Plan Review Details - Permit 01041075
Plan Review Stops For Permit 01041075
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-10-30 Cont ID  
Sent By hpiskura Date 2001-10-30 Time 14:41 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-10-30 00:00:00IMPACT FEES, RESIDENT INSPECTOR REQUIRED

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-08-02 Cont ID  
Sent By hpiskura Date 2001-08-02 Time 08:26 Rev Time 0.00
Received By hpiskura Date 2001-08-01 Time 14:20 Sent To  
Notes
2001-08-02 00:00:00SHEET S1 OF THE PUBLIX PLANS DESIGN
 CRITERIA CALLS OUT CONFLICTING
 INFORMATION FOR THE WIND.SEE SBC
 1606.1.2.1 RE: MIXING OF WINDLOADS.
 THE ENTIRE BUILDING, INCLUDING THE
 RETAIL WINGS, MUST BE DESIGNED TO ONE
 STANDARD.EITHER ASCE 7-95 OR SBC
 1606.2.WEST PALM BEACH IS IN THE 140
 MPH VELOCITY ZONE FOR ASCE 7-95 AND 110
 MPH FOR SBC 1606.2. NOT THE 100 MPH
 DECLARED.
  
 PLEASE INCLUDE CALCULATIONS
 DEMONSTRATING COMPLIANCE WITH ONE OF
 THE ABOVE.ALSO WHICH IS THE DESIRED
 SOIL BEARING PRESSURE,2000 PSF OR 2500
 PSF?
  
 THE FP1 HAS A STATEMENT THAT SAYS SEE
 THE ARCHITECTURAL PLANS FOR THE CANOPY
 SPRINKLER DESIGN.THE ARCHITECTURAL
 PLANS DO NOT SHOW ANY FIRE SPRINKLER
 DESIGN.
  
 NFPA 13 SS 4-5.7.1 REQUIRES SPRINKLERS
 FOR THIS APPLICATION AND CHP.
 61G15-32.003 COMMON REQUIREMENTS TO ALL
 FIRE PROTECTION ENGINEERING DOCUMENTS
 FBPE,SET OUT SPECIFIC INFORMATION FOR
 DOCUMENT SUBMITTAL.PLEASE REVISE AS
 NECESSARY.
  
 PLEASE INDICATE THE PORTIONS OF THE
 BILDING THAT WILL HAVE HURRICANE
 SHUTTERS AND WHICH WILL HAVE IMPACT
 RESISTANT GLASS?
  
 SEE THE PREVIOUS CHECKLISTS REGARDING
 IMPACT FEES AND A RESIDENT INSPECTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-07-12 Cont ID  
Sent By hpiskura Date 2001-07-12 Time 13:50 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-07-12 00:00:00WHAT IS THE 11' STRUCTURE ON THE WEST
 WALL NEAR THE TRASH COMPACTOR?IT IS
 SHOWN ON THE SITE PLAN AND THE CIVIL
 PLANS.THERE ARE NO CONSTRUCTINON
 DETAILS SHOWN FOR THIS PROJECTION.IF
 IT IS A PORTION OF THE BUILDING AND THE
 DISTANCE TO THE PROPERTY LINE IS LESS
 THAN 40' THAN THE UNLIMITED AREA
 EXCEPTION IS NOT APPLICABLE.IF IT IS
 AN OPEN LOADING DOCK, SHOW THE DETAILS.
  
  
 SHEET A0.1 CITES THE SFBC 514.2(B).
 THEBUILDING NEEDS TO COMPLY WITH SBC
 503.4.THIS IS THE STANDARD BUILDING
 CODE NOT
 THE SOUTH FLORIDA BUILDING CODE.
  
 THE FLOOR PLAN ON SHEET A2.1 IS
 INADEQUATE TO DETERMINE EGRESS
 REQUIREMENTS.
  
 THE MAY 10, CHECKLIST IS INCLUDED FOR
 REFERENCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-05-10 Cont ID  
Sent By hpiskura Date 2001-05-10 Time 15:42 Rev Time 0.00
Received By hpiskura Date 2001-05-08 Time 08:57 Sent To  
Notes
2001-05-10 00:00:00INDICATE CLEARLY ON THE SITE PLAN THE
 DISTANCE TO THE WEST PROPERTY LINE
  
 THE 3 HOUR RATED WALL REQUIRES 3 HOUR
 RATED OPENEINGS.
  
 SHOW A SPECIFIC FIRE DESIGN NUMBER FOR
 THE FIRE RATED WALL.
  
 WHAT IS THE NET CLEAR OPENING OF THE
 STOREFRONT DOORS?
  
 SHEET S1 SHOWS 7-93.SBC 97 INVOKES
 ASCE 7-95.
  
 SHOW THE HURRICANE MISSILE IMPACT
 PROTECTION.
  
 IMPACT FEES MUST BE PAID TO THE COUNTY.
 CALL 233-5025 FOR MORE INFORMATION.
  
 PROVIDE THE TEST DATA AND REPORTS FOR
 THE DOORS WINDOWS AND THE ROOF COVERING.
  
 PROVIDE A RECENT PROPERTY SURVEY.
  
 A RESIDENT INSPECTOR IS REQUIRED.
 CONTACT DON NEELY 561-659-8096 X 8333
 FOR MORE INFORMATION.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-02-25 Cont ID  
Sent By shernand Date 2003-05-07 Time 13:50 Rev Time 0.00
Received By dpalmer Date 2003-02-25 Time 17:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-09-16 Cont ID  
Sent By dpalmer Date 2002-09-16 Time 06:19 Rev Time 0.75
Received By dpalmer Date 2002-09-16 Time 06:19 Sent To  
Notes
2002-09-16 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE NOTE REVISIONS NOTED ON
 PLANS DO NOT SHOW THE REVISIONS DONE
 BETWEEN THE LAST SET WAS SUBMITTED AND
 NOW. PLANS ARE SHOWING SPACES THAT HAVE
 REVISIONS TO THEM WHEN THE PLANS ON
 RECORD DO NOT SHOW THOSE SPACE BEING
 FITTED UP?
 PLEASE ALSO SEE ANY BUILDING REVIEW
 COMMENTS FORBUILD OUT OF SPACES UNDER
 A SHELL PERMIT?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 PLEASE NOTE REVIEW NOTES TYPED UNDER
 THIS MAIN # FORREVISIONS TO #`S
 01041078,01041079.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-12-12 Cont ID  
Sent By dpalmer Date 2001-12-12 Time 17:37 Rev Time 0.00
Received By dpalmer Date 2001-12-12 Time 17:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-14 Cont ID  
Sent By dpalmer Date 2001-08-14 Time 20:35 Rev Time 0.00
Received By dpalmer Date 2001-08-14 Time 20:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-14 Cont ID  
Sent By dpalmer Date 2001-05-14 Time 16:26 Rev Time 0.00
Received By dpalmer Date 2001-05-14 Time 16:26 Sent To  
Notes
2001-05-14 00:00:00***************** UNSAT****************
  
 1)NOTE: PLEASE NOTE THAT THERE IS A
 PERMIT APPLICATION FOR BLDG "D" BUT CAN'
 T FIND BLDG"D PLANS. PLEASE CLARIFY.
  
 2)NOTE: PLEASE NOTE THAT ELECTRICAL
 DRAWING HAVE PASSED ELEC REVIEW, BUT
 HAVE NOTICED THAT FIRE REVIEW HAVE
 FAILED AND MIGHT AFFECT ELECTRICAL
 DRAWINGS. ELECTRICAL DRAWINGS WILL
 BE STAMPED PENDING NO CHANGES AND
 CLARIFICATION ON BLDG "D" PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2002-05-02 Cont ID  
Sent By mamini Date 2002-05-02 Time 14:38 Rev Time 0.00
Received By mamini Date 2002-05-02 Time 14:38 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2001-08-15 Cont ID  
Sent By mamini Date 2001-08-15 Time 11:32 Rev Time 5.00
Received By mamini Date 2001-08-15 Time 11:01 Sent To  
Notes
2001-08-15 00:00:00FAILED:
 ***NOTES***
 REVIEW COMMENTS APPLY TO PERMITS
 # 01041078
 # 01041079
 # 01041080
  
 1. PLEASE PROVIDE THE STATUS OF APPROVAL
 FROM THE SFWMD & DEP IN REGARDS TO THIS
 PROJECT.
 2. PLEASE PROVIDE THE STATUS OF THE
 AGREEMENTS WITH THE CITY OF WEST PALM
 BEACH CONCERNING THE PROPOSED POND FOR
 OFF-SITE DISCHARGE.
  
