Plan Review Stops For Permit 01040869 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2001-07-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-07-18 |
Time |
11:09 |
Rev Time |
3.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-07-18 00:00:00 | PROVISO: SBC 407.1.3.4 EITHER(1) OR(2) | | JW 7/18/01 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2001-07-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-07-16 |
Time |
18:05 |
Rev Time |
8.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-07-16 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01040869 | | 2400 CENTERPARK W DRIVE | | SUITE # 100 | | LEIGHTON MCGINN | | 863-4455 | | | | 1)- SBC 903.1 APPROVED FIRE SPRINKLER | | EQUIPMENT, DEVICES AND LAYOUT OF THE | | COMPLETE SYSTEM. | | | | 2)- SBC 308.2.2: CONTROL AREAS CONTAIN- | | ING HAZARDOUS MATERIAL NOT EXCEEDING THE | | EXEMPT QUANITIES SHALL BE PERMITTED IN | | ALL OCCUPANCIES. THE CONTROL AREAS SHALL | | BE SEPERATED BY 1-HR. FIRE RESISTANT | | CONSTRUCTION WITH 3/4 HR OPRNING PROTECT | | ION WITH SELF CLOSING OR AUTOMATIC CLOS- | | ING DEVICES IN ACCORDANCE WITH | | 705.1.3.2.3. MACHINE SHOP, ASSEMBLY-138A | | AND ASSEMBLY 138B. | | | | 3)- SBC T 308.2B: ALLOWABLE LIMIT OF | | CLASS 1-A FLAMMABLE/ COMBUSTIBLE LIQUIDS | | FOR A SPRINKLERED BLDG. NOT IN A CABINET | | IS 60 GAL./ CONTROL AREA. | | | | 4)- CHIP SPIN AREA: SBC 308.2.3: WHEN | | STORED AMOUNTS OF ANY HAAZARDOUS MATER- | | IAL LISTED IN TABLES308.2A THROUGH | | 308.2D IS EXCEEDED IN ANY ONE CONTROL | | AREA, SUCH STORAGE SHALL BE WITHIN A | | ROOM OR BUILDING CONFORMING TO THE CODE | | REQUIREMENTS FOR H2 OCCUPANCIES. 440 GAL | | OF HAZARDOUS MATERIALS ARE LOCATED IN | | THE CHIP SPIN AREA. | | | | 5)- SBC TABLE 704.1.4 REQUIRES A 2HR. | | SEPERATION BETWEEN THE H2 OCCUPANCY AND | | THE FACTORY / MACHINE SHOP ( FACTORY OCC | | UPANCY). | | | | 6)- SBC 407.1.3.4: HIGHLY TOXIC SOLIDS | | OR LIQUIDS: EXTERIOR STORAGE OF HIGHLY | | TOXIC SOLIDS OR LIQUIDS SHALL BE IN FIRE | | RESISTANT CONTAINERS OR SHALL COMPLY | | WITH ONE OF THE FOLLOWING: | | 1)- THE STORAGE AREA SHALL BE PROTECT- | | ED BY AN AUTOMATIC, OPEN HEAD, DELUGE | | SYSTEM OF THE TYPE AND DENSITY SPECIFIED | | IN NFPA 13 OR; | | 2)- STORAGE SHALL BE UNDER A ROOF | | STRUCTURE OF NONCOMBUSTIBLE CONSTRUCTION | | WITH THE AREA UNDER THE ROOF PROTECTED | | BY AN AUTOMATIC FIRE EXTINGUISHING | | SYSTEM. | | | | 7)- SBC 407.2.10: VISIBLE HAZARD | | IDENTIFICATION SIGNS AS SPECIFIED IN | | NFPA 704 SHALL BE PLACED AT ALL ENTRANCE | | TO LOCATIONS WHERE HAZARDOUS MATERIALS | | ARE STORED, DISPENSED USED OR HANDLED IN | | QUANITIES IN EXCESS OF THE EXEMPT | | AMOUNTS. | | | | 8)- SBC 407.2.11: SECURITY DISPENSING, | | USE & HANDELING AREAS SHALL BE SECURED | | AGAINST UNATHORIZED ENTRY. STORAGE AREAS | | OF HIGHLY TOXIC AND TOXIC COMPRESSED | | GASSES SHALL BE SECURE AGAINST UNATHORIZ | | ED ENTRY. | | | | 9)- CAFETERIA #130 60X32= 1920 SQ FT | | @ 15 FT/PER= 128 OCC. LOAD, GIVE SEATING | | ARRANGEMENT, > 50 PERSONS REQUIRES THE | | EGRESS DOORS TO SWING IN THE FLOW OF | | EXITING, SEE DOOR #40. | | | | 10)- DOOR #30 FL ACCESSIBILITY 4.13.6 | | REQUIRES MANEUVERING CLEARENCES AT DOORS | | | | 11)- EITHER DOOR 30 OR 40 WILL BE REQUIR | | ED TO MEET THE EXITING REQUIREMENTS OF | | 2 EXITS ONE WILL NEED TO MEET THE SWING | | REQUIREMENTS FOR EXITING. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 EX 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-04-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-04-24 |
Time |
06:34 |
Rev Time |
