Plan Review Stops For Permit 01041098 |
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2001-04-24 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-04-24 |
Time |
13:57 |
Rev Time |
0.50 |
Received By |
mamini |
Date |
2001-04-24 |
Time |
13:54 |
Sent To |
|
|
Notes |
2001-04-24 00:00:00 | PASSED: | | APPROVED FOR FIRE LINE CONNECTIONS. | | IF ANY QUESTION PLEASE CONTACT 659- 8096 | | EXT. 8492 |
|
|
Review Stop |
FS |
|
Rev No |
1 |
Status |
P |
Date |
2001-04-24 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-04-24 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-04-24 |
Time |
13:25 |
Sent To |
|
|
Notes |
2001-04-24 00:00:00 | 1) A SPARE HEAD BOX IS TO BE PROVIDED. | | 2) FIRE DEPARTMENT CONNECTION IS TO BE | | NO MORE THAN 150 FEET FROM A FIRE | | HYDRANT. | | 3) PORCH C12 AND C13 ARE TO BE | | PROTECTED. | | 4) EXISTING BACKFLOW DEVICE IS TO BE | | CHAINED AND LOCKED WITH TAMPER SWITCHES | | SINCE NO INDICATING VALVES ARE PRESENT | | AT THE BUILDING. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
|