 ABOVE MENTIONED ISSUES ARE THE ONLY
 ITEMS THAT HOLDING APPROVAL OF THE CIVIL
 PLANS FOR THE ENTIRE SITE AT THE PRESENT
 TIME.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-04-26 Cont ID  
Sent By mamini Date 2001-04-26 Time 15:54 Rev Time 4.00
Received By mamini Date 2001-04-26 Time 14:45 Sent To  
Notes
2001-04-26 00:00:00FAILED:
 INSUFFICIENT INFORMATION SUBMITTED FOR
 CIVIL ENGINEERING REVIEW.PLEASE
 RESUBMIT WHEN CIVIL PLANS ARE DEVELOPED.
 2. PERVIOUS & IMPERVIOUS CALCULATION
 MUST BE SHOWN ON PAVING AND DRAINAGE
 PLAN, THE TOTAL AMOUNT MUST BE EQUAL
 100% OF TOTAL SITE ACRES OR S.F.PLEASE
 STATE EITHER ADDRESS OR PROPERTY CONTROL
 NUMBER.STORM WATER CHARGES WILL BE
 CALCULATED FROM THESE.
 3. PLEASE PROVIDE STORM WATER
 CALCULATION FOR OUR REVIEW IF YOU HAVE
 NOT SUBMITTED TO JOSE DEL RIO, STORM
 WATER ENGINEER, 1000 45TH STREET WEST
 PALM BEACH, FL 33407. SEE ATTACHED
 4. PLEASE PROVIDE POLLUTION PREVENTION
 PLAN WHICH INCLUDE TRUCK WASHOUT AT EXIT
 AND COVERAGE FOR DRAINGE,SOIL ERROSION.
 PLAN SHOULD BE INSTALLED IN FIELD PRIOR
 TO ANY EARTH WORK. THE POLLUTION CONTROL
 PLAN SHALL BE KEPTH ON SITE AT ALL TIME
 DURING CONSTRUCTION.
 5. ONCE REVISED, TWO SETS OF PLANS MUST
 BE SUBMITTED TO PUBLIC UTILITIES
 ENGINEERING SERVICES FOR THEIR REVIEW
 AND ACTUAL SERVICE CONNECTIONS.
 6. WORK PERFORMED ALONG PUBLIC R.O.W
 REQUIRES A PERMIT THROUGH CITY ENGINEERS
 OFFICE, RICHARD PITTMAN, 1000 45TH
 STREET WEST PALM BEACH, FL 33407
 7. PLEASE PROVIDE DETAILS FOR DUMPSTER
 ENCLOSURES. SHEET 2 OF 2 REFERS TO
 ARCHITECTURAL PALNS FOR DETAILS, NO
 DETAILS FOR ENCLOSURES IS PROVIDED.
 DUMSTERS ENCLOSURES AT MIN. SHOULD BE
 PER CITY OF WPB STANDARD. SEE ATTACHED
 8. PLEASE COORDINATE WITH PUBLIC
 UTILITIES ENGINEERING SERVICES FOR
 CONNECTION OF ALL SERVICES AND FOR LOCAT
 ION OF BACKFLOW PREVENTERS ,FIRE, WATER
 IRRIGATIONS.
 9. STANDARD, DETAILS, APPROVED PRODUCT
 LIST COULD BE OBTAIN FROM PUBLIC
 UTILITIES ENGINEERING SERVICES
 DEPARTMENT 1000 45TH STREET WEST PALM
 BEACH, FL 33407561 659-8040
 ANY QUESTION PLEASE CONTACT 561-659-8096
 EXT. 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2001-12-19 Cont ID  
Sent By mcarsill Date 2001-12-19 Time 14:18 Rev Time 0.00
Received By mcarsill Date 2001-12-19 Time 14:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2001-10-22 Cont ID  
Sent By mcarsill Date 2001-10-22 Time 09:06 Rev Time 0.00
Received By mcarsill Date 2001-10-22 Time 09:06 Sent To  
Notes
2001-10-22 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 ON PLANS, SHOULD READ 1985 EDITION
 INSTEAD OF 1997 EDITION.
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD,DUCT,AND EXTINGUISHING SYSTEMS.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR LP GAS INSTALLATION.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2001-08-20 Cont ID  
Sent By mcarsill Date 2001-08-20 Time 12:32 Rev Time 0.00
Received By mcarsill Date 2001-08-20 Time 12:32 Sent To  
Notes
2001-08-20 00:00:001) NO FIRE SPRINKLER SYSTEM DRAWINGS
 OR HYDRAULIC CALCULATIONS PROVIDED
 WITH PLANS.
 2) STILL MORE DETAILS NEEDED ON PROPANE
 TANK SHOWN ON CIVIL DRAWINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-08-09 Cont ID  
Sent By mcarsill Date 2001-08-09 Time 13:27 Rev Time 0.00
Received By mcarsill Date 2001-08-09 Time 13:27 Sent To  
Notes
2001-08-09 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. HYDRAULIC CALCULATIONS?
 2) PLAN REVIEW NOTES "SEE RESPONSE BY
 OTHERS" COULD NOT BE LOCATED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-07-10 Cont ID  
