Plan Review Details - Permit 01040810
Plan Review Stops For Permit 01040810 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-05-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-05-02 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-05-02 |
Time |
16:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-05-10 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-05-10 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-05-10 |
Time |
08:34 |
Sent To |
|
|
Notes |
2001-05-10 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | TO,DURING AND AFTER CONSTRUCTION. | | 2) BUILDING ADDRESSES REQUIRED PER CITY | | CODE REQUIREMENTS. | | 3) ELECTRIC POWERED SMOKE DETECTORS | | REQUIRED ON EVERY LEVEL. | | 4) PORTABLE FIRE EXTINGUISHERS ARE | | REQUIRED. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-09-29 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-09-29 |
Time |
12:05 |
Rev Time |
0.10 |
Received By |
pkrauss |
Date |
2001-09-29 |
Time |
12:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-05-10 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-05-10 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
2001-05-10 |
Time |
16:00 |
Sent To |
|
|
Notes |
2001-05-10 00:00:00 | PER HMOSER |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2001-04-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-04-26 |
Time |
16:04 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2001-04-26 |
Time |
16:40 |
Sent To |
|
|
Notes |
2001-04-26 00:00:00 | PLUMBING PLAN REVIEW.REFERANCE SPC-94 | | | | PASSED | | | | PROVISO: SUBMIT SANITARY RISER REVISION. | | NO TUB ON RISER DIAGRAM IN BATH #2 | | AS SHOWN ON FLOOR PLAN. | | | | TYPICAL WATER RISER DIAGRAM - AIR | | CHAMBERS TO COMPLY WITH 607.8.3 | | MUST BE ACCESSABLE AND RECHARGEABLE. | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | EXT. 8377 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2001-05-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-05-12 |
Time |
17:36 |
Rev Time |
1.25 |
Received By |
jgomez |
Date |
2001-05-12 |
Time |
17:36 |
Sent To |
|
|
Notes |
2001-05-12 00:00:00 | APPROVED WITH PROVISO: SEE NOTES ON | | PERMIT 01040803. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-04-20 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-04-20 |
Time |
12:05 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy