Plan Review Details - Permit 01040625
Plan Review Stops For Permit 01040625
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-06-26 Cont ID  
Sent By pkrauss Date 2001-06-26 Time 15:56 Rev Time 0.00
Received By pkrauss Date 2001-06-26 Time 15:56 Sent To  
Notes
2001-06-26 00:00:00APPROVED PER LUIS MARTINEZ 6/26/01.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-27 Cont ID  
Sent By hpiskura Date 2001-04-27 Time 13:55 Rev Time 0.00
Received By hpiskura Date 2001-04-27 Time 11:18 Sent To  
Notes
2001-04-27 00:00:00THE NEW VESTIBULE IN AREA C "QA RECORDS"
 CREATES A DEAD END CORRIDOR >20'SEE
 SBC 1005.2.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-04-26 Cont ID  
Sent By dpalmer Date 2001-04-26 Time 20:15 Rev Time 0.00
Received By dpalmer Date 2001-04-26 Time 20:15 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-07 Cont ID  
Sent By kstevens Date 2001-08-07 Time 13:09 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-06-07 Cont ID  
Sent By mcarsill Date 2001-06-07 Time 15:02 Rev Time 0.00
Received By mcarsill Date 2001-06-07 Time 15:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-05-09 Cont ID  
Sent By mcarsill Date 2001-05-09 Time 12:40 Rev Time 0.00
Received By mcarsill Date 2001-05-09 Time 12:40 Sent To  
Notes
2001-05-09 00:00:00RECEIVED LETTER REGARDING FIRE HYDRANT
 INSTALLATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-19 Cont ID  
Sent By mcarsill Date 2001-04-19 Time 09:54 Rev Time 0.00
Received By mcarsill Date 2001-04-19 Time 09:54 Sent To  
Notes
2001-04-19 00:00:001) THE NEW VESTIBULE SHOWN ON PAGE
 A-3 CREATES A DEAD-END CORRIDOR OF AT
 LEAST 34 FEET LONG.
 2) NO ILLUMINATED EXIT SIGN SHOWN ON
 PAGE A-1 QA RECORDS HALLWAY. IS THIS
 A DESIGNATED EXIT.
 3) IS THE BUILDING FIRE SPRINKLER
 PROTECTED. IF IT IS SOME ADJUSTMENTS
 WILL BE NEEDED TO ALTER SYSTEM TO
 NEW BUILDING MODIFICATIONS.
 4) THE SMOKE DETECTOR LOCATED IN THE
 EXISTING VESTIBULE APPEARS TO BE TOO
 CLOSE TO AIR CONDITIONING DIFFUSERS.
 CODE REQUIRES A MINIMUM OF THREE FEET
 FROM SMOKE DETECTORS TO AIR CONDITIONING
 DIFFUSERS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-08-22 Cont ID  
Sent By pkrauss Date 2001-08-22 Time 12:26 Rev Time 0.40
Received By pkrauss Date 2001-08-22 Time 11:59 Sent To  
Notes
2001-08-22 00:00:00******************PROVISO***************
  
  
 PRIOR TO CONNECTING TO ANY EXISTING DUCT
 WORK CALL FOR AN INSPECTION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-09 Cont ID  
Sent By pkrauss Date 2001-06-09 Time 11:18 Rev Time 0.45
Received By pkrauss Date 2001-06-09 Time 11:02 Sent To  
Notes
2001-06-09 00:00:00******************PROVISO***************
  
  
 DRYER EXHAUST SHALL COMPLY WITH 1997
 SMC509.3, BE CONSTRUCTED OF MIN.
 0.0157"GALVANIZD STEEL OF OTHER
 NONCOMBUSTIBLE MATERIAL OF EQUAL
 STRENGTH & CORROSION
 RESISTANCE.MAXIMUM LENGTH SHALL NOT
 EXCEED 25' FROM DRYER (DEDUCT 2 1/2'
 PER 45 DEGREE OFFSET AND 5' PER 90
 DEGREE BEND.
  
 NO COMBUSTIBLES ABOVE CEILING IN RETURN
 AIR PLENUM.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS
 PER 406.1.WITH NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS
 AS PER NFPA 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-04-27 Cont ID  
Sent By pkrauss Date 2001-04-27 Time 07:05 Rev Time 0.45
Received By pkrauss Date 2001-04-27 Time 07:02 Sent To  
Notes
2001-04-27 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT REQUIRED PRIOR TO ANY
 WORK BEING DONE.
  
 PLEASE SUBMIT INFORMATION ON RTU-8,
 TONNAGE AND ANY OTHER EXISTING DROPS.
 INDICATE CFM'S BEING DISTRIBUTED.
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK CALL FOR AN INSPECTION.
  
 PLEASE PROVIDE DETAIL ON DRYER BEING
 RELOCATED, SPECIFICALLY THE DRYER VENT
 LOCATION, SIZE AND TERMINATION.
  
 DRAWING A-3 SUPPLY DROP SHALL NOT BE
 LOCATED CLOSER THAN 3 FT TO THE SMOKE
 DETECTOR.(NFPA 72 2-5.2.1.7)

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-10-05 Cont ID  
Sent By kstevens Date 2001-10-05 Time 08:23 Rev Time 1.50
Received By kstevens Date 2001-10-05 Time 07:59 Sent To  
Notes
2001-10-05 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) PLEASE GIVE OCCUPANT LOAD FOR EACH
 AREA. GIVE CALCULATIONS FOR MINIMUM FAC-
 ILITIES PER SPC TABLE 407. PAGE A-15
 2) PAGE A-15 GAS ISOMETRIC. VALVE RE-
 QUIRED BEFORE REGULATORS. PLEASE SHOW ON
 PLAN REVISION.
 3) PAGE A-15 GAS ISOMETRIC. PLEASE PRO-
 VIDE MANUFACTURE INFO ON GAS W/HEATERS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-08-07 Cont ID  
Sent By kstevens Date 2001-08-07 Time 13:10 Rev Time 0.50
Received By kstevens Date 2001-08-07 Time 13:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-06-26 Cont ID  
Sent By pschmitz Date 2001-06-10 Time 12:06 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-10 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) CONTACTED MR CHIP GRONAUER,RE:LETTER
 FROM MR RICHARD WENSING,DATED MAY 21,01
 CARP PHASE IV, SHOWERS IN DETOXIC AREA
 MEN'S & WOMENS,TO COMPLY W/FACBC 4.1.3.
 (11) , ALSO DRWGS ON DWV,WATER SUPPLY.
 END OF COMMENTSPAUL SCHMITZ
 QUESTOONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-07 Cont ID  
Sent By jleech Date 2001-05-07 Time 17:57 Rev Time 1.50
Received By pschmitz Date 2001-05-07 Time 17:57 Sent To  
Notes
2001-05-07 00:00:00DENIED;
  
 1.FLOOR DRAINS WITH TRAP PRIMERS
 REQUIRED IN WOMAN'S AND MEN'S DETOX
 BATHROOMS 94 SPC 409.4.1.1.
  
 2.SHOW SIZE AND TURNING RATIUS OF DETOX
 BATHROOMS, ALSO LOCATION OF GRAB BARS.
  
 3.SHOWER STALLS SHALL COMPLY WITH FACBC
 4.21.2 THRU 4.21.8. SHOW SIZE.
  
 4.DRINKING FOUNTAINS SHALL COMPLY WITH
 FACBC 4.1.3 (10).
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-07 Cont ID  
Sent By kstevens Date 2001-08-07 Time 13:10 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***