Sent By mcarsill Date 2001-07-10 Time 15:24 Rev Time 0.00
Received By mcarsill Date 2001-07-10 Time 15:24 Sent To  
Notes
2001-07-10 00:00:001) PLEASE PROVIDE MORE DETAILS ON
 PROPANE TANK SHOWN ON THE DRAWINGS.
 PLEASE INCLUDE TANK SIZE, PIPE SIZE,
 PHYSICAL PROTECTION, DISTANCES TO
 PROPERTY LINES, BUILDINGS, ETC.
 2) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH DRAWINGS. COMPLETE HYDRAULIC
 CALCULATIONS ALSO MISSING.
 3) NO INFORMATION PROVIDED FOR OPTIONAL
 DAY CARE CENTER.
 4) NO DETAILS PROVIDED ON GENERATOR.
 5) NO DETAILS PROVIDED FOR THE INTERIOR
 OF PUBLIX STORE.
 6) NO MECHANICAL,ELECTRICAL OR PLUMBING
 SHOWN FOR PUBLIX.
 7) NO DETAILS PROVIDED FOR HOOD, DUCT
 AND EXTINGUISHING SYSTEMS.
 8) BUILDING ADDRESS PLAN REVIEW COMMENTS
 NOT COMPLETELY CORRECT. THE RESPONSE
 DID NOT INCLUDE BUILDING ADDRESS ON
 THE ADDRESS SIDE OF THE BUILDINGS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-24 Cont ID  
Sent By mcarsill Date 2001-04-24 Time 11:05 Rev Time 0.00
Received By mcarsill Date 2001-04-24 Time 11:05 Sent To  
Notes
2001-04-24 00:00:001) GENERAL NOTES ON PAGE A0.2 INDICATES
 THE 2000 EDITION OF THE LIFE SAFETY
 CODE. IT DEPENDS WHEN THE PERMIT IS
 LET AND WHAT DISCUSSION HAVE OCCURRED
 AS TO WHAT EDITION IS GOING TO BE USED.
 EITHER THE 2000 OR THE 1985 EDITION.
 2) FIVE FIRE HYDRANTS LOCATED ON SITE
 MAP. ADDITIONAL FIRE HYDRANTS MAY BE
 REQUIRED BY THIS OFFICE.
 3) THE FIRE LANE MARKINGS AND SIGNAGE IS
 TO BE APPROVED BY THIS OFFICE.
 4) KNOX-BOXES WILL BE REQUIRED.
 5) BUILDING ADDRESSES ARE REQUIRED FOR
 ALL BUILDINGS LOCATED AT THE SITE PER
 CITY CODE REQUIREMENTS.
 6) WET FIRE HYDRANTS MUST BE AVAILABLE
 PRIOR TO AND DURING CONSTRUCTION.ALSO
 SUITABLE ACCESS ROADS ARE TO BE
 PROVIDED DURING CONSTRUCTION.
 7) PROVIDE SEPARATE PLANS AND PERMITS
 FOR ANY HOOD, DUCT AND EXTINGUISHING
 SYSTEMS PLANNED FOR COMMERCIAL
 COOKING APPLICATIONS.
 8) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE ALARM EQUIPMENT PLANNED FOR THE
 BUILDINGS.
 9) NO FIRE SPRINKLER OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS. THIS
 INFORMATION IS REQUIRED PRIOR TO
 RECEIVING A BUILDING PERMIT.
 10) TENANT DEMISING WALLS IN BUILDINGS
 B AND C TO MEET BUILDING CODE
 REQUIREMENTS.
 11) PLEASE EXPLAIN OPTIONAL DAY CARE
 AREA FOR RETAIL BUILDING B.
 12) PLEASE PROVIDE DETAILS ON
 EMERGENCY GENERATOR. PLEASE PROVIDE
 INFORMATION ON ANY FUEL STORAGE FOR THE
 GENERATOR.
 13) PLEASE PROVIDE MECHANICAL,ELECTRICAL
 AND PLUMBING DRAWINGS FOR THE PUBLIX.
 14) PLEASE PROVIDE MORE INFORMATION
 FOR THE INTERIOR OF THE PUBLIX STORE.
 PLEASE PROVIDE A LIFE SAFETY PLAN
 AND AN OCCUPANT LOAD DRAWING FOR THE
 PUBLIX.
 15) ANY CHANGES IN ELEVATIONS LESS THAN
 TWENTY ONE INCHES SHALL BE BY RAMPS.
 16) PLEASE SHOW ALL UNDERGOUND FIRE
 MAINS, THEIR SIZES, CONNECTION POINTS,
 BACKFLOW DEVICES, ETC.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-07 Cont ID  
Sent By shernand Date 2003-05-07 Time 13:50 Rev Time 0.00
Received By shernand Date 2003-05-07 Time 13:50 Sent To E
Notes
2003-05-07 00:00:00DP DESK. RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-24 Cont ID  
Sent By dpalmer Date 2003-02-24 Time 17:29 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 17:29 Sent To  
Notes
2003-02-25 00:00:00TO #28 COMM BOARD.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-02-28 Cont ID  
Sent By pkrauss Date 2003-02-28 Time 08:52 Rev Time 0.45
Received By pkrauss Date 2003-02-28 Time 08:52 Sent To  
Notes
2003-02-28 00:00:00REVISIONS MECH HOOD PERMIT 02101854 &
 REFRIGERATION 02090605

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-12-08 Cont ID  
Sent By pkrauss Date 2001-12-08 Time 10:36 Rev Time 0.50
Received By pkrauss Date 2001-12-08 Time 10:36 Sent To  
Notes
2001-12-08 00:00:00 
 PROVISO:
  
 ADDITIONAL MECHANICAL PERMITS REQUIRED
 FOR HOOD, FIRE SUPRESSION AND WALK-IN
 COOLERS.PLEASE PROVIDE PLANS AND
 MANUFACTURER SUBMITTAL DATA/PRODUCT
 APPROVALS WITH PERMIT APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-10-24 Cont ID  
Sent By pkrauss Date 2001-10-24 Time 16:32 Rev Time 0.45
Received By pkrauss Date 2001-10-24 Time 14:45 Sent To  
Notes
2001-10-24 00:00:00*******************PROVISO**************
  
  
 MECHANICAL CENTER SHALL HAVE HORN/STROBE
 OUTSIDE AT ENTRANCE AS WELL AS INSIDE.
  
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN
 COOLER/FREEZERS.PLEASE PROVIDE PLANS
 AND MANUFACTURER INFORMATION WITH
 PERMIT APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-08-17 Cont ID  
Sent By pkrauss Date 2001-08-15 Time 16:16 Rev Time 4.00
Received By pkrauss Date 2001-08-15 Time 15:00 Sent To  
Notes
2001-08-15 00:00:00********************DENIED**************
  
  
 PLAN SHEET A-6, FLUE PIPE SHALL BE NO
 LESS THAN 10' FROM ANY FRESH AIR INTAKE.
 (1997 SGC 608.3.1)
  
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN
 COOLERS/FREEZERS.PLEASE PROVIDE PLANS
 AND ALL MANUFACTURER SUBMITTAL DATA AT
 THE TIME OF PERMIT APPLICATION.
  
 PROVIDE INFORMATION ON THE MECHANICAL
 CENTERS ON THE ROOF, SHOW COMPLIANCE
 WITH CHAPTER 11 OF THE 1997 SMC.
  
  
 NOTE:CONDENSERS INDICATED ON PLAN
 SHEET A-6, CONDENSER STANDS SHALL
 BE A MINIMUM OF 18" BETWEEN ROOF
 SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL. (AMENDED 1997 SMC
 304.2.5)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-05-23 Cont ID  
Sent By pkrauss Date 2001-05-23 Time 16:38 Rev Time 2.00
Received By pkrauss Date 2001-05-23 Time 15:12 Sent To  
Notes
2001-05-23 00:00:00*******************PROVISO**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 RETAIL "B" 01041078 & "C" 01041079
  
 1.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS AS PER NFPA
 90A 4-4.4.3.
  
 2.PVC FOR CONDENSATE ON ROOF TO COMPLY
 WITH MANUFACTURERS RECOMMENDATIOIN
 FOR UV TOLERANCE.
  
 PUBLIX STORE 01041075
  
 1.DRAWING A-9, DETAIL 11 - GREASE
 DUCT EXHAUST SHALL COMPLY WITH 1997
 SMC 506.1 FOR TERMINATION ABOVE
 ROOF (40" MIN. & 10' FROM ANY FRESH
 AIR INTAKES.)
  
 2.PLEASE PROVIDE AIR BALANCE SCHEDULE
 (1997 SMC 501.2)
  
 3.CLARIFY AC-4, IS IT CONDITIONING THE
 SPACE ABOVE THE CEILING?
  
 4.ADDITIONAL MECHANICAL PERMITS ARE
 REQUIRED FOR HOODS, FIRE SUPPRESSION
 FUEL AND WALK-IN COOLERS/FREEZERS.
 PLEASE SUBMIT PLANS AND MANUFACTURE
 CUT SHEETS AT THE TIME OF PERMIT
 APPLICATION.
  
 RETAIL "D"01041080
  
 NO PLANS SUBMITTED FOR THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 6 Status F Date 2002-09-23 Cont ID  
Sent By kstevens Date 2002-09-23 Time 16:17 Rev Time 0.00
Received By kstevens Date 2002-09-23 Time 16:17 Sent To  
Notes
2002-09-23 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT P1.0 DRINKING FOUNTAIN REQUIRED
 IN SPACE B-8 NOT SHOWN ON FLOOR PLAN.
 2) SHT P4.0 SUITE B-8, SANITARY ENLARGE-
 MENT PLAN/SANITARY ISOMETRIC PLAN #2,
 HUB DRAIN ARE NOT APPROVED. PLEASE IN-
 DICATE WHAT THE HUB DRAINS ARE TO BE
 USED FOR. 2" VENT BELOW SLAB NOT APPROV-
 ED. NO HORIZONTAL DRY VENTS ARE ALLOWED
 SEC. 906.2.1
 3) PLEASE PROVIDE A WATER RISER DIAGRAM
 FOR ALL REVISED AREAS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-01-02 Cont ID  
Sent By kstevens Date 2002-01-02 Time 11:38 Rev Time 1.25
Received By kstevens Date 2002-01-02 Time 11:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-12-10 Cont ID  
Sent By pschmitz Date 2001-12-10 Time 10:21 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-10 00:00:00PLUMBING PLAN REVIEW,DENIED. PREVIOUS
 COMMENTS DATED 10-28-01 NOT APPROVED.
 (1) GREASE TRAPS TO BE PIPED PARALLEL.
 (2) WATER HAMMER ARESSTORS TO BE INSTAL-
 LED AS PER MFG. NOT AT HIGH POINT.
 (3) PROVIDECUT SHTS FOR 2# REGULATORS.
 SHOW MANUAL SOV & UNION UP STREAM OF
 REGULATOR.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS 561-659 8096X8233

