Plan Review Details - Permit 01040897
Plan Review Stops For Permit 01040897
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-06-04 Cont ID  
Sent By dpalmer Date 2001-06-04 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2001-06-04 Time 20:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-30 Cont ID  
Sent By dpalmer Date 2001-04-30 Time 19:00 Rev Time 0.00
Received By dpalmer Date 2001-04-30 Time 19:00 Sent To  
Notes
2001-04-30 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOT
 SIGNED AND SEALED BY THE ARCH/ENGINEERS
 OF RECORD PER 471.025/481.221 OF THE
 F.A.C..
  
 2)NOTE: PLEASE NOTE THAT PLANS ARE
 COMING BACK, PLEASE ADDRESS THE
 FOLLOWING COMMENTS.
  
 3) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 THERE ARE ROOMS SHOWING "FAN" J-BOX.
 PLEASE CLARIFY EGRESS LIGHTING.
  
 4)NOTE: PLEASE NOTE MISSING SMOKE DETECT
 OR INSIDE BEDRO0M #4. NFPA-72 2-2.1.1.1
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-09 Cont ID  
Sent By pkrauss Date 2001-07-09 Time 14:48 Rev Time 0.30
Received By pkrauss Date 2001-07-09 Time 14:40 Sent To  
Notes
2001-07-09 00:00:00REVISION MECH PERMIT 01040908

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-07 Cont ID  
Sent By hmoser Date 2001-04-28 Time 07:53 Rev Time 0.33
Received By hmoser Date 2001-04-28 Time 07:53 Sent To  
Notes
2001-04-28 00:00:00PROVISO NO GRILL SIZE & CFM BATHROOM DUC
 T

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-12-09 Cont ID  
Sent By pschmitz Date 2001-12-09 Time 16:23 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-09 00:00:00REVISION PLBG ISOMETRIC.

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-12-05 Cont ID  
Sent By kstevens Date 2001-12-05 Time 17:59 Rev Time 0.50
Received By kstevens Date 2001-12-05 Time 17:59 Sent To  
Notes
2001-12-05 00:00:00DENIED
 REFERENCE: SPC-94
  
 SANITARY DIAGRAM DOES NOT REFLECT FLOOR
 PLAN. BATH #2 IS NOT SHOWN ON REVISED
 SANT. RISER DIAGRAM. PLEASE RESUBMIT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-07 Cont ID  
Sent By kstevens Date 2001-06-07 Time 17:33 Rev Time 0.25
Received By kstevens Date 2001-06-07 Time 17:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-04-25 Cont ID  
Sent By kstevens Date 2001-04-25 Time 15:24 Rev Time 0.25
Received By kstevens Date 2001-04-25 Time 15:24 Sent To  
Notes
2001-04-25 00:00:00PLUMBING PLAN REVIEW.
  
 FAILED:
  
 (1) PLANS NOT SIGNED & SEALED
  
 (2) M/BATH SHOWS 2 TUBS ON RISER
 DIAGRAM BUT 1 TUB - 1 SHOWER ON
 FLOOR PLAN.
  
 (3) BATH 2 SHOWS 2 LAVS ON RISER
 DIAGRAM, BUT 1 ON FLOOR PLAN.
  
 (4) BATH 3 SHOWS 1 LAV ON RISER
 DIAGRAM, BUT 2 ON FLOOR PLAN.
  
 PLEASE CORRECT AND RESUBMIT.
 REVIEW BY KEN STEVENS (561) 659-8096
 X'S 8389/8377

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-05-24 Cont ID  
Sent By lsmith Date 2001-05-24 Time 14:25 Rev Time 4.00
Received By lsmith Date   Time   Sent To  
Notes
2001-05-24 00:00:00PROOVISO:
 1. PAY RADON FEES $48.02
 2. SUPPLY SURVEY WITH FF ELEVATION SHOWN
 3. UP VALUE TO $269791.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-04-20 Cont ID  
Sent By sgraham Date 2001-04-20 Time 15:02 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***