Plan Review Details - Permit 01041098
Plan Review Stops For Permit 01041098
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-04-24 Cont ID  
Sent By mamini Date 2001-04-24 Time 13:57 Rev Time 0.50
Received By mamini Date 2001-04-24 Time 13:54 Sent To  
Notes
2001-04-24 00:00:00PASSED:
 APPROVED FOR FIRE LINE CONNECTIONS.
 IF ANY QUESTION PLEASE CONTACT 659- 8096
 EXT. 8492

Review Stop FS  
Rev No 1 Status P Date 2001-04-24 Cont ID  
Sent By mcarsill Date 2001-04-24 Time 13:25 Rev Time 0.00
Received By mcarsill Date 2001-04-24 Time 13:25 Sent To  
Notes
2001-04-24 00:00:001) A SPARE HEAD BOX IS TO BE PROVIDED.
 2) FIRE DEPARTMENT CONNECTION IS TO BE
 NO MORE THAN 150 FEET FROM A FIRE
 HYDRANT.
 3) PORCH C12 AND C13 ARE TO BE
 PROTECTED.
 4) EXISTING BACKFLOW DEVICE IS TO BE
 CHAINED AND LOCKED WITH TAMPER SWITCHES
 SINCE NO INDICATING VALVES ARE PRESENT
 AT THE BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910