Plan Review Details - Permit 01040868
Plan Review Stops For Permit 01040868
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-07-31 Cont ID  
Sent By lmartine Date 2001-07-27 Time 12:45 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-07-31 00:00:00 
 BUILDING COMMENTS
 -------------------
  
 1]
 SUBMIT COUNTY IMPACT FEE RECEIPT.
 2]
 PAY BALANCE OF PERMIT FEE $246.00.
 3]
 SUBMIT TESTING RESULTS FOR EXTERIOR
 GLAZING COMPLIANCE FOR IMPACT
 PROTECTION.
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-12 Cont ID  
Sent By hpiskura Date 2001-06-11 Time 07:15 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-06-12 00:00:00IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. CALL 233-5025 FOR MORE
 INFORMATION.
  
 SHOW A DETAIL FOR THE B10 BEAM
 CONNECTION TO THE C2 COLUMNS.
  
 SHOW A CONSTRUCTION DETAIL FOR THE METAL
 STUD WALL DEPICTED IN SECTION S3/2.
 INCLUDE FASTENERS AND SPACING AS WELL
 AS WINDOW CONNECTION.
  
 NOTE THE ASSUMED SOIL BEARING VALUE.
  
 THE PAD FOOTING ON SHEET S1 GRID G4 IS
 NOT LABELED.
  
 SECTION 1 S/3 SHOWS A 12" LONG ANGLE
 SUPPORTING THE BAR JOIST WHICH WILL
 CONFLICT THE NOTED 2' OC SPACING OF THE
 ANCHOR BOLTS.
  
 S2 IN THE VICINITY OF GRID H & I 5 CALLS
 OUT AN ANGLE 3/8" THICK 8" LONG AND
 DOES NOT AGREE WITH S5 WHICH SHOWS A
 1/4" ANGLE APPARENTLY CONTINUOUS.
 PLEASE CLARIFY.
  
 PLEASE PROVIDE A RECENT SURVEY.IF THE
 PHASE I BUILDING IS ON THE SAME LOT SHOW
 THE OPENINGS IN THE FACING WALL SO THAT
 COMPLIANCE WITH SBC TABLE 600 MAY BE
 DETERMINED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-05-23 Cont ID  
Sent By dpalmer Date 2001-05-23 Time 07:06 Rev Time 0.00
Received By dpalmer Date 2001-06-04 Time 07:06 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-07-10 Cont ID  
Sent By mamini Date 2001-07-10 Time 14:23 Rev Time 4.00
Received By mamini Date 2001-07-10 Time 14:16 Sent To  
Notes
2001-07-10 00:00:00PASSED:
 1. RESPONSES TO THE PREVIOUS REVIEW
 COMMENTS DATED 5-16-01 SATISFACTORY.
 PALNS HAVE BEEN REVISED AND REQUESTED
 ITEMS PROVIDED.
  