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-10-28 Cont ID  
Sent By pschmitz Date 2001-10-28 Time 13:25 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-28 00:00:00PLUMBING PLAN REVIEW, DENIED
 (1) SHT P-3-4GREASE TRAP REFERENCE,
 GREASE TANKS TO BE PIPED PARALLEL NOT
 IN SERIES.
 (2) SHT P-2 WATER PIPING ISOMETRIC SHOW
 A REERENCE FOR WATER HAMMER ARRESTORS,
 INSTALLED PER.MFG FOR PLACEMENT AND
 LOCATION,SEC 607.8, PDI-WH201, ASSE 1010
 (3) SHT P-2 GAS PIPING ISOMETRIC L-P GAS
 CODE REFERENCE FOR L-P GAS IS NFPA-54-99
 LIQUIDFIED PETROLEM, TAB 12.1 TANK TO
 METER, TAB 12.3 SECOND STAGE REGULATOR
 TO APPLIANCE.
 TOTAL DEVELOPED LGTH SHALL BE FROM L-P
 TANK TO METER, METER TO THE FARTHEST
 APPLIANCE.
 PIPING AS SHOWN IS OVER SIZED.
 SPECIFICATIONS CALL FOR ALL BLK STEEL
 PIPING TO BE WELDED, REGARDLESS OF SIZE?
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 5610659-8096X8233

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-08-18 Cont ID  
Sent By kstevens Date 2001-08-18 Time 08:58 Rev Time 2.00
Received By kstevens Date 2001-08-18 Time 08:58 Sent To  
Notes
2001-08-18 00:00:00DENIED
 REFERENCES STD PLBG CODE 94 STG GAS 97
  
 1) GREASE TRAP LOCATION, NO SP-1 PAGE
 SUBMITTED AS PER RESPONSE. PLEASE SEE
 ATTACHED SHEET FOR APPROVED GREASE TRAP.
 2) FLOOR SINKS TO BE RUN SEPARATELY OFF
 MAIN DRAIN.
 3) GAS TO BE SIZED WITH SGC-97 305.4A
 4) WATER HEATER MANUFACTURE SHEET NOT
 FOUND. PLEASE SUBMIT.
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-11 Cont ID  
Sent By pschmitz Date 2001-05-11 Time 08:20 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-11 00:00:00PLUMBING PLAN REVIEWDENIED
 REFERENCES STD PLBG CODE 94 STD GAS 97
 (1) SHT SP-1 SHOW LOCATION OF GREASE
 TANKS.
 (2) SHT P-1 RETAIL B,C DRINKING FOUNTAIN
 REQUIRED,EACH SPACE TAB 407.
 (3) SHT P-2,6 COMPLY WITH GAS APPLICAT-
 ION PERMT REQUIRMENTS,SEE ATTACHED.
 ESOV FOR BAKERY: MANUAL SOV TO BE UP
 STREAM OF UNION.
 (4) SHT P-4 SAFE WASTE NOT PERMITTED,
 EACH PLBG FIXTURE SHALL BE TRAPED,VENTED
 SEC 1001.8
 (5) SHT P-6 CONDENSATE DRAINS: ALL
 INDIRECT WASTE TO FLOOR SINKS SEC 802.
 (6) SHT P-6 DETAIL 8P-6 SANITIZER
 INSTALLERS ARE NOT LICENSED PLUMBERS.
 PLUMBER TO LEAVE A VALVED CONNECTION
 W/A WATTS 36-N ANTI SYPHON DEVICE FOR
 EACH SANITIZER CONNECTION TO POTTABLE
 WATER.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS561-659-8096 X 8233

Review Stop Z ZONING
Rev No 2 Status P Date 2001-11-29 Cont ID  
Sent By sgraham Date 2001-11-29 Time 11:06 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-11-29 00:00:00APPROVED BY M SANCHEZ

Review Stop Z ZONING
Rev No 1 Status F Date 2001-05-25 Cont ID  
Sent By sgraham Date 2001-05-25 Time 14:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-05-25 00:00:00MINOR AMENDENT WAITING APPROVAL