5.28 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-04-24 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01040869 | | 2400 CENTERPARK W DRIVE | | LEIGHTON MCGINN | | 863-4455 | | | | 1)- LAY OUT OF OFFICE FURNITURE FOR ROOM | | 123A & B, MINIMUM ACCESS AISLES. | | | | 2)- CONTAINMENT DIKE: SIZE OF NITROGEN | | TANK IN LBS. OR GALLONS. SBC 407.2.3.4 | | TO MEET THE SECONDARY CONTAINMENT RE | | QUIREMENTS. | | | | 3)- SBC 104.2.2: MEDICAL GASSES WILL | | REQUIRE A SEPERATE PERMIT(COMPRESSED | | GASSES). | | | | 4)- SBC 407.1.3.5. LABORATORY HOODS: | | WHERE FLAMMABLE MATERIALS ARE TO BE USED | | SHALL REQUIRE A AUTOMATIC SPRINKLER | | SYSTEM. | | | | 5)- SBC 903.1 APPROVED FIRE SPRINKLER | | EQUIPMENT, DEVICES,AND LAYOUT OF THE | | COMPLETE SYSTEM. | | | | 6)- PREFABRICATED MEZZANINE STRUCTURE | | LOCATION MISSING ON THE FLOOR PLAN. LOCA | | TION OF STAIRS ISN'T CLEAR THERE IS | | EITHER A LANDING MISSING AT THE TOP OF | | THE STAIR OR BOTTOM. ATTACHED ARE SHEETS | | WITH REQUIREMENTS FOR MEZZANINES. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 EX 8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
P |
Date |
2001-12-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-12-10 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-12-10 |
Time |
08:51 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2001-11-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-11-20 |
Time |
18:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-11-20 |
Time |
18:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
P |
Date |
2001-11-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-11-05 |
Time |
18:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-11-05 |
Time |
18:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2001-10-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-26 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-26 |
Time |
14:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2001-10-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-03 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-03 |
Time |
12:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2001-07-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-07-31 |
Time |
10:59 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-07-31 |
Time |
10:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-07-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-07-16 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-07-12 |
Time |
16:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-04-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-04-27 |
Time |
05:52 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2001-04-27 |
Time |
05:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2001-06-26 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-06-26 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2001-12-17 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-12-17 |
Time |
12:09 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-12-17 |
Time |
12:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2001-07-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-12-10 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-09 |
Time |
15:37 |
Sent To |
|
|
Notes |
2001-07-09 00:00:00 | ON JULY 9, 2001, GRAHAM BLACK OF HEDRICK | | BROTHERS CONSTRUCTION BROUGHT PAPERWORK | | FOR THE ABOVE PLAN. THIS INFORMATION | | WAS SUBMITTED INTO THE PLANS AND THE | | ASSOCIATED PAPERWORK WAS INCLUDED WITH | | THE PERMIT APPLICATION. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2001-07-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-05 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-05 |
Time |
14:16 |
Sent To |
|
|
Notes |
