Plan Review Stops For Permit 01040803 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-05-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-05-02 |
Time |
16:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-05-02 |
Time |
16:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-05-10 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-05-10 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-05-10 |
Time |
08:53 |
Sent To |
|
|
Notes |
2001-05-10 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | TO, DURING AND AFTER CONSTRUCTION. | | 2) BUILDING ADDRESSES REQUIRED PER CITY | | CODE. | | 3) ELECTRIC POWERED SMOKE DETECTORS ARE | | REQUIRED ON EVERY LEVEL. | | 4) PORTABLE FIRE EXTINGUISHERS ARE | | REQUIRED. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-11-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-11-01 |
Time |
12:23 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2001-11-01 |
Time |
12:23 |
Sent To |
|
|
Notes |
2001-11-01 00:00:00 | MECH REV 01040819 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-09-29 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-09-29 |
Time |
11:54 |
Rev Time |
0.10 |
Received By |
pkrauss |
Date |
2001-09-29 |
Time |
11:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-05-10 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-05-10 |
Time |
15:57 |
Rev Time |
0.33 |
Received By |
lsmith |
Date |
2001-04-28 |
Time |
11:05 |
Sent To |
|
|
Notes |
2001-05-10 00:00:00 | PER HMOSER |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2001-04-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-04-26 |
Time |
17:33 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2001-04-26 |
Time |
17:33 |
Sent To |
|
|
Notes |
2001-04-26 00:00:00 | PLUMBING PLAN REVIEW. SPC-94 | | | | ***PASSED*** | | | | PROVISO | | | | WATER RESER DIAGRAM. - AIR CHAMBERS MUST | | COMPLY WITH 607.8.3 AND MUST BE | | ACCESSABLE AND RECHARGEABLE | | | | REVIEW BY KEN STEVENS (561) 569-8096 | | EXT. 8377 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
6 |
Status |
P |
Date |
2001-09-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-09-10 |
Time |
10:14 |
Rev Time |
0.25 |
Received By |
jgomez |
Date |
2001-09-10 |
Time |
10:14 |
Sent To |
|
|
Notes |
2001-09-10 00:00:00 | TRUSS DRAWINGS REVIEW. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
5 |
Status |
F |
Date |
2001-08-17 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-08-17 |
Time |
18:13 |
Rev Time |
0.25 |
Received By |
jgomez |
Date |
2001-08-17 |
Time |
18:13 |
Sent To |
|
|
Notes |
2001-08-17 00:00:00 | TRUSS DRAWINGS 3RD CHECKLIST: | | | | 1-THE TWO SETS OF ENGINEERED TRUSS | | DON'T MATCH. THEY ARE TWO DIFFERENT | | SETS. ONE IS SIGNED ON JUNE 11TH AND | | THE OTHER ON JULY 25TH. | | -SET OF ENGINEERED DRAWINGS SIGNED ON | | JULY 25TH HAS TWO DIFFERENT MEAN ROOF | | HEIGHTS. ITEM THAT WAS ALREADY REVISED | | ON SET SIGNED ON JUNE 11TH. | | | | | | | | | | | | | | | | NOTES: | | -DRAWINGS ARE FILED UNDER PERMIT #: | | 01040803. | | -THESE COMMENTS APPLY TO PERMIT #S: | | 01040803, 01040806, 01040808 AND | | 01040810. | | -THERE WILL BE ADDITIONAL RESUBMITTAL | | FEES. SEE COPY OF POLICY ATTACHED. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
4 |
Status |
F |
Date |
2001-08-07 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-08-07 |
Time |
16:23 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2001-08-07 |
Time |
16:23 |
Sent To |
|
|
Notes |
2001-08-07 00:00:00 | REVIEW OF PRODUCT APPROVALS: | | 1-PROVIDE CURRENT DADE COUNTY PRODUCT | | APPROVAL FOR WINDOW MULLIONS. | | INFORMATION SUBMITTED IS NOT A | | PRODUCT APPROVAL. | | | | 2-STORM PANELS, SLIDING GLASS DOORS AND | | "CAST-CRETE" LINTELS ARE APPROVED. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
