Plan Review Stops For Permit 01041207 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-04-26 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-04-26 |
Time |
14:27 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2001-04-26 |
Time |
14:23 |
Sent To |
|
|
Notes |
2001-04-26 00:00:00 | ******************PROVISO*************** | | | | AS PER REVIEW ON BUILDING PERMIT | | #01020747: | | | | DUCT SMOKE DETECTORS SHALL BE TESTED. | | (NFPA 90A 4-4.4.1) | | | | FAN SHUTDOWN WITH NOTIFICATION TO | | ALARM/STROBE.(NFPA 90A 4-4.4.3) |
|
|
|