Plan Review Details - Permit 01040869
Plan Review Stops For Permit 01040869
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-07-18 Cont ID  
Sent By jwitmer Date 2001-07-18 Time 11:09 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-18 00:00:00PROVISO: SBC 407.1.3.4 EITHER(1) OR(2)
 JW 7/18/01

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-07-16 Cont ID  
Sent By jwitmer Date 2001-07-16 Time 18:05 Rev Time 8.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-07-16 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01040869
 2400 CENTERPARK W DRIVE
 SUITE # 100
 LEIGHTON MCGINN
 863-4455
  
 1)- SBC 903.1 APPROVED FIRE SPRINKLER
 EQUIPMENT, DEVICES AND LAYOUT OF THE
 COMPLETE SYSTEM.
  
 2)- SBC 308.2.2: CONTROL AREAS CONTAIN-
 ING HAZARDOUS MATERIAL NOT EXCEEDING THE
 EXEMPT QUANITIES SHALL BE PERMITTED IN
 ALL OCCUPANCIES. THE CONTROL AREAS SHALL
 BE SEPERATED BY 1-HR. FIRE RESISTANT
 CONSTRUCTION WITH 3/4 HR OPRNING PROTECT
 ION WITH SELF CLOSING OR AUTOMATIC CLOS-
 ING DEVICES IN ACCORDANCE WITH
 705.1.3.2.3. MACHINE SHOP, ASSEMBLY-138A
 AND ASSEMBLY 138B.
  
 3)- SBC T 308.2B: ALLOWABLE LIMIT OF
 CLASS 1-A FLAMMABLE/ COMBUSTIBLE LIQUIDS
 FOR A SPRINKLERED BLDG. NOT IN A CABINET
 IS 60 GAL./ CONTROL AREA.
  
 4)- CHIP SPIN AREA: SBC 308.2.3: WHEN
 STORED AMOUNTS OF ANY HAAZARDOUS MATER-
 IAL LISTED IN TABLES308.2A THROUGH
 308.2D IS EXCEEDED IN ANY ONE CONTROL
 AREA, SUCH STORAGE SHALL BE WITHIN A
 ROOM OR BUILDING CONFORMING TO THE CODE
 REQUIREMENTS FOR H2 OCCUPANCIES. 440 GAL
 OF HAZARDOUS MATERIALS ARE LOCATED IN
 THE CHIP SPIN AREA.
  
 5)- SBC TABLE 704.1.4 REQUIRES A 2HR.
 SEPERATION BETWEEN THE H2 OCCUPANCY AND
 THE FACTORY / MACHINE SHOP ( FACTORY OCC
 UPANCY).
  
 6)- SBC 407.1.3.4: HIGHLY TOXIC SOLIDS
 OR LIQUIDS: EXTERIOR STORAGE OF HIGHLY
 TOXIC SOLIDS OR LIQUIDS SHALL BE IN FIRE
 RESISTANT CONTAINERS OR SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
 1)- THE STORAGE AREA SHALL BE PROTECT-
 ED BY AN AUTOMATIC, OPEN HEAD, DELUGE
 SYSTEM OF THE TYPE AND DENSITY SPECIFIED
 IN NFPA 13 OR;
 2)- STORAGE SHALL BE UNDER A ROOF
 STRUCTURE OF NONCOMBUSTIBLE CONSTRUCTION
 WITH THE AREA UNDER THE ROOF PROTECTED
 BY AN AUTOMATIC FIRE EXTINGUISHING
 SYSTEM.
  
 7)- SBC 407.2.10: VISIBLE HAZARD
 IDENTIFICATION SIGNS AS SPECIFIED IN
 NFPA 704 SHALL BE PLACED AT ALL ENTRANCE
 TO LOCATIONS WHERE HAZARDOUS MATERIALS
 ARE STORED, DISPENSED USED OR HANDLED IN
 QUANITIES IN EXCESS OF THE EXEMPT
 AMOUNTS.
  
 8)- SBC 407.2.11: SECURITY DISPENSING,
 USE & HANDELING AREAS SHALL BE SECURED
 AGAINST UNATHORIZED ENTRY. STORAGE AREAS
 OF HIGHLY TOXIC AND TOXIC COMPRESSED
 GASSES SHALL BE SECURE AGAINST UNATHORIZ
 ED ENTRY.
  
 9)- CAFETERIA #130 60X32= 1920 SQ FT
 @ 15 FT/PER= 128 OCC. LOAD, GIVE SEATING
 ARRANGEMENT, > 50 PERSONS REQUIRES THE
 EGRESS DOORS TO SWING IN THE FLOW OF
 EXITING, SEE DOOR #40.
  
