Plan Review Details - Permit 01050329
Plan Review Stops For Permit 01050329
Review Stop P PLUMBING
Rev No 5 Status P Date 2001-08-03 Cont ID  
Sent By kstevens Date 2001-08-03 Time 07:52 Rev Time 0.25
Received By kstevens Date 2001-08-03 Time 07:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-07-12 Cont ID  
Sent By sjohnson Date 2001-07-12 Time 11:11 Rev Time 0.50
Received By kstevens Date 2001-07-12 Time 11:08 Sent To  
Notes
2001-07-12 00:00:00APPROVED PER KEN STEVENS

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-06-21 Cont ID  
Sent By kstevens Date 2001-06-21 Time 08:51 Rev Time 0.50
Received By kstevens Date 2001-06-21 Time 08:51 Sent To  
Notes
2001-06-21 00:00:00REVIEW NOTES:FAILED
  
 1) 20 PSI NOT APPROVED IN RESIDENTIAL
 APPLICATION. PLEASE FURNISH DELIVERY
 PRESSURE PER #7 OF THE GAS PERMIT
 APPLICATION REQUIREMENTS.
  
 2) INFORMATION ON FIREPLACE FROM TWO
 DIFFERENT MANUFACTURES. PLEASE SUPPLY
 COMPLETE INFORMATION FOR FIREPLACE TO BE
 INSTALLED.
  
 3) PLEASE INDICATE WHICH ROOM THE FIRE-
 PLACE WILL BE LOCATED, AND GIVE COMBUST-
 ION AND VENTILATION AIR CALCULATIONS FOR
 ROOM AS SHOWN ON PAGE 3 OF THE INSTALLA-
 TION INSTRUCTIONS.
  
 4) PLEASE FURNISH DETAILS OF THE INTEG-
 RAL OUTSIDE AIR INTAKE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-06-11 Cont ID  
Sent By kstevens Date 2001-06-11 Time 13:17 Rev Time 0.50
Received By kstevens Date 2001-06-11 Time 13:17 Sent To  
Notes
2001-06-11 00:00:00REVIEW NOTES: FAILED
  
 1) INDICATE NATURAL OR L/P GAS.
  
 2) PSI INDICATED IS 20 PSI. IF THIS IS
 A 2 PSI SYSTEM, REGULATORS ARE NOT SHOWN
 FOR SECOND STAGE PRESSURE.
  
 3) COPY OF APPROIATE GAS SIZING TABLES
 ARE REQUIRED.
  
 4) PLEASE INDICATE WHICH MODEL FIREPLACE
 AND SHOW WHERE THE BTU RATING IS LOCATED
  
 5) INDICATE IN WHICH ROOM THE FIREPLACE
 WILL BE LOCATED, AND GIVE COMBUSTION AND
 VENTILATION AIR CALCULATIONS FOR ROOM AS
 SHOWN ON PAGE 3 OF THE INSTALLATION
 INSTRUCTIONS.
  
 6) RE: 1/2 SHEET FURNISHED WITH FIRE-
 PLACE. PLEASE SUBMIT ALL INFORMATION
 FROM THAT SHEET.
  
 7) BTU'S FOR GAS GRILL INDICATE ON RISER
 DIAGRAM 60,000 BTU'S, BUT ONLY 40,000 IN
 INSTRUCTION MANUAL. PLEASE CLARIFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-14 Cont ID  
Sent By kstevens Date 2001-05-14 Time 13:36 Rev Time 0.33
Received By kstevens Date 2001-05-14 Time 13:36 Sent To  
Notes
2001-05-14 00:00:00REVIEW NOTES...FAILED...
  
 1) NOT ENOUGH INFORMATION. SEE GAS
 PERMIT APPLICATION REQUIREMENTS OF JULY
 12, 2000. INFORMATION STILL NEEDED
 MARKED ON REQUIREMENT FORM.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377