Plan Review Stops For Permit 01041075 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2001-10-30 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-10-30 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-10-30 00:00:00 | IMPACT FEES, RESIDENT INSPECTOR REQUIRED |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2001-08-02 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-08-02 |
Time |
08:26 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2001-08-01 |
Time |
14:20 |
Sent To |
|
|
Notes |
2001-08-02 00:00:00 | SHEET S1 OF THE PUBLIX PLANS DESIGN | | CRITERIA CALLS OUT CONFLICTING | | INFORMATION FOR THE WIND.SEE SBC | | 1606.1.2.1 RE: MIXING OF WINDLOADS. | | THE ENTIRE BUILDING, INCLUDING THE | | RETAIL WINGS, MUST BE DESIGNED TO ONE | | STANDARD.EITHER ASCE 7-95 OR SBC | | 1606.2.WEST PALM BEACH IS IN THE 140 | | MPH VELOCITY ZONE FOR ASCE 7-95 AND 110 | | MPH FOR SBC 1606.2. NOT THE 100 MPH | | DECLARED. | | | | PLEASE INCLUDE CALCULATIONS | | DEMONSTRATING COMPLIANCE WITH ONE OF | | THE ABOVE.ALSO WHICH IS THE DESIRED | | SOIL BEARING PRESSURE,2000 PSF OR 2500 | | PSF? | | | | THE FP1 HAS A STATEMENT THAT SAYS SEE | | THE ARCHITECTURAL PLANS FOR THE CANOPY | | SPRINKLER DESIGN.THE ARCHITECTURAL | | PLANS DO NOT SHOW ANY FIRE SPRINKLER | | DESIGN. | | | | NFPA 13 SS 4-5.7.1 REQUIRES SPRINKLERS | | FOR THIS APPLICATION AND CHP. | | 61G15-32.003 COMMON REQUIREMENTS TO ALL | | FIRE PROTECTION ENGINEERING DOCUMENTS | | FBPE,SET OUT SPECIFIC INFORMATION FOR | | DOCUMENT SUBMITTAL.PLEASE REVISE AS | | NECESSARY. | | | | PLEASE INDICATE THE PORTIONS OF THE | | BILDING THAT WILL HAVE HURRICANE | | SHUTTERS AND WHICH WILL HAVE IMPACT | | RESISTANT GLASS? | | | | SEE THE PREVIOUS CHECKLISTS REGARDING | | IMPACT FEES AND A RESIDENT INSPECTOR. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2001-07-12 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-07-12 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-07-12 00:00:00 | WHAT IS THE 11' STRUCTURE ON THE WEST | | WALL NEAR THE TRASH COMPACTOR?IT IS | | SHOWN ON THE SITE PLAN AND THE CIVIL | | PLANS.THERE ARE NO CONSTRUCTINON | | DETAILS SHOWN FOR THIS PROJECTION.IF | | IT IS A PORTION OF THE BUILDING AND THE | | DISTANCE TO THE PROPERTY LINE IS LESS | | THAN 40' THAN THE UNLIMITED AREA | | EXCEPTION IS NOT APPLICABLE.IF IT IS | | AN OPEN LOADING DOCK, SHOW THE DETAILS. | | | | | | SHEET A0.1 CITES THE SFBC 514.2(B). | | THEBUILDING NEEDS TO COMPLY WITH SBC | | 503.4.THIS IS THE STANDARD BUILDING | | CODE NOT | | THE SOUTH FLORIDA BUILDING CODE. | | | | THE FLOOR PLAN ON SHEET A2.1 IS | | INADEQUATE TO DETERMINE EGRESS | | REQUIREMENTS. | | | | THE MAY 10, CHECKLIST IS INCLUDED FOR | | REFERENCE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-05-10 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-05-10 |
Time |
15:42 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2001-05-08 |
Time |
08:57 |
Sent To |
|
|
Notes |
2001-05-10 00:00:00 | INDICATE CLEARLY ON THE SITE PLAN THE | | DISTANCE TO THE WEST PROPERTY LINE | | | | THE 3 HOUR RATED WALL REQUIRES 3 HOUR | | RATED OPENEINGS. | | | | SHOW A SPECIFIC FIRE DESIGN NUMBER FOR | | THE FIRE RATED WALL. | | | | WHAT IS THE NET CLEAR OPENING OF THE | | STOREFRONT DOORS? | | | | SHEET S1 SHOWS 7-93.SBC 97 INVOKES | | ASCE 7-95. | | | | SHOW THE HURRICANE MISSILE IMPACT | | PROTECTION. | | | | IMPACT FEES MUST BE PAID TO THE COUNTY. | | CALL 233-5025 FOR MORE INFORMATION. | | | | PROVIDE THE TEST DATA AND REPORTS FOR | | THE DOORS WINDOWS AND THE ROOF COVERING. | | | | PROVIDE A RECENT PROPERTY SURVEY. | | | | A RESIDENT INSPECTOR IS REQUIRED. | | CONTACT DON NEELY 561-659-8096 X 8333 | | FOR MORE INFORMATION. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2003-02-25 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-07 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-02-25 |
Time |
17:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2002-09-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-09-16 |
Time |
06:19 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2002-09-16 |
Time |
06:19 |
Sent To |
|
|
Notes |
2002-09-16 00:00:00 | *********** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE REVISIONS NOTED ON | | PLANS DO NOT SHOW THE REVISIONS DONE | | BETWEEN THE LAST SET WAS SUBMITTED AND | | NOW. PLANS ARE SHOWING SPACES THAT HAVE | | REVISIONS TO THEM WHEN THE PLANS ON | | RECORD DO NOT SHOW THOSE SPACE BEING | | FITTED UP? | | PLEASE ALSO SEE ANY BUILDING REVIEW | | COMMENTS FORBUILD OUT OF SPACES UNDER | | A SHELL PERMIT? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | | | PLEASE NOTE REVIEW NOTES TYPED UNDER | | THIS MAIN # FORREVISIONS TO #`S | | 01041078,01041079. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2001-12-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-12-12 |
Time |
17:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-12-12 |
Time |
17:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-08-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-14 |
Time |
20:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-14 |
Time |
20:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-05-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-05-14 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-05-14 |
Time |
16:26 |
Sent To |
|
|
Notes |
2001-05-14 00:00:00 | ***************** UNSAT**************** | | | | 1)NOTE: PLEASE NOTE THAT THERE IS A | | PERMIT APPLICATION FOR BLDG "D" BUT CAN' | | T FIND BLDG"D PLANS. PLEASE CLARIFY. | | | | 2)NOTE: PLEASE NOTE THAT ELECTRICAL | | DRAWING HAVE PASSED ELEC REVIEW, BUT | | HAVE NOTICED THAT FIRE REVIEW HAVE | | FAILED AND MIGHT AFFECT ELECTRICAL | | DRAWINGS. ELECTRICAL DRAWINGS WILL | | BE STAMPED PENDING NO CHANGES AND | | CLARIFICATION ON BLDG "D" PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
P |
Date |
2002-05-02 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-05-02 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
mamini |
Date |
2002-05-02 |
Time |
14:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
F |
Date |
2001-08-15 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-08-15 |
Time |
11:32 |
Rev Time |
5.00 |
Received By |
mamini |
Date |
2001-08-15 |
Time |
11:01 |
Sent To |
|
|
Notes |
2001-08-15 00:00:00 | FAILED: | | ***NOTES*** | | REVIEW COMMENTS APPLY TO PERMITS | | # 01041078 | | # 01041079 | | # 01041080 | | | | 1. PLEASE PROVIDE THE STATUS OF APPROVAL | | FROM THE SFWMD & DEP IN REGARDS TO THIS | | PROJECT. | | 2. PLEASE PROVIDE THE STATUS OF THE | | AGREEMENTS WITH THE CITY OF WEST PALM | | BEACH CONCERNING THE PROPOSED POND FOR | | OFF-SITE DISCHARGE. | | | | ABOVE MENTIONED ISSUES ARE THE ONLY | | ITEMS THAT HOLDING APPROVAL OF THE CIVIL | | PLANS FOR THE ENTIRE SITE AT THE PRESENT | | TIME. | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2001-04-26 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-04-26 |
Time |
15:54 |
Rev Time |
4.00 |
Received By |
mamini |
Date |
2001-04-26 |
Time |
14:45 |
Sent To |
|
|
Notes |
2001-04-26 00:00:00 | FAILED: | | INSUFFICIENT INFORMATION SUBMITTED FOR | | CIVIL ENGINEERING REVIEW.PLEASE | | RESUBMIT WHEN CIVIL PLANS ARE DEVELOPED. | | 2. PERVIOUS & IMPERVIOUS CALCULATION | | MUST BE SHOWN ON PAVING AND DRAINAGE | | PLAN, THE TOTAL AMOUNT MUST BE EQUAL | | 100% OF TOTAL SITE ACRES OR S.F.PLEASE | | STATE EITHER ADDRESS OR PROPERTY CONTROL | | NUMBER.STORM WATER CHARGES WILL BE | | CALCULATED FROM THESE. | | 3. PLEASE PROVIDE STORM WATER | | CALCULATION FOR OUR REVIEW IF YOU HAVE | | NOT SUBMITTED TO JOSE DEL RIO, STORM | | WATER ENGINEER, 1000 45TH STREET WEST | | PALM BEACH, FL 33407. SEE ATTACHED | | 4. PLEASE PROVIDE POLLUTION PREVENTION | | PLAN WHICH INCLUDE TRUCK WASHOUT AT EXIT | | AND COVERAGE FOR DRAINGE,SOIL ERROSION. | | PLAN SHOULD BE INSTALLED IN FIELD PRIOR | | TO ANY EARTH WORK. THE POLLUTION CONTROL | | PLAN SHALL BE KEPTH ON SITE AT ALL TIME | | DURING CONSTRUCTION. | | 5. ONCE REVISED, TWO SETS OF PLANS MUST | | BE SUBMITTED TO PUBLIC UTILITIES | | ENGINEERING SERVICES FOR THEIR REVIEW | | AND ACTUAL SERVICE CONNECTIONS. | | 6. WORK PERFORMED ALONG PUBLIC R.O.W | | REQUIRES A PERMIT THROUGH CITY ENGINEERS | | OFFICE, RICHARD PITTMAN, 1000 45TH | | STREET WEST PALM BEACH, FL 33407 | | 7. PLEASE PROVIDE DETAILS FOR DUMPSTER | | ENCLOSURES. SHEET 2 OF 2 REFERS TO | | ARCHITECTURAL PALNS FOR DETAILS, NO | | DETAILS FOR ENCLOSURES IS PROVIDED. | | DUMSTERS ENCLOSURES AT MIN. SHOULD BE | | PER CITY OF WPB STANDARD. SEE ATTACHED | | 8. PLEASE COORDINATE WITH PUBLIC | | UTILITIES ENGINEERING SERVICES FOR | | CONNECTION OF ALL SERVICES AND FOR LOCAT | | ION OF BACKFLOW PREVENTERS ,FIRE, WATER | | IRRIGATIONS. | | 9. STANDARD, DETAILS, APPROVED PRODUCT | | LIST COULD BE OBTAIN FROM PUBLIC | | UTILITIES ENGINEERING SERVICES | | DEPARTMENT 1000 45TH STREET WEST PALM | | BEACH, FL 33407561 659-8040 | | ANY QUESTION PLEASE CONTACT 561-659-8096 | | EXT. 8492 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2001-12-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-12-19 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-12-19 |
Time |
14:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-22 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-22 |
Time |
09:06 |
Sent To |
|
|
Notes |
2001-10-22 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED | | ON PLANS, SHOULD READ 1985 EDITION | | INSTEAD OF 1997 EDITION. | | 2) SEPARATE PLANS AND PERMITS REQUIRED | | FOR HOOD,DUCT,AND EXTINGUISHING SYSTEMS. | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | FOR LP GAS INSTALLATION. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