2001-07-05 00:00:00 | 1) EXIT DOORS IN CAFETERIA 130 SWING | | IN THE WRONG DIRECTION. EXIT DOORS | | SHOULD SWING IN THE DIRECTION OF EXIT | | TRAVEL SINCE OCCUPANT LOAD IS NOTED TO | | BE 132 PERSONS. EVEN IF THE ROOM HAS 50 | | OR MORE PERSONS, THE DOORS SHOULD SWING | | IN THE DIRECTION OF EXIT TRAVEL. | | 2) DETAILS WERE PROVIDED FOR THE HOOD | | EXHAUST USED TO EXHUAST THE IONOX FUMES | | USED IN THE DEGREASER. IF THIS HOOD IS | | USED TO EXHUAST NOXIOUS GASES, FLAMMABLE | | OR CORROSIVE MATERIALS, THEN COMPLIANCE | | WITH SECTION 506 OF THE STANDARD | | MECHANICAL CODE, EXHUAST OUTLETS IS TO | | BE PROVIDED. | | 3) TRAVEL DISTANCE SHOWN FROM THE | | MACHINE SHOP DOWN THE CORRIDOR INTO THE | | ASSEMBLY ROOM DOES NOT APPEAR TO BE THE | | MOST DIRECT ROUTE AND WOULD BE | | CONFUSING TO USE. | | 4) PLEASE PROVIDE CHEMICAL LIST | | AMOUNTS TO THIS OFFICE. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-04-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-04-20 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-04-20 |
Time |
15:48 |
Sent To |
|
|
Notes |
2001-04-20 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | WITH PLANS. FIRE SPRINKLER DRAWINGS | | ARE REQUIRED PRIOR TO RECEIVING A | | BUILDING PERMIT. | | 2) FIRE ALARM CIRCUITS TO BE CLASS A, | | STYLE D, NOT CLASS B, STYLE C AS | | REFLECTED IN THE FIRE ALARM NOTES | | SECTION. SEPARATE PLANS AND PERMITS | | REQUIRED FOR FIRE ALARM SYSTEM | | INSTALLATION. | | 3) PLEASE PROVIDE DETAILS ON NITROGEN | | TANK INSTALLATION. | | 4) PLEASE PROVIDE DETAILS ON EXHAUST | | HOOD AND WHAT WILL IT BE USED FOR. | | 5) PLEASE PROVIDE MORE DETAILS ON | | HEAT TREAT OVEN LOCATED IN ROOM 139. | | 6) PLEASE PROVIDE DETAILS ON FURNACE | | LOCATED IN ROOM 136. | | 7) PLEASE PROVIDE A LIFE SAFETY PLAN | | TO THIS OFFICE. THIS PLAN IS TO | | INCLUDE OCCUPANT LOAD CALCULATIONS AND | | TRAVEL DISTANCES TO EXITS. | | 8) PLEASE SUBMIT A CHEMICAL LIST TO | | THIS OFFICE. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2001-12-10 |
Time |
11:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-07-20 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-07-18 |
Time |
11:14 |
Rev Time |
3.00 |
Received By |
pkrauss |
Date |
2001-07-18 |
Time |
11:14 |
Sent To |
|
|
Notes |
2001-07-20 00:00:00 | ********************PROVISO************* | | | | | | EXHAUST OUTLETS SHALL COMPLY WITH 506.1. | | | | PLEASE SUBMIT INFORMATION FOR DEGREASER | | HOOD AS TO WHAT CHEMICAL WILL BE USED | | FOR DEGREASING AND AIR MAKE-UP FOR HOOD. | | | | | | ALL WORK PER CITY CODE SUBJECT TO FIELD | | INSPECTORS APPROVAL. | | | | PROVISO COMMENTS TO BE ADDRESSED PRIOR | | TO FIRST INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-05-11 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-05-11 |
Time |
09:33 |
Rev Time |
3.00 |
Received By |
pkrauss |
Date |
2001-05-11 |
Time |
09:33 |
Sent To |
|
|
Notes |
2001-05-11 00:00:00 | ********************DENIED************** | | | | 1.PLEASE PROVIDE OUTSIDE AIR | | CALCULATIONS AS PER ASHRAE 62-89. | | | | 2.PLEASE PROVIDE AIR BALANCE SCHEDULE | | TO SHOW COMPLIANCE WITH 1997 SMC | | 501.2. | | | | 3.RTU 11 ON SCHEDULE INDICATES 3000 | | CFM ON SCHEDULE AND PLAN TOTALS | | 4020 CFM.SCHEDULE AND PLAN NEED | | TO CORRELATE. | | | | 4.RTU 7A SCHEDULE INDICATES 3800 CFM | | PLAN REFLECTS 2330, A DIFFERENCE | | OF 1470 CFM. | | | | 5.RTU 7 SCHEDULE 3200 CFM, PLAN 3310 | | CFM. | | | | 6.RTU 6 SCHEDULE 4200 CFM, PLAN 4700 | | CFM. | | | | 7.THE REST OF THE ROOF TOP UNITS THE | | SCHEDULE SHOWS MORE CFM'S THAN THE | | PLAN BUT ARE WITHIN RANGE. | | | | 8.FIRE DAMPERS ON DRAWING M2.1 IN | | CORRIDOR 135A, ARE THEY FIRE | | DAMPERS OR FIRE/SMOKE DAMPERS? | | | | 9.DRAWING M6.1, DETAIL FOR A/C ROOF | | EQUIPMENT, WE ARE UNDER THE | | STANDARD MECHANICAL CODE NOT THE | | SOUTH FLORIDA BUILDING CODE. | | CONDENDSER UNIT STAND SHALL COMPLY | | WITH THE AMENDED 1997 SMC 304.2.5, | | MINIMUM OF 18" FROM ROOF SURFACE TO | | THE BOTTOM OF C.U. SUPPORT RAIL. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | NOTE:MECHANICAL PLANS AND PERMIT ARE | | REQUIRED FOR CHILLER, CHILL WATER | | PIPING AND ANY EQUIPMENT SERVED | | BY CHILLED WATER. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2001-11-02 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-11-02 |
Time |
09:03 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-11-02 00:00:00 | PLUMBING REVISION, PRIVATE BATH CURB IN | | SHOWER REMOVED TO 1/2" RISE, | | DOOR TO SWING OUT. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2001-07-30 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-07-30 |
Time |
15:02 |
Rev Time |
1.50 |
Received By |
jleech |
Date |
2001-07-30 |
Time |
15:01 |
Sent To |
|
|
Notes |
2001-07-30 00:00:00 | REVISIONS; ADDITION OF EYEWASH AND | | SHOWERS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2001-07-20 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-07-20 |
Time |
11:14 |
Rev Time |
2.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-07-20 00:00:00 | PLUMBING PLAN,PROVISO | | PREVIOUS COMMENTS DATED 05-09-01 | | (3) SHT P5-1 COMPLY WITH NFPA-99,CH-10 | | LABORTORIES; ADDRESS EA. SEC.IN CH-10 | | RE: HAZARDOUS MATERIALS PROCEDURE POLICY | | FOR THE STORAGE AND USE OF HAZARDOUS | | CHEMICALS. PROVIDE A OXYGEN DEPELETION | | ALARM. | | PREVIOUS COMMENT DATED 07-11-01 | | (1) COMPLY WITH MFG MSDS REQUIRMENTS, | | SAFTEY SHOWERS WITH DRAINS (INSIDE BLDG) | | REQUIRED AS PER MFG.INSTRUCTIONS. | | (1) NEW COMMENT: REVISED PLANS BEFORE | | 1ST ROUGH APPROVAL. | | (2) ALL WORK PER CITY CODES SUBJECT TO | | FIELD INSPECTOR APPROVAL. | | END OF COMMENTSPAUL SCHMITZ | | QUESTIONS561-659-8096X 8233 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2001-07-11 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-07-11 |
Time |
17:57 |
Rev Time |
2.00 |
Received By |
jleech |
Date |
2001-07-11 |
Time |
17:56 |
Sent To |
|
|
Notes |
2001-07-11 00:00:00 | DENIED; | | | | 1.BECAUSE OF CHEMICALS THAT WILL BE | | STORED AND USED DALUGE SHOWERS AND | | EYE WASH STATIONS NEED TO BE INSTALLED | | AS SAFTY EQUIPMENT. SHOW ADDITIONAL | | PIPING REQUIRED ON PLANS. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT 8369 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-05-09 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-05-09 |
Time |
14:37 |
Rev Time |
2.50 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-05-09 00:00:00 | PLUMBING PLAN REVIEWDENIED | | CODE REFERENCES SPC-94, NFPA-99 CH.10 | | (1) SHT A-3 COMPLY WITH FACBC-97 | | SEC.4.1.6 H/C ACCESSIBLE BUILDINGS | | SHOW ACCESSIBLE ROUTE,TURNING RADIUS, | | CLEAR FLOOR SPACE,IN ALL AREAS. | | EXECUTIVE OFFICE #114 ,TO BE H/C | | ADAPTABLE BACKING IN WALLS,SHO,NO CURB. | | (2) SHT P2.1 ENVIRO LAB, ALL INDIRECT | | WASTE TO FLOOF SINKS,SEC 802. | | (3) SHT P5.1 COMPLY W/NFPA-99 CH 10, | | LABORTORIES, ADDRESS EACH SECTION IN | | CHAPTER 10,RE: NITROGEN GAS. HAZARD, | | PROCEDURE POLICY,STORAGE AND TRANSFERE, | | QUANITY, ALARM FOR OXYGEN DEPELETION | | MSDS SHTS. | | (4) SHT P6.1 INFORMATION ON COMPRESSED | | AIR, LOCATION AND SOURCE OF COMPRESSED | | AIR. | | END OF COMMENTS PAUL SCHMITZ | | QUESTIONS 561-659-8096 X 8233 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-06-25 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-06-25 |
Time |
15:17 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|