Plan Review Details - Permit 01050082
Plan Review Stops For Permit 01050082
Review Stop E ELECTRICAL
Rev No 3 Status   Date   Cont ID  
Sent By rmcdouga Date 2001-11-06 Time 10:50 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-11-06 00:00:00OK PER D. PALMER 11-6-01 RM

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-29 Cont ID  
Sent By dpalmer Date 2001-10-29 Time 21:29 Rev Time 0.00
Received By dpalmer Date 2001-10-29 Time 21:29 Sent To  
Notes
2001-10-29 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ONLY ONE
 COPY WAS SUBMITTED. PLEASE SUBMIT TWO.
  
 2)NOTE: PLEASE NOTE OUTLETS SHOWN FOR
 KITCHEN COUNTERSPACE NEED TO BE SHOWN
 AS GFI/GFI PROTECTED. 210-8-A-6.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-05-23 Cont ID  
Sent By dpalmer Date 2001-05-23 Time 07:27 Rev Time 0.00
Received By dpalmer Date 2001-05-23 Time 07:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-10-30 Cont ID  
Sent By pkrauss Date 2001-10-30 Time 14:28 Rev Time 0.35
Received By pkrauss Date 2001-10-30 Time 14:08 Sent To  
Notes
2001-10-30 00:00:00 
 PLANS ARE NOT SEALED BY ENGINEER OF
 RECORD.
  
 DRYER VENT LOCATION SIZE OR OF VENT NOT
 INDICATED ON PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-11 Cont ID  
Sent By pkrauss Date 2001-06-11 Time 14:27 Rev Time 0.35
Received By pkrauss Date 2001-06-11 Time 14:11 Sent To  
Notes
2001-06-11 00:00:00RESUBMITAL-CHANGED 1.5 TON TO 3 TON
 UNIT.ALSO ADDED CFM THAT
 WAS MISSING FROM DROP IN
 BEDROOM 2.
  
 APPROVED 6/11/01PHK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-05-19 Cont ID  
Sent By hmoser Date 2001-05-19 Time 14:04 Rev Time 0.50
Received By hmoser Date 2001-05-19 Time 14:05 Sent To  
Notes
2001-05-19 00:00:00A/C #2 WRONG SIZE 1225CFM 1.50 TON A/C
 DROP IN BEDROOM #2 NO GRILL SIZE OR CFM

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-07 Cont ID  
Sent By kstevens Date 2001-05-07 Time 11:06 Rev Time 0.25
Received By kstevens Date 2001-05-07 Time 11:06 Sent To  
Notes
2001-05-07 00:00:00REVIEW NOTES. PASSED
  
 *****PROVISO*****
  
 SANITARY RISER DIAGRAM DOES NOT COMPLY
 WITH CODE SPC-94 913.2. SUBMIT SANITARY
 RISER DIAGRAM WITH CORRECTONS.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2001-11-06 Cont ID  
Sent By rmcdouga Date 2001-11-06 Time 10:48 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-11-06 00:00:00REVISION OK 11-6-01 RM

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-11-02 Cont ID  
Sent By rmcdouga Date 2001-11-02 Time 16:48 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-11-02 00:00:00REVISION DENIED
 - REVISED SHEETS A-2 ARE REQUIRED TO BE
 SIGNED, SEALED AND DATED BY THE DESIGNER
 OF RECORD (ENGINEER).

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-06-13 Cont ID  
Sent By rmcdouga Date 2001-06-13 Time 12:33 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-06-13 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GLASS BLOCK;(THE INFORMATION SUBMITTED
 IS NOT ACCEPTABLE.)
  
 2) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS PRIOR TO
 INSTALLATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-06-06 Cont ID  
Sent By rmcdouga Date 2001-06-06 Time 13:28 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-06-06 00:00:00*************BUILDING UNSAT*************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR WINDOWS
 - EXTERIOR DOORS
 - GARAGE DOOR
 - STORM PANELS
 - GLASS BLOCK
  
 2) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 3) PROVIDE SOIL TEST PER SEC. 1804.2.2
 OF CITY AMENDMENTS TO 1997 SBC.
  
 4) PROVIDE ENERGY CALCULATIONS AND
 MANUAL "J" CALCULATIONS PER 97 FLORIDA
 ENERGY CODE FOR BUILDING CONSTRUCTION.
  
 5) WALL SECTIONS 4&5 ON A-6 INDICATE
 R-13 INSULATION AND THE FLOOR PLAN ON
 A-2 INDICATES R-11 INSULATION PLEASE
 CORRECT.
  
 6) THE SCALES GIVEN FOR THE ELEVATIONS
 ON A-3 ARE INCORRECTLY LISTED AS 1/8" =
 1'-0". PLEASE CORRECT.
  
 7) PROVIDE CONSTRUCTION DETAILS FOR ARCH
 OPENINGS IN EXTERIOR WALLS.
  
 8) PROVIDE DESIGN COMPLIANCE FORM TO
 INDICATE THE DESIGN PARAMETERS AND
 ASSUMPTIONS USED FOR THIS STRUCTURE.
  
 9) SPACING OF VERTICLE WALL REINFORCE-
 MENT DOES NOT COMPLY WITH SSTD 10-97.
 PEASE REVIEW AND CORRECT, IF USING THE
 PRESCRIPTIVE METHOD OF DESIGN COMPLIANCE
  
 10) PROVIDE DESIGN PARAMETERS AND
 ASSUMPTIONS USED TO DETERMINE FORCES AND
 REACTIONS APPLIED TO ROOF TRUSSES AND
 GIRDERS.
  
 11) INDICATE THE TRUSS CONNECTORS THAT
 WILL BE USED ON THE TRUSSES THAT ARE NOT
 SPECIFICALLY INDICATED ON PLANS.
  
 12) INDICATE MEAN ROOF HEIGHT ON PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-03 Cont ID  
Sent By sgraham Date 2001-05-03 Time 10:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***