F |
Date |
2001-08-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-20 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-20 |
Time |
12:32 |
Sent To |
|
|
Notes |
2001-08-20 00:00:00 | 1) NO FIRE SPRINKLER SYSTEM DRAWINGS | | OR HYDRAULIC CALCULATIONS PROVIDED | | WITH PLANS. | | 2) STILL MORE DETAILS NEEDED ON PROPANE | | TANK SHOWN ON CIVIL DRAWINGS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2001-08-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-09 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-09 |
Time |
13:27 |
Sent To |
|
|
Notes |
2001-08-09 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | WITH PLANS. HYDRAULIC CALCULATIONS? | | 2) PLAN REVIEW NOTES "SEE RESPONSE BY | | OTHERS" COULD NOT BE LOCATED. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2001-07-10 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-10 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-10 |
Time |
15:24 |
Sent To |
|
|
Notes |
2001-07-10 00:00:00 | 1) PLEASE PROVIDE MORE DETAILS ON | | PROPANE TANK SHOWN ON THE DRAWINGS. | | PLEASE INCLUDE TANK SIZE, PIPE SIZE, | | PHYSICAL PROTECTION, DISTANCES TO | | PROPERTY LINES, BUILDINGS, ETC. | | 2) NO FIRE SPRINKLER DRAWINGS PROVIDED | | WITH DRAWINGS. COMPLETE HYDRAULIC | | CALCULATIONS ALSO MISSING. | | 3) NO INFORMATION PROVIDED FOR OPTIONAL | | DAY CARE CENTER. | | 4) NO DETAILS PROVIDED ON GENERATOR. | | 5) NO DETAILS PROVIDED FOR THE INTERIOR | | OF PUBLIX STORE. | | 6) NO MECHANICAL,ELECTRICAL OR PLUMBING | | SHOWN FOR PUBLIX. | | 7) NO DETAILS PROVIDED FOR HOOD, DUCT | | AND EXTINGUISHING SYSTEMS. | | 8) BUILDING ADDRESS PLAN REVIEW COMMENTS | | NOT COMPLETELY CORRECT. THE RESPONSE | | DID NOT INCLUDE BUILDING ADDRESS ON | | THE ADDRESS SIDE OF THE BUILDINGS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-04-24 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-04-24 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-04-24 |
Time |
11:05 |
Sent To |
|
|
Notes |
2001-04-24 00:00:00 | 1) GENERAL NOTES ON PAGE A0.2 INDICATES | | THE 2000 EDITION OF THE LIFE SAFETY | | CODE. IT DEPENDS WHEN THE PERMIT IS | | LET AND WHAT DISCUSSION HAVE OCCURRED | | AS TO WHAT EDITION IS GOING TO BE USED. | | EITHER THE 2000 OR THE 1985 EDITION. | | 2) FIVE FIRE HYDRANTS LOCATED ON SITE | | MAP. ADDITIONAL FIRE HYDRANTS MAY BE | | REQUIRED BY THIS OFFICE. | | 3) THE FIRE LANE MARKINGS AND SIGNAGE IS | | TO BE APPROVED BY THIS OFFICE. | | 4) KNOX-BOXES WILL BE REQUIRED. | | 5) BUILDING ADDRESSES ARE REQUIRED FOR | | ALL BUILDINGS LOCATED AT THE SITE PER | | CITY CODE REQUIREMENTS. | | 6) WET FIRE HYDRANTS MUST BE AVAILABLE | | PRIOR TO AND DURING CONSTRUCTION.ALSO | | SUITABLE ACCESS ROADS ARE TO BE | | PROVIDED DURING CONSTRUCTION. | | 7) PROVIDE SEPARATE PLANS AND PERMITS | | FOR ANY HOOD, DUCT AND EXTINGUISHING | | SYSTEMS PLANNED FOR COMMERCIAL | | COOKING APPLICATIONS. | | 8) PROVIDE SEPARATE PLANS AND PERMITS | | FOR FIRE ALARM EQUIPMENT PLANNED FOR THE | | BUILDINGS. | | 9) NO FIRE SPRINKLER OR HYDRAULIC | | CALCULATIONS PROVIDED WITH PLANS. THIS | | INFORMATION IS REQUIRED PRIOR TO | | RECEIVING A BUILDING PERMIT. | | 