 10)- DOOR #30 FL ACCESSIBILITY 4.13.6
 REQUIRES MANEUVERING CLEARENCES AT DOORS
  
 11)- EITHER DOOR 30 OR 40 WILL BE REQUIR
 ED TO MEET THE EXITING REQUIREMENTS OF
 2 EXITS ONE WILL NEED TO MEET THE SWING
 REQUIREMENTS FOR EXITING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-24 Cont ID  
Sent By jwitmer Date 2001-04-24 Time 06:34 Rev Time 5.28
Received By hpiskura Date   Time   Sent To  
Notes
2001-04-24 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01040869
 2400 CENTERPARK W DRIVE
 LEIGHTON MCGINN
 863-4455
  
 1)- LAY OUT OF OFFICE FURNITURE FOR ROOM
 123A & B, MINIMUM ACCESS AISLES.
  
 2)- CONTAINMENT DIKE: SIZE OF NITROGEN
 TANK IN LBS. OR GALLONS. SBC 407.2.3.4
 TO MEET THE SECONDARY CONTAINMENT RE
 QUIREMENTS.
  
 3)- SBC 104.2.2: MEDICAL GASSES WILL
 REQUIRE A SEPERATE PERMIT(COMPRESSED
 GASSES).
  
 4)- SBC 407.1.3.5. LABORATORY HOODS:
 WHERE FLAMMABLE MATERIALS ARE TO BE USED
 SHALL REQUIRE A AUTOMATIC SPRINKLER
 SYSTEM.
  
 5)- SBC 903.1 APPROVED FIRE SPRINKLER
 EQUIPMENT, DEVICES,AND LAYOUT OF THE
 COMPLETE SYSTEM.
  
 6)- PREFABRICATED MEZZANINE STRUCTURE
 LOCATION MISSING ON THE FLOOR PLAN. LOCA
 TION OF STAIRS ISN'T CLEAR THERE IS
 EITHER A LANDING MISSING AT THE TOP OF
 THE STAIR OR BOTTOM. ATTACHED ARE SHEETS
 WITH REQUIREMENTS FOR MEZZANINES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2001-12-10 Cont ID  
Sent By dpalmer Date 2001-12-10 Time 08:51 Rev Time 0.00
Received By dpalmer Date 2001-12-10 Time 08:51 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2001-11-20 Cont ID  
Sent By dpalmer Date 2001-11-20 Time 18:35 Rev Time 0.00
Received By dpalmer Date 2001-11-20 Time 18:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-11-05 Cont ID  
Sent By dpalmer Date 2001-11-05 Time 18:03 Rev Time 0.00
Received By dpalmer Date 2001-11-05 Time 18:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-10-26 Cont ID  
Sent By dpalmer Date 2001-10-26 Time 14:18 Rev Time 0.00
Received By dpalmer Date 2001-10-26 Time 14:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-10-03 Cont ID  
Sent By dpalmer Date 2001-10-03 Time 13:12 Rev Time 0.00
Received By dpalmer Date 2001-10-03 Time 12:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-07-31 Cont ID  
Sent By dpalmer Date 2001-07-31 Time 10:59 Rev Time 0.00
Received By dpalmer Date 2001-07-31 Time 10:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-16 Cont ID  
Sent By dpalmer Date 2001-07-16 Time 10:33 Rev Time 0.00
Received By dpalmer Date 2001-07-12 Time 16:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-04-27 Cont ID  
Sent By dpalmer Date 2001-04-27 Time 05:52 Rev Time 0.00
Received By hpiskura Date 2001-04-27 Time 05:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-06-26 Cont ID  
Sent By lsmith Date 2001-06-26 Time 08:24 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-12-17 Cont ID  
Sent By mcarsill Date 2001-12-17 Time 12:09 Rev Time 0.00
Received By mcarsill Date 2001-12-17 Time 12:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-07-09 Cont ID  
Sent By dpalmer Date 2001-12-10 Time 08:51 Rev Time 0.00
Received By mcarsill Date 2001-07-09 Time 15:37 Sent To  
Notes
2001-07-09 00:00:00ON JULY 9, 2001, GRAHAM BLACK OF HEDRICK
 BROTHERS CONSTRUCTION BROUGHT PAPERWORK
 FOR THE ABOVE PLAN. THIS INFORMATION
 WAS SUBMITTED INTO THE PLANS AND THE
 ASSOCIATED PAPERWORK WAS INCLUDED WITH
 THE PERMIT APPLICATION.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-07-05 Cont ID  
Sent By mcarsill Date 2001-07-05 Time 14:16 Rev Time 0.00
Received By mcarsill Date 2001-07-05 Time 14:16 Sent To  
Notes
2001-07-05 00:00:001) EXIT DOORS IN CAFETERIA 130 SWING
 IN THE WRONG DIRECTION. EXIT DOORS
 SHOULD SWING IN THE DIRECTION OF EXIT
 TRAVEL SINCE OCCUPANT LOAD IS NOTED TO
 BE 132 PERSONS. EVEN IF THE ROOM HAS 50
 OR MORE PERSONS, THE DOORS SHOULD SWING
 IN THE DIRECTION OF EXIT TRAVEL.
 2) DETAILS WERE PROVIDED FOR THE HOOD
 EXHAUST USED TO EXHUAST THE IONOX FUMES
 USED IN THE DEGREASER. IF THIS HOOD IS
 USED TO EXHUAST NOXIOUS GASES, FLAMMABLE
 OR CORROSIVE MATERIALS, THEN COMPLIANCE
 WITH SECTION 506 OF THE STANDARD
 MECHANICAL CODE, EXHUAST OUTLETS IS TO
 BE PROVIDED.
 3) TRAVEL DISTANCE SHOWN FROM THE
 MACHINE SHOP DOWN THE CORRIDOR INTO THE
 ASSEMBLY ROOM DOES NOT APPEAR TO BE THE
 MOST DIRECT ROUTE AND WOULD BE
 CONFUSING TO USE.
 4) PLEASE PROVIDE CHEMICAL LIST
 AMOUNTS TO THIS OFFICE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-20 Cont ID  
Sent By mcarsill Date 2001-04-20 Time 15:48 Rev Time 0.00
Received By mcarsill Date 2001-04-20 Time 15:48 Sent To  
Notes
2001-04-20 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. FIRE SPRINKLER DRAWINGS
 ARE REQUIRED PRIOR TO RECEIVING A
 BUILDING PERMIT.
 2) FIRE ALARM CIRCUITS TO BE CLASS A,
 STYLE D, NOT CLASS B, STYLE C AS
 REFLECTED IN THE FIRE ALARM NOTES
 SECTION. SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM SYSTEM
 INSTALLATION.
 3) PLEASE PROVIDE DETAILS ON NITROGEN
 TANK INSTALLATION.
 4) PLEASE PROVIDE DETAILS ON EXHAUST
 HOOD AND WHAT WILL IT BE USED FOR.
 5) PLEASE PROVIDE MORE DETAILS ON
 HEAT TREAT OVEN LOCATED IN ROOM 139.
 6) PLEASE PROVIDE DETAILS ON FURNACE
 LOCATED IN ROOM 136.
 7) PLEASE PROVIDE A LIFE SAFETY PLAN
 TO THIS OFFICE. THIS PLAN IS TO
 INCLUDE OCCUPANT LOAD CALCULATIONS AND
 TRAVEL DISTANCES TO EXITS.
 8) PLEASE SUBMIT A CHEMICAL LIST TO
 THIS OFFICE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pkrauss Date 2001-12-10 Time 11:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-20 Cont ID  
Sent By pkrauss Date 2001-07-18 Time 11:14 Rev Time 3.00
Received By pkrauss Date 2001-07-18 Time 11:14 Sent To  
Notes
2001-07-20 00:00:00********************PROVISO*************
  
