Plan Review Stops For Permit 01040625 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2001-06-26 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-06-26 |
Time |
15:56 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2001-06-26 |
Time |
15:56 |
Sent To |
|
|
Notes |
2001-06-26 00:00:00 | APPROVED PER LUIS MARTINEZ 6/26/01. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-04-27 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-04-27 |
Time |
13:55 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2001-04-27 |
Time |
11:18 |
Sent To |
|
|
Notes |
2001-04-27 00:00:00 | THE NEW VESTIBULE IN AREA C "QA RECORDS" | | CREATES A DEAD END CORRIDOR >20'SEE | | SBC 1005.2. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-04-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-04-26 |
Time |
20:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-04-26 |
Time |
20:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2001-08-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-08-07 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2001-06-07 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-06-07 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-06-07 |
Time |
15:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-05-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-05-09 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-05-09 |
Time |
12:40 |
Sent To |
|
|
Notes |
2001-05-09 00:00:00 | RECEIVED LETTER REGARDING FIRE HYDRANT | | INSTALLATION. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-04-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-04-19 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-04-19 |
Time |
09:54 |
Sent To |
|
|
Notes |
2001-04-19 00:00:00 | 1) THE NEW VESTIBULE SHOWN ON PAGE | | A-3 CREATES A DEAD-END CORRIDOR OF AT | | LEAST 34 FEET LONG. | | 2) NO ILLUMINATED EXIT SIGN SHOWN ON | | PAGE A-1 QA RECORDS HALLWAY. IS THIS | | A DESIGNATED EXIT. | | 3) IS THE BUILDING FIRE SPRINKLER | | PROTECTED. IF IT IS SOME ADJUSTMENTS | | WILL BE NEEDED TO ALTER SYSTEM TO | | NEW BUILDING MODIFICATIONS. | | 4) THE SMOKE DETECTOR LOCATED IN THE | | EXISTING VESTIBULE APPEARS TO BE TOO | | CLOSE TO AIR CONDITIONING DIFFUSERS. | | CODE REQUIRES A MINIMUM OF THREE FEET | | FROM SMOKE DETECTORS TO AIR CONDITIONING | | DIFFUSERS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-08-22 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-22 |
Time |
12:26 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2001-08-22 |
Time |
11:59 |
Sent To |
|
|
Notes |
2001-08-22 00:00:00 | ******************PROVISO*************** | | | | | | PRIOR TO CONNECTING TO ANY EXISTING DUCT | | WORK CALL FOR AN INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-06-09 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-06-09 |
Time |
11:18 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-06-09 |
Time |
11:02 |
Sent To |
|
|
Notes |
2001-06-09 00:00:00 | ******************PROVISO*************** | | | | | | DRYER EXHAUST SHALL COMPLY WITH 1997 | | SMC509.3, BE CONSTRUCTED OF MIN. | | 0.0157"GALVANIZD STEEL OF OTHER | | NONCOMBUSTIBLE MATERIAL OF EQUAL | | STRENGTH & CORROSION | | RESISTANCE.MAXIMUM LENGTH SHALL NOT | | EXCEED 25' FROM DRYER (DEDUCT 2 1/2' | | PER 45 DEGREE OFFSET AND 5' PER 90 | | DEGREE BEND. | | | | NO COMBUSTIBLES ABOVE CEILING IN RETURN | | AIR PLENUM. | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS | | PER 406.1.WITH NOTIFICATION TO | | ALARM/STROBE IN NORMALLY OCCUPIED AREAS | | AS PER NFPA 4-4.4.3. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2001-04-27 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-04-27 |
Time |
07:05 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-04-27 |
Time |
07:02 |
Sent To |
|
|
Notes |
2001-04-27 00:00:00 | *******************DENIED*************** | | | | MECHANICAL PERMIT REQUIRED PRIOR TO ANY | | WORK BEING DONE. | | | | PLEASE SUBMIT INFORMATION ON RTU-8, | | TONNAGE AND ANY OTHER EXISTING DROPS. | | INDICATE CFM'S BEING DISTRIBUTED. | | | | PRIOR TO CONNECTING TO ANY EXISTING | | DUCTWORK CALL FOR AN INSPECTION. | | | | PLEASE PROVIDE DETAIL ON DRYER BEING | | RELOCATED, SPECIFICALLY THE DRYER VENT | | LOCATION, SIZE AND TERMINATION. | | | | DRAWING A-3 SUPPLY DROP SHALL NOT BE | | LOCATED CLOSER THAN 3 FT TO THE SMOKE | | DETECTOR.(NFPA 72 2-5.2.1.7) |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2001-10-05 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-10-05 |
Time |
08:23 |
Rev Time |
1.50 |
Received By |
kstevens |
Date |
2001-10-05 |
Time |
07:59 |
Sent To |
|
|
Notes |
2001-10-05 00:00:00 | DENIED | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | 1) PLEASE GIVE OCCUPANT LOAD FOR EACH | | AREA. GIVE CALCULATIONS FOR MINIMUM FAC- | | ILITIES PER SPC TABLE 407. PAGE A-15 | | 2) PAGE A-15 GAS ISOMETRIC. VALVE RE- | | QUIRED BEFORE REGULATORS. PLEASE SHOW ON | | PLAN REVISION. | | 3) PAGE A-15 GAS ISOMETRIC. PLEASE PRO- | | VIDE MANUFACTURE INFO ON GAS W/HEATERS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2001-08-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-08-07 |
Time |
13:10 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-08-07 |
Time |
13:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2001-06-26 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-06-10 |
Time |
12:06 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-06-10 00:00:00 | PLUMBING PLAN REVIEWDENIED | | (1) CONTACTED MR CHIP GRONAUER,RE:LETTER | | FROM MR RICHARD WENSING,DATED MAY 21,01 | | CARP PHASE IV, SHOWERS IN DETOXIC AREA | | MEN'S & WOMENS,TO COMPLY W/FACBC 4.1.3. | | (11) , ALSO DRWGS ON DWV,WATER SUPPLY. | | END OF COMMENTSPAUL SCHMITZ | | QUESTOONS561-659-8096X8233 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-05-07 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-05-07 |
Time |
17:57 |
Rev Time |
1.50 |
Received By |
pschmitz |
Date |
2001-05-07 |
Time |
17:57 |
Sent To |
|
|
Notes |
2001-05-07 00:00:00 | DENIED; | | | | 1.FLOOR DRAINS WITH TRAP PRIMERS | | REQUIRED IN WOMAN'S AND MEN'S DETOX | | BATHROOMS 94 SPC 409.4.1.1. | | | | 2.SHOW SIZE AND TURNING RATIUS OF DETOX | | BATHROOMS, ALSO LOCATION OF GRAB BARS. | | | | 3.SHOWER STALLS SHALL COMPLY WITH FACBC | | 4.21.2 THRU 4.21.8. SHOW SIZE. | | | | 4.DRINKING FOUNTAINS SHALL COMPLY WITH | | FACBC 4.1.3 (10). | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8369 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2001-08-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-08-07 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|