10) TENANT DEMISING WALLS IN BUILDINGS | | B AND C TO MEET BUILDING CODE | | REQUIREMENTS. | | 11) PLEASE EXPLAIN OPTIONAL DAY CARE | | AREA FOR RETAIL BUILDING B. | | 12) PLEASE PROVIDE DETAILS ON | | EMERGENCY GENERATOR. PLEASE PROVIDE | | INFORMATION ON ANY FUEL STORAGE FOR THE | | GENERATOR. | | 13) PLEASE PROVIDE MECHANICAL,ELECTRICAL | | AND PLUMBING DRAWINGS FOR THE PUBLIX. | | 14) PLEASE PROVIDE MORE INFORMATION | | FOR THE INTERIOR OF THE PUBLIX STORE. | | PLEASE PROVIDE A LIFE SAFETY PLAN | | AND AN OCCUPANT LOAD DRAWING FOR THE | | PUBLIX. | | 15) ANY CHANGES IN ELEVATIONS LESS THAN | | TWENTY ONE INCHES SHALL BE BY RAMPS. | | 16) PLEASE SHOW ALL UNDERGOUND FIRE | | MAINS, THEIR SIZES, CONNECTION POINTS, | | BACKFLOW DEVICES, ETC. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-05-07 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-07 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-07 |
Time |
13:50 |
Sent To |
E |
|
Notes |
2003-05-07 00:00:00 | DP DESK. RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-02-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-24 |
Time |
17:29 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-02-20 |
Time |
17:29 |
Sent To |
|
|
Notes |
2003-02-25 00:00:00 | TO #28 COMM BOARD. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2003-02-28 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-02-28 |
Time |
08:52 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2003-02-28 |
Time |
08:52 |
Sent To |
|
|
Notes |
2003-02-28 00:00:00 | REVISIONS MECH HOOD PERMIT 02101854 & | | REFRIGERATION 02090605 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2001-12-08 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-12-08 |
Time |
10:36 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2001-12-08 |
Time |
10:36 |
Sent To |
|
|
Notes |
2001-12-08 00:00:00 | | | PROVISO: | | | | ADDITIONAL MECHANICAL PERMITS REQUIRED | | FOR HOOD, FIRE SUPRESSION AND WALK-IN | | COOLERS.PLEASE PROVIDE PLANS AND | | MANUFACTURER SUBMITTAL DATA/PRODUCT | | APPROVALS WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-10-24 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-10-24 |
Time |
16:32 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-10-24 |
Time |
14:45 |
Sent To |
|
|
Notes |
2001-10-24 00:00:00 | *******************PROVISO************** | | | | | | MECHANICAL CENTER SHALL HAVE HORN/STROBE | | OUTSIDE AT ENTRANCE AS WELL AS INSIDE. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | FIRE SUPRESSION AND WALK-IN | | COOLER/FREEZERS.PLEASE PROVIDE PLANS | | AND MANUFACTURER INFORMATION WITH | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2001-08-17 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-15 |
Time |
16:16 |
Rev Time |
4.00 |
Received By |
pkrauss |
Date |
2001-08-15 |
Time |
15:00 |
Sent To |
|
|
Notes |