  
 EXHAUST OUTLETS SHALL COMPLY WITH 506.1.
  
 PLEASE SUBMIT INFORMATION FOR DEGREASER
 HOOD AS TO WHAT CHEMICAL WILL BE USED
 FOR DEGREASING AND AIR MAKE-UP FOR HOOD.
  
  
 ALL WORK PER CITY CODE SUBJECT TO FIELD
 INSPECTORS APPROVAL.
  
 PROVISO COMMENTS TO BE ADDRESSED PRIOR
 TO FIRST INSPECTION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-05-11 Cont ID  
Sent By pkrauss Date 2001-05-11 Time 09:33 Rev Time 3.00
Received By pkrauss Date 2001-05-11 Time 09:33 Sent To  
Notes
2001-05-11 00:00:00********************DENIED**************
  
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS AS PER ASHRAE 62-89.
  
 2.PLEASE PROVIDE AIR BALANCE SCHEDULE
 TO SHOW COMPLIANCE WITH 1997 SMC
 501.2.
  
 3.RTU 11 ON SCHEDULE INDICATES 3000
 CFM ON SCHEDULE AND PLAN TOTALS
 4020 CFM.SCHEDULE AND PLAN NEED
 TO CORRELATE.
  
 4.RTU 7A SCHEDULE INDICATES 3800 CFM
 PLAN REFLECTS 2330, A DIFFERENCE
 OF 1470 CFM.
  
 5.RTU 7 SCHEDULE 3200 CFM, PLAN 3310
 CFM.
  
 6.RTU 6 SCHEDULE 4200 CFM, PLAN 4700
 CFM.
  
 7.THE REST OF THE ROOF TOP UNITS THE
 SCHEDULE SHOWS MORE CFM'S THAN THE
 PLAN BUT ARE WITHIN RANGE.
  
