Plan Review Details - Permit 01040741
Plan Review Stops For Permit 01040741
Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-08-27 Cont ID  
Sent By pkrauss Date 2001-08-27 Time 07:06 Rev Time 0.30
Received By pkrauss Date 2001-08-27 Time 07:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-05-04 Cont ID  
Sent By ndenmark Date 2001-05-04 Time 10:33 Rev Time 0.33
Received By ndenmark Date 2001-05-04 Time 10:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-04-25 Cont ID  
Sent By pkrauss Date 2001-04-25 Time 11:04 Rev Time 0.30
Received By pkrauss Date 2001-04-25 Time 11:04 Sent To  
Notes
2001-04-25 00:00:00******************DENIED****************
  
 EQUIPMENT SCHEDULED FOR AHU-1 INDICATES
 1,000 CFM, THE PLAN SHOWS ONLY 650 CFM
 BEING DISTRIBUTED, PLEASE CORRECT.
  
 EQUIPMENT SCHEDULED FOR AHU-3 IS 1,600
 CFM AND PLANS REFLECT ONLY 975 CFM
 BEING DISTRIBUTED.
  
 NO EXHAUST FANS ARE INDICATED ON PLANS,
 AS PER 1997 SMC 503.3.1, AIR EXHAUSTED
 FROM BATH, TOILET, COAT ROOM OR SIMILAR
 ROOMS SHALL NOT BE RECIRCULATED, IT
 SHALL BE MECHANICALLY EXHAUSTED TO
 OUTDOORS OR SHALL HAVE WINDOWS WITH NO
 LESS THAN 3 SQ. FT. OF OPEN SPACE.
  
 ALSO PLANS INDICATE A FIREPLACE, IF A
 PRE-FAB FIREPLACE IS BEING INSTALLED,
 PLEASE PROVIDE MANUFACTURE DETAILS (UL
 LISTING) AND FLUE INFORMATION/DETAILS.
  
 PLAN REVIEW BY PATTY KRAUSS
 (561) 659-8096 EXT 8388.