2001-08-15 00:00:00 | ********************DENIED************** | | | | | | PLAN SHEET A-6, FLUE PIPE SHALL BE NO | | LESS THAN 10' FROM ANY FRESH AIR INTAKE. | | (1997 SGC 608.3.1) | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | FIRE SUPRESSION AND WALK-IN | | COOLERS/FREEZERS.PLEASE PROVIDE PLANS | | AND ALL MANUFACTURER SUBMITTAL DATA AT | | THE TIME OF PERMIT APPLICATION. | | | | PROVIDE INFORMATION ON THE MECHANICAL | | CENTERS ON THE ROOF, SHOW COMPLIANCE | | WITH CHAPTER 11 OF THE 1997 SMC. | | | | | | NOTE:CONDENSERS INDICATED ON PLAN | | SHEET A-6, CONDENSER STANDS SHALL | | BE A MINIMUM OF 18" BETWEEN ROOF | | SURFACE AND THE BOTTOM OF THE | | SUPPORT RAIL. (AMENDED 1997 SMC | | 304.2.5) |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-05-23 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-05-23 |
Time |
16:38 |
Rev Time |
2.00 |
Received By |
pkrauss |
Date |
2001-05-23 |
Time |
15:12 |
Sent To |
|
|
Notes |
2001-05-23 00:00:00 | *******************PROVISO************** | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | WITH MECHANICAL PERMIT APPLICATION. | | | | RETAIL "B" 01041078 & "C" 01041079 | | | | 1.FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | WITH NOTIFICATION TO ALARM/STROBE IN | | NORMALLY OCCUPIED AREAS AS PER NFPA | | 90A 4-4.4.3. | | | | 2.PVC FOR CONDENSATE ON ROOF TO COMPLY | | WITH MANUFACTURERS RECOMMENDATIOIN | | FOR UV TOLERANCE. | | | | PUBLIX STORE 01041075 | | | | 1.DRAWING A-9, DETAIL 11 - GREASE | | DUCT EXHAUST SHALL COMPLY WITH 1997 | | SMC 506.1 FOR TERMINATION ABOVE | | ROOF (40" MIN. & 10' FROM ANY FRESH | | AIR INTAKES.) | | | | 2.PLEASE PROVIDE AIR BALANCE SCHEDULE | | (1997 SMC 501.2) | | | | 3.CLARIFY AC-4, IS IT CONDITIONING THE | | SPACE ABOVE THE CEILING? | | | | 4.ADDITIONAL MECHANICAL PERMITS ARE | | REQUIRED FOR HOODS, FIRE SUPPRESSION | | FUEL AND WALK-IN COOLERS/FREEZERS. | | PLEASE SUBMIT PLANS AND MANUFACTURE | | CUT SHEETS AT THE TIME OF PERMIT | | APPLICATION. | | | | RETAIL "D"01041080 | | | | NO PLANS SUBMITTED FOR THIS SECTION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
F |
Date |
2002-09-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-09-23 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-09-23 |
Time |
16:17 |
Sent To |
|
|
Notes |
2002-09-23 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) SHT P1.0 DRINKING FOUNTAIN REQUIRED | | IN SPACE B-8 NOT SHOWN ON FLOOR PLAN. | | 2) SHT P4.0 SUITE B-8, SANITARY ENLARGE- | | MENT PLAN/SANITARY ISOMETRIC PLAN #2, | | HUB DRAIN ARE NOT APPROVED. PLEASE IN- | | DICATE WHAT THE HUB DRAINS ARE TO BE | | USED FOR. 2" VENT BELOW SLAB NOT APPROV- | | ED. NO HORIZONTAL DRY VENTS ARE ALLOWED | | SEC. 906.2.1 | | 3) PLEASE PROVIDE A WATER RISER DIAGRAM | | FOR ALL REVISED AREAS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2002-01-02 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-01-02 |
Time |
11:38 |
Rev Time |
1.25 |
Received By |
kstevens |
Date |
2002-01-02 |
Time |
11:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2001-12-10 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-12-10 |
Time |
10:21 |
Rev Time |
2.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-12-10 00:00:00 | PLUMBING PLAN REVIEW,DENIED. PREVIOUS | | COMMENTS DATED 10-28-01 NOT APPROVED. | | (1) GREASE TRAPS TO BE PIPED PARALLEL. | | (2) WATER HAMMER ARESSTORS TO BE INSTAL- | | LED AS PER MFG. NOT AT HIGH POINT. | | (3) PROVIDECUT SHTS FOR 2# REGULATORS. | | SHOW MANUAL SOV & UNION UP STREAM OF | | REGULATOR. | | END OF COMMENTSPAUL SCHMITZ | | QUESTIONS 561-659 8096X8233 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2001-10-28 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-10-28 |