 8.FIRE DAMPERS ON DRAWING M2.1 IN
 CORRIDOR 135A, ARE THEY FIRE
 DAMPERS OR FIRE/SMOKE DAMPERS?
  
 9.DRAWING M6.1, DETAIL FOR A/C ROOF
 EQUIPMENT, WE ARE UNDER THE
 STANDARD MECHANICAL CODE NOT THE
 SOUTH FLORIDA BUILDING CODE.
 CONDENDSER UNIT STAND SHALL COMPLY
 WITH THE AMENDED 1997 SMC 304.2.5,
 MINIMUM OF 18" FROM ROOF SURFACE TO
 THE BOTTOM OF C.U. SUPPORT RAIL.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 NOTE:MECHANICAL PLANS AND PERMIT ARE
 REQUIRED FOR CHILLER, CHILL WATER
 PIPING AND ANY EQUIPMENT SERVED
 BY CHILLED WATER.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-11-02 Cont ID  
Sent By pschmitz Date 2001-11-02 Time 09:03 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-11-02 00:00:00PLUMBING REVISION, PRIVATE BATH CURB IN
 SHOWER REMOVED TO 1/2" RISE,
 DOOR TO SWING OUT.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-07-30 Cont ID  
Sent By jleech Date 2001-07-30 Time 15:02 Rev Time 1.50
Received By jleech Date 2001-07-30 Time 15:01 Sent To  
Notes
2001-07-30 00:00:00REVISIONS; ADDITION OF EYEWASH AND
 SHOWERS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-07-20 Cont ID  
Sent By pschmitz Date 2001-07-20 Time 11:14 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-07-20 00:00:00PLUMBING PLAN,PROVISO
 PREVIOUS COMMENTS DATED 05-09-01
 (3) SHT P5-1 COMPLY WITH NFPA-99,CH-10
 LABORTORIES; ADDRESS EA. SEC.IN CH-10
 RE: HAZARDOUS MATERIALS PROCEDURE POLICY
 FOR THE STORAGE AND USE OF HAZARDOUS
 CHEMICALS. PROVIDE A OXYGEN DEPELETION
 ALARM.
 PREVIOUS COMMENT DATED 07-11-01
 (1) COMPLY WITH MFG MSDS REQUIRMENTS,
 SAFTEY SHOWERS WITH DRAINS (INSIDE BLDG)
 REQUIRED AS PER MFG.INSTRUCTIONS.
 (1) NEW COMMENT: REVISED PLANS BEFORE
 1ST ROUGH APPROVAL.
 (2) ALL WORK PER CITY CODES SUBJECT TO
 FIELD INSPECTOR APPROVAL.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X 8233

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-07-11 Cont ID  
Sent By jleech Date 2001-07-11 Time 17:57 Rev Time 2.00
Received By jleech Date 2001-07-11 Time 17:56 Sent To  
Notes
2001-07-11 00:00:00DENIED;
  
 1.BECAUSE OF CHEMICALS THAT WILL BE
 STORED AND USED DALUGE SHOWERS AND
 EYE WASH STATIONS NEED TO BE INSTALLED
 AS SAFTY EQUIPMENT. SHOW ADDITIONAL
 PIPING REQUIRED ON PLANS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-09 Cont ID  
Sent By pschmitz Date 2001-05-09 Time 14:37 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-09 00:00:00PLUMBING PLAN REVIEWDENIED
 CODE REFERENCES SPC-94, NFPA-99 CH.10
 (1) SHT A-3 COMPLY WITH FACBC-97
 SEC.4.1.6 H/C ACCESSIBLE BUILDINGS
 SHOW ACCESSIBLE ROUTE,TURNING RADIUS,
 CLEAR FLOOR SPACE,IN ALL AREAS.
 EXECUTIVE OFFICE #114 ,TO BE H/C
 ADAPTABLE BACKING IN WALLS,SHO,NO CURB.
 (2) SHT P2.1 ENVIRO LAB, ALL INDIRECT
 WASTE TO FLOOF SINKS,SEC 802.
 (3) SHT P5.1 COMPLY W/NFPA-99 CH 10,
 LABORTORIES, ADDRESS EACH SECTION IN
 CHAPTER 10,RE: NITROGEN GAS. HAZARD,
 PROCEDURE POLICY,STORAGE AND TRANSFERE,
 QUANITY, ALARM FOR OXYGEN DEPELETION
 MSDS SHTS.
 (4) SHT P6.1 INFORMATION ON COMPRESSED
 AIR, LOCATION AND SOURCE OF COMPRESSED
 AIR.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-25 Cont ID  
Sent By sgraham Date 2001-06-25 Time 15:17 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***