F |
Date |
2001-07-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-07-11 |
Time |
10:44 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2001-07-10 |
Time |
18:37 |
Sent To |
|
|
Notes |
2001-07-10 00:00:00 | TRUSS DRAWINGS SECOND CHECKLIST: | | | | 1-UPDATE ALL GENERAL TRUSS DETAILS AND | | SPECIFICATIONS.CLEARLY SPECIFY CODE | | USED FOR DESIGN CRITERIA. | | | | 2-CLARIFY WHY THERE ARE TWO DIFFERENT | | ENGINEERS SIGNING AND SEALING THE | | GENERAL DETAILS. FOLLOW 61G15-27 | | PROCEDURE TO SEAL ANOTHER'S WORK. | | | | 3-PROVIDE CLEAR AND LEGIBLE COPIES OF | | GENERAL DETAILS. | | | | | | NOTE: | | THESE ITEMS WERE ADDRESSED SEVERAL TIMES | | BEFORE & STILL THE SAME PACKAGE IS | | SUBMITTED OVER AND OVER WITHOUT MAKING | | THE NECESSARY CORRECTIONS. | | SEE ATTACHED COPY OF POLICY AND | | PROCEDURE FOR IMPLEMENTATION OF PERMIT | | FEE ADJUSTMENTS. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2001-05-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-05-30 |
Time |
17:46 |
Rev Time |
1.50 |
Received By |
jgomez |
Date |
2001-05-30 |
Time |
17:46 |
Sent To |
|
|
Notes |
2001-05-30 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | 1-TRUSS ENGINEER TO PROVIDE ALL HIS | | INFORMATION REQUIRED BY CHAPTER 61G15 | | OF FLORIDA BOARD OF PROFESSIONAL | | ENGINEERS AND CHAPTER 471 OF FLORIDA | | STATUTES. | | -PROVIDE INFO. ON TRUSS LAYOUT AS WELL. | | 2-TRUSS GENERAL DRAWINGS: | | -UPDATE DRAWINGS AS REQUIRED. SPECIFY | | CODE AND DESIGN CRITERIA USED. | | -(61G15-27): FOLLOW PROCEDURE TO SEAL | | ANOTHER'S WORK. | | -PROVIDE CLEAR, LEGIBLE AND UNCUT | | COPIES. | | 3-THERE IS ONLY ONE MEAN ROOF HEIGHT FOR | | ENTIRE BUILDING. TABLE 1606.2A SBC/97. | | 4-IF USING ASCE IT SHALL BE ASCE 7-95 | | FOR 145MPH NOT ASCE 7-93 FOR 110MPH. | | -COVER SHEET SAYS USING SBC/97. CLARIFY | | -SOME TRUSSES ARE DESIGNED USING ASCE | | AND OTHERS ARE USING SBC. CLARIFY. | | 5-ARCHITECT TO REVIEW ALL TRUSS DRAWINGS | | AFTER CORRECTIONS ARE DONE. | | 6-TRUSS S15 WAS DESIGNED WITH THREE | | BEARING POINTS. ARCHITECT TO SPECIFY | | CONNECTOR AT MID BEARING POINT. | | 7-ARCHITECT TO SPECIFY CONNECTOR THAT | | MEETS THE UPLIFT LOADS CALCULATED ON | | ENGINEERED TRUSSES S45, S46 AND T27. | | | | | | | | -THESE COMMENTS APPLY TO 01040803, | | 01040806, 01040808 AND 01040810. | | | | -IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT 659-8096 EXT. 8232. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2001-05-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-05-12 |
Time |
16:38 |
Rev Time |
1.25 |
Received By |
jgomez |
Date |
2001-05-12 |
Time |
16:38 |
Sent To |
|
|
Notes |
2001-05-12 00:00:00 | APPROVED WITH PROVISO: | | | | 1-FLOOD ZONE AO. WILL NEED TO PROVIDE | | ELEVATION CERTIFICATE. | | | | 2-TOWNHOUSES ARE SEPARATED BY TWO HOUR | | FIRE RATED WALL. MODEL C HAS GLASS | | BLOCK AT ZERO LOT LINE. PROVIDE TWO | | HOUR FIRE RATED GLASS BLOCK OR CLOSE | | OPENING. SEC 704.4.2 SBC 1997. | | | | 3-PROVIDE PRODUCT APPROVAL FOR: | | -SLIDING GLASS DOORS. | | -2 HOUR FIRE RATED GLASS BLOCK. | | -PRECAST LINTEL(NOTE: CURRENT PRODUCT | | APPROVAL WILL EXPIRE ON 5-21-01) | | -WINDOW MULLIONS. | | | | 4-PROVIDE COMPLETE INSTALLATION SCHED. | | AND KEY PLAN FOR STORM PANELS. | | | | 5-REVISE NOTE #2 ON SHEET BP-1: MAX. | | CHANGE IN LEVEL IS 1/4" OR 1/2" MAX. | | IF BEVELED. FAIR HOUSING ACT PAGE 4.4. | | | | | | NOTE:THIS COMMENTS APPLY TO THE | | FOLLOWING PERMIT #S: 01040803, | | 01040806, 01040808 AND 01040810. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-04-20 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-04-20 |
Time |
11:45 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|