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-05-16 Cont ID  
Sent By mamini Date 2001-05-16 Time 13:10 Rev Time 4.00
Received By mamini Date 2001-05-16 Time 11:24 Sent To  
Notes
2001-05-16 00:00:00FAILED :
 1. PLEASE COORDINATE WITH CIVIL ENGINEER
 AND PUBLIC UTILITIES ENGINEERING
 SERVICES FOR ALL UNDERGROUND UTILITY
 CHANGES.WE BELIEVE THAT SOME CHANGES
 ARE BEING MADE THAT MAY AFFECT THIS SITE
 ALSO.
 2. SECTION A-A, SHEET 4 OF 9 SHOWS A 10'
 U.E ADJACENT TO WEST R/W, PLEASE VERIFY
 IF THIS 10' U.E STILL NEEDED.ALL
 UTILITY EASEMENT SHOULD BE APPROVED BY
 PUBLIC UTILITY ENGINEERING SERVICES.
 3. PLEASE PROVIDE DETAILS FOR DUMPSTER
 ENCLOSURES.SHEET A-1 REFERS TO SP-1,
 THIS SHEET IS NOT SUBMITTED.
 4. PLEASE PROVIDE PARKING STALL DETAILS
 DIMENSIONS FOR BOTH H.C AND NONE-H.C
 5. PROVIDE STORM WATER CALCULATION FOR
 OUR REVIEW IF YOU HAVE NOT SUBMITTED TO
 JOSE DEL RIO, STORM WATER ENGINEER AT
 1000 45TH STREET WEST PALM BEACH, FL
 33407.
 6. PERVIOUS & IMPERVIOUS CALCULATION
 MUST BE SHOWN ON PAVING AND DRAINAGE,
 THE TOTAL AMOUNT MUST EQUAL 100% OF
 TOTAL SITE ACRES OR S.F.PLEASE STATE
 EITHER ADDRESS OR PROPERTY CONTROL
 NUMBER.STORM WATER CHANGES WILL BE
 CALCULATED FROM THESE DATA.
 7. ANY WORK WITHIN PUBLIC R.O.W REQUIRES
 A SEPARATE PERMIT THROUGH OFFICE OF CITY
 ENGINEER.
 8. DEP PERMIT FOR UNDERGROUND UTILITY
 WORKS IS REQUIRED.
 9. PLEASE PROVIDE POLLUTION PREVENTION
 PLANS.PLAN SHOULD BE INSTALLED IN
 FIELD PRIOR TO ANY EARTH WORK.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-07-09 Cont ID  
Sent By mcarsill Date 2001-07-09 Time 08:46 Rev Time 0.00
Received By mcarsill Date 2001-07-09 Time 08:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-05-09 Cont ID  
Sent By mcarsill Date 2001-05-09 Time 15:50 Rev Time 0.00
Received By mcarsill Date 2001-05-09 Time 15:50 Sent To  
Notes
2001-05-09 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 TO COMPLY WITH CITY CODE 3343-00.
 2) UNDERGROUND UTILITIES PLANNED FOR
 THE FIRE MAIN ARE TO BE LISTED FOR
 FIRE PROTECTION SERVICE AND COMPLY WITH
 NFPA 24, THE STANDARD FOR FIRE SERVICE
 MAINS AND THEIR APPURTENANCES.
 3) A KNOX-BOX RAPID ENTRY SYSTEM SHALL
 BE PROVIDED FOR THE BUILDING.
 4) WHY ARE EXISTING FIRE HYDRANTS BEING
 REMOVED, ONE ON BRISTOL AND ONE ON
 CENTERPARK WEST DRIVE.
 5) TENANT SEPARATION WALLS TO COMPLY
 WITH BUILDING CODE REGULATIONS.
 6) PLEASE INDICATE OCCUPANCY LOAD
 CALCULATIONS FOR THE BUILDING. PLEASE
 EXPLAIN EXITING RATIONALE. WILL A SINGLE
 MEANS OF EGRESS OR TWO MEANS OF EGRESS
 BE PROVIDED.
 7) DUCT SMOKE DETECTORS ARE REQUIRED
 IN AIR HANDLING SYSTEMS OVER 2000 CFM.
 WHEN ACTIVATED, THESE DEVICES ARE TO
 SHUT DOWN AIRT HANDLING EQUIPMENT.
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM INSTALLATION.
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-05-29 Cont ID  
Sent By ndenmark Date 2001-05-29 Time 08:48 Rev Time 0.33
Received By ndenmark Date 2001-05-29 Time 08:48 Sent To  
Notes
2001-05-29 00:00:00PROVISO:
 MINIMUM CLEARANCE OF 18" REQUIRED
 BETWEEN ROOF SURFACE AND BOTTOM OF
 SUPPORT STRUCTURE OF STAND

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-25 Cont ID  
Sent By pschmitz Date 2001-05-25 Time 15:09 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-25 00:00:00PROVISO: SHT PO-1 AIR CHAMBERS TO BE
 ACCESSIBLE, RECHARGEABLE.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-07 Cont ID  
Sent By sgraham Date 2001-06-07 Time 15:53 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-06-07 00:00:00NEED CITY COMMISSION APPROVAL