Plan Review Details - Permit 01040612
Plan Review Stops For Permit 01040612
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-30 Cont ID  
Sent By jwitmer Date 2001-04-30 Time 19:48 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-30 00:00:00PROVISO, SBC 303.1/ TABLE 704.1
  
 ADMINISTRATIVE 106.4.2/106.4.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-19 Cont ID  
Sent By jwitmer Date 2001-04-19 Time 08:09 Rev Time 6.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-19 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01040612
 1100 TECHNOLOGY PLACE SUITE 120
 HEDRICK BROTHERS
 689-8880
  
 1)- A COPY OF THE CODE COMMENTARY THAT
 PERTAINS TO CALCULATING AREA FOR A
 MEZZANINE IS ENCLOSED FOR REFRENCE, SEE
 AREA FOR OPEN AREA & AREA THAT IS
 ENCLOSED UNDER THE MEZZANINE.
 SBC 503.2.3.2. THE TOTAL SQ. FT. OF THE
 INTERIOR 24'-6" X 81'-9"= 2002.875 SQ FT
 CALC AREA MEZZANINE:
 29'-8"X24'-6"=726'
 12'-0"X16'-0"=192'
 TOTAL SQ FT918 SQ FT
  
 ALLOWABLE IF OPEN BELOW:
 2002.875'X .33%= 660.948 SQ FT
  
 ALLOWABLE AREA ENCLOSED:
 40'-6"X24'-6"=992.25X.33%=327.44 SQ FT
  
 2)- DISCREPANCIES:
 A)- SHEET A-1 MEZZANINE DETAIL: DEPICTS
 A DOOR ON THE MEZZANINE LEVEL SWING
 ING FROM AREA BELOW?
 B)- SHEET A-1 DEPICT 1ST FLOOR UNDER
 THE PROPOSED MEZZANINE AS FILE
 STORAGE WHERE AS S-3 FLOOR LOADS
 INDICATES THE UAS AS A OFFICE.
 C)- S-3 FLOOR LOADS ALSO INDICATES A
 CATWALK?
 D)- S-3 ALSO INDICATES THE MECH. ROOM
 AS 125 LBS. FLOOR LOAD BUT NOT THE
 MEZZANINE FLOOR.
  
 3)- THE TYPE OF STORAGE FOR THE PROPOSED
 MEZZANINE NEEDS TO BE DETERMINED:
 STORAGE SBC TABLE 204.1
 MODERATE HAZARD S1- 3 HR
 LOW HAZARDS2- 2 HR
 DEPENDING ON THE TYPE OF MATERIALS TO BE
 CLASSIFIED (S1/S2), WE MAY NEED TO
 ADDRESS THE TENANT SEPERATION WALLS,
 WHAT MATERIALS ARE THEY MADE OF?
  
 4)- ADMINISTRATIVE CODE/ CITY AMENDMENTS
 106.4.2 IT SHALL BE THE RESPONSIBLITY OF
 THE OWNER,AGENT,PROPREITOR OR OCCUPANT
 OF GROUP S & GROUP F OCCUPANCIES,OR ANY
 OCCUPANCY WHERE EXCESSIVE FLOOR LOADING
 IS LIKELY TO OCCUR, TO EMPLOY A COMPE-
 TANT ARCHITECT OR ENGINEER IN COMPUTING
 THE SAFE LOAD CAPACITY. ALL SUCH COMPU-
 TATIONS SHALL BE ACCOMPANIED BY AN AFFI-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE FLOOR LOAD ON EACH
 FLOOR IN POUNDS PER SQUARE FOOT UNIFORM-
 LY DISTRIBUTED. THE COMPUTATIONS AND AFF
 IDAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BUILDING DEPARTMENT.
  
 5)- ADMINISTRATIVE CODE/ CITY AMENDMENTS
 106.4.3. IN EVERY BUILDING OR PART OF
 BUILDING USED FOR STORAGE, THE SAFE
 FLOOR LOADS, AS REVIEWED BY THE BUILDING
 OFFICIAL ON THTE PLAN, SHALL BE MARKED
 ON PLATES OF APPROVED DESIGN WHICH SHALL
 BE SUPPLIED AND SECURELY AFFIXED BY THE
 OWNER OF THE BUILDING IN A CONSPICUOUS
 PLACE IN EACH STORY, TO WHICH THEY RE-
 LATE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-05-30 Cont ID  
Sent By jleahy Date 2001-05-30 Time 09:12 Rev Time 0.30
Received By jleahy Date 2001-05-30 Time 09:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-05-01 Cont ID  
Sent By jwitmer Date 2001-05-01 Time 12:15 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-05-01 00:00:00PER DEWEY V PALMER SIGNNED APPLICATION

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-17 Cont ID  
Sent By dpalmer Date 2001-04-17 Time 20:56 Rev Time 0.00
Received By dpalmer Date 2001-04-17 Time 20:56 Sent To  
Notes
2001-04-17 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 I DID SEE THE NOTE DRAWN ON THE PLANS.
 HOWEVER, TRANSFORMERS ARE BEING CHANGED
 OUT EVERYDAY BY FPL AND WHAT EQUIPMNET
 WAS RATED FOR BEFORE MAY BE DIFFERENT AT
 THE PRESENT TIME. PLEASE SUBMIT AIC
 RATINGS FOR ALL NEW EQUIPMNET AND MAINS
 ETC.
 PLEASE SUBMIT THE ABOVE INFORMATION. IF
 THERE ARE ANY QUESTIONS OR IF CLARIFICAT
 ION IS NEEDED, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-17 Cont ID  
Sent By mcarsill Date 2001-04-17 Time 08:06 Rev Time 0.00
Received By mcarsill Date 2001-04-17 Time 08:06 Sent To  
Notes
2001-04-17 00:00:00ON APRIL 16, 2001, WRITER SPOKE TO
 DALE HEDRICK AND STEVEN ROY OF HEDRICK
 BROTHERS CONSTRUCTION BY TELEPHONE.
 ACCORDING TO DALE HEDRICK, ONLY ONE
 TENANT SPACE AT 1100 TECHNOLOGY PLACE
 IS FIRE SPRINKLER PROTECTED WHICH HAS
 BE IDENTIFIED AS A DRY CLEANERS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-16 Cont ID  
Sent By mcarsill Date 2001-04-16 Time 13:52 Rev Time 0.00
Received By mcarsill Date 2001-04-16 Time 13:52 Sent To  
Notes
2001-04-16 00:00:00ACCORDING TO FIRE RESCUE RECORDS, THE
 BUILDING LOCATED AT 1100 TECHNOLOGY
 PLACE IS FIRE SPRINKLER PROTECTED. NO
 FIRE SPRINKLER DRAWINGS INCLUDED WITH
 PLANS. PLEASE CLARIFY WITH THIS OFFICE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-04-30 Cont ID  
Sent By jwitmer Date 2001-04-30 Time 19:31 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-04-28 Cont ID  
Sent By kstevens Date 2001-04-28 Time 14:49 Rev Time 0.33
Received By kstevens Date 2001-04-28 Time 14:49 Sent To  
Notes
***NONE***