Time |
13:25 |
Rev Time |
3.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-10-28 00:00:00 | PLUMBING PLAN REVIEW, DENIED | | (1) SHT P-3-4GREASE TRAP REFERENCE, | | GREASE TANKS TO BE PIPED PARALLEL NOT | | IN SERIES. | | (2) SHT P-2 WATER PIPING ISOMETRIC SHOW | | A REERENCE FOR WATER HAMMER ARRESTORS, | | INSTALLED PER.MFG FOR PLACEMENT AND | | LOCATION,SEC 607.8, PDI-WH201, ASSE 1010 | | (3) SHT P-2 GAS PIPING ISOMETRIC L-P GAS | | CODE REFERENCE FOR L-P GAS IS NFPA-54-99 | | LIQUIDFIED PETROLEM, TAB 12.1 TANK TO | | METER, TAB 12.3 SECOND STAGE REGULATOR | | TO APPLIANCE. | | TOTAL DEVELOPED LGTH SHALL BE FROM L-P | | TANK TO METER, METER TO THE FARTHEST | | APPLIANCE. | | PIPING AS SHOWN IS OVER SIZED. | | SPECIFICATIONS CALL FOR ALL BLK STEEL | | PIPING TO BE WELDED, REGARDLESS OF SIZE? | | END OF COMMENTS PAUL SCHMITZ | | QUESTIONS 5610659-8096X8233 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2001-08-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-08-18 |
Time |
08:58 |
Rev Time |
2.00 |
Received By |
kstevens |
Date |
2001-08-18 |
Time |
08:58 |
Sent To |
|
|
Notes |
2001-08-18 00:00:00 | DENIED | | REFERENCES STD PLBG CODE 94 STG GAS 97 | | | | 1) GREASE TRAP LOCATION, NO SP-1 PAGE | | SUBMITTED AS PER RESPONSE. PLEASE SEE | | ATTACHED SHEET FOR APPROVED GREASE TRAP. | | 2) FLOOR SINKS TO BE RUN SEPARATELY OFF | | MAIN DRAIN. | | 3) GAS TO BE SIZED WITH SGC-97 305.4A | | 4) WATER HEATER MANUFACTURE SHEET NOT | | FOUND. PLEASE SUBMIT. | | | | REVIEW BY KEN STEVENS | | (561) 569-8096 EXT. 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-05-11 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-05-11 |
Time |
08:20 |
Rev Time |
3.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-05-11 00:00:00 | PLUMBING PLAN REVIEWDENIED | | REFERENCES STD PLBG CODE 94 STD GAS 97 | | (1) SHT SP-1 SHOW LOCATION OF GREASE | | TANKS. | | (2) SHT P-1 RETAIL B,C DRINKING FOUNTAIN | | REQUIRED,EACH SPACE TAB 407. | | (3) SHT P-2,6 COMPLY WITH GAS APPLICAT- | | ION PERMT REQUIRMENTS,SEE ATTACHED. | | ESOV FOR BAKERY: MANUAL SOV TO BE UP | | STREAM OF UNION. | | (4) SHT P-4 SAFE WASTE NOT PERMITTED, | | EACH PLBG FIXTURE SHALL BE TRAPED,VENTED | | SEC 1001.8 | | (5) SHT P-6 CONDENSATE DRAINS: ALL | | INDIRECT WASTE TO FLOOR SINKS SEC 802. | | (6) SHT P-6 DETAIL 8P-6 SANITIZER | | INSTALLERS ARE NOT LICENSED PLUMBERS. | | PLUMBER TO LEAVE A VALVED CONNECTION | | W/A WATTS 36-N ANTI SYPHON DEVICE FOR | | EACH SANITIZER CONNECTION TO POTTABLE | | WATER. | | END OF COMMENTS PAUL SCHMITZ | | QUESTIONS561-659-8096 X 8233 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2001-11-29 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-11-29 |
Time |
11:06 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-11-29 00:00:00 | APPROVED BY M SANCHEZ |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2001-05-25 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-05-25 |
Time |
14:52 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-05-25 00:00:00 | MINOR AMENDENT WAITING APPROVAL |
|
|