | | | | 3) COPY OF APPROIATE GAS SIZING TABLES | | ARE REQUIRED. | | | | 4) PLEASE INDICATE WHICH MODEL FIREPLACE | | AND SHOW WHERE THE BTU RATING IS LOCATED | | | | 5) INDICATE IN WHICH ROOM THE FIREPLACE | | WILL BE LOCATED, AND GIVE COMBUSTION AND | | VENTILATION AIR CALCULATIONS FOR ROOM AS | | SHOWN ON PAGE 3 OF THE INSTALLATION | | INSTRUCTIONS. | | | | 6) RE: 1/2 SHEET FURNISHED WITH FIRE- | | PLACE. PLEASE SUBMIT ALL INFORMATION | | FROM THAT SHEET. | | | | 7) BTU'S FOR GAS GRILL INDICATE ON RISER | | DIAGRAM 60,000 BTU'S, BUT ONLY 40,000 IN | | INSTRUCTION MANUAL. PLEASE CLARIFY. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-05-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-05-14 |
Time |
13:36 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2001-05-14 |
Time |
13:36 |
Sent To |
|
|
Notes |
2001-05-14 00:00:00 | REVIEW NOTES...FAILED... | | | | 1) NOT ENOUGH INFORMATION. SEE GAS | | PERMIT APPLICATION REQUIREMENTS OF JULY | | 12, 2000. INFORMATION STILL NEEDED | | MARKED ON REQUIREMENT FORM. | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | EXT. 8377 |
|
|
|