Plan Review Details - Permit 01040717
Plan Review Stops For Permit 01040717
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-04-25 Cont ID  
Sent By hpiskura Date 2001-04-25 Time 11:16 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-04-25 00:00:00TEST AND OR PRODUCT ACCEPTANCE REPORTS
 FOR THE DOORS WINDOWS AND ROOF COVERING
 WILL BE REQUIRED WITH THE PERMIT.
  
 IF FIRE RATED PARTITIONS ARE INSTALLED A
 FIRE DESIGN NUMBER WILL BE NECESARY.
 SEE SBC 701.5
  
 SECTION 6 A/5.0 TERMS SUCH AS "ANCHORED
 WITH APPROVED FASTENERS" ARE NOT AN
 ACCEPTABLE SUBSTITUTE FOR SPECIFIC
 DESIGN INFORMATION.SEE SBC 104.2.
  
 SECTION 1/S1SPECIFY ANCHOR BOLT LENGTH
 AND WELD SIZE.
  
 SHEET S 2.0SBC 1997 INVOKES ASCE 7-95
 NOT 7-93.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-26 Cont ID  
Sent By dpalmer Date 2001-04-26 Time 21:27 Rev Time 0.00
Received By dpalmer Date 2001-04-26 Time 21:27 Sent To  
Notes
2001-04-26 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE SIGNED AND SEALED BY THE
 ARCHS/ENGINEER OF RECORD PER 417.025
 AND 481.221
 F.A.C.
  
 2)NOTE: PLEASE NOTE THAT COLD WATER
 PIPE ISMISSING FROM GROUNDING
 ELECTRODE SYSTEM PER 250-50.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 AIC RATING IS GIVEN FOR PANEL BUT NOT
 FOR MAIN. IS MAIN FUSED OR BRKR?
  
 4)NOTE: PLEASE SEE ELECTRICAL PLAN
 SUBMITTED FOR SITE LIGHTING.E-5
 PLANS SHOW ALL OUTSIDE EQUIPMENT AS
 NEMA-1(INDOOR). ALL EQUIPMENT NEEDS TO
 BE RATED FOR LOCATION OF ENVIROMENT.
 TYPE-O?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-04-27 Cont ID  
Sent By mamini Date 2001-04-27 Time 14:00 Rev Time 4.00
Received By mamini Date 2001-04-27 Time 13:15 Sent To  
Notes
2001-04-27 00:00:00FAILED:
 1. PLEASE PROVIDE STORM WATER
 CALCULATION FOR OUR REVIEW IF YOU HAVE
 NOT SUBMITTED TO JOSE DEL RIO, STORM
 WATER ENGINEER AT 1000 45TH STREET WEST
 PALM BEACH,FL 33407.
 2. PERVIOUS & IMPERVIOUS CALCULATION
 MUST BE SHOWN ON CIVIL PLAN, PLEASE
 STATE EITHER ADDRESS OR PROPERTY CONTROL
 NUMBER.
 3. PLEASE PROVIDE POLLUTION PREVENTION
 PLAN.THE POLLUTION PREVENTION PLAN
 MUST BE INSTALLED IN THE FIELD PRIOR TO
 ANY EARTHWORK.
 4. AN APPROVED BACKFLOW PREVENTER
 ASSEMBLY WILL NEED TO BE INSTALLED, IF
 NOT ALREADY IN PLACE AT THE POINT OF
 SERVICE ON PROPERTY.ALL BACKFLOW
 PREVENTERS SHALL BE COMPLETLY HIDDEN
 FROM VIEW WITH SHRUBS PRIOR TO
 ACTIVATION.
 5. A CLEAN-OUT WILL NEED TO BE INSTALLED
 IN THE SANITARY LATERAL, ON THE PROPERTY
 , AT THE BACK OF THE SIDEWALK, IF NOT
 ALREADY INSTALLED.
 6. ALL DRIVEWAY APPROACHES MUST BE (AT A
 MIN.) PER CITY STANDARD.SEE ATTACHED
 7. ALL GRADES FOR CITY SIDEWALKS MUST BE
 SET BY THE CITY SURVEY CREW, CALL 659-
 8040.
 8. DETAILS FOR EXFILTRATION TRENCH,
 SHOWS 2 IN. TYPE II ASPHALT, SECTION B-B
 SHOWS 1 1/2 IN. TYPE II, PLEASE VERIFY.
 8. PLEASE SPECIFY THICKNESS FOR
 SIDEWALKS.
 9. PLEASE REFER TO APPROPRIATE SHEET FOR
 HANDICAP PARKING SIGN DETAILS AND
 INSTALLATION.
 IF ANY QUESTION PLEASE CONTACT 561-659-
 8096 EXT. 8492.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-20 Cont ID  
Sent By mcarsill Date 2001-04-20 Time 12:52 Rev Time 0.00
Received By mcarsill Date 2001-04-20 Time 12:51 Sent To  
Notes
2001-04-20 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS.
 2) WRONG TRAVEL DISTANCE NOTED ON PLANS.
 MAXIMUM TRAVEL DISTANCE ALLOWED BY THE
 CURRENT FIRE CODE IS 150 FEET MAXIMUM.
 3) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 4) PLANS NOT SIGNED AND SEALED.
 5) PLEASE EXPLAIN USE OF CLASSROOMS,
 HOURS OF OPERATION, AND AGE OF CHILDREN.
 6) THIS PROPERTY MAY BE LOCATED IN THE
 CITY FIRE LIMITS. IF THE BUILDING IS
 LOCATED IN THE FIRE LIMITS CERTAIN
 RESTRICTIONS MAY APPLY TO IT.
 7) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED FOR WALLS AND
 CEILING.
 8) PLEASE PROVIDE OCCUPANT LOAD
 CALCULATIONS FOR THE BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-05-08 Cont ID  
Sent By pkrauss Date 2001-05-08 Time 11:45 Rev Time 0.45
Received By pkrauss Date 2001-05-08 Time 11:26 Sent To  
Notes
2001-05-08 00:00:00********************DENIED**************
  
 FIRE DAMPERS ARE REQUIRED WHEN DUCTS
 PENETRATE RATED WALLS AS PER 1997 SMC
 610.1.1.PLEASE INDICATE FIRE DAMPERS
 AND ACCESS FOR MAINTENANCE/RESETTING ON
 PLANS.
  
 MECHANICAL DRAWINGS SHALL BE SIGNED AND
 SEALED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-08 Cont ID  
Sent By pschmitz Date 2001-05-08 Time 07:01 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-08 00:00:00PLUMBING PLAN REVIEWDENIED
 REFERENCE CODES,STD PLBG 94,FACBC 97
 (1) SHT A2.1 FACBC SEC4.1.6 ACCESSIBLE
 BUILDINGS, SHOW H/C ACCESSIBLE ROUTE,
 TURNING RADIUS IN EACH REST RM,DRINKING
 FOUNTAIN REQ,W/CLEAR FLR SPACE,FOR EA
 FIXTURE.
 (2) SHT MP.2 SHOW LOCATION OF BACK FLOW
 PREVENTER ON WATER SERVICE,LOCAL ORD
 #2938-96.
 AIR CHAMBERS TO COMPLY WITH SEC 607.8.3
 ACCESSIBLE,RECHARGEABLE
 END OF COMMENTSP[AUL SCHMITZ
 QUESTIONS561-659-8096 X 8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-05-08 Cont ID  
Sent By pkrauss Date 2001-05-08 Time 12:05 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved