2001-04-19 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 01040612 |
| 1100 TECHNOLOGY PLACE SUITE 120 |
| HEDRICK BROTHERS |
| 689-8880 |
| |
| 1)- A COPY OF THE CODE COMMENTARY THAT |
| PERTAINS TO CALCULATING AREA FOR A |
| MEZZANINE IS ENCLOSED FOR REFRENCE, SEE |
| AREA FOR OPEN AREA & AREA THAT IS |
| ENCLOSED UNDER THE MEZZANINE. |
| SBC 503.2.3.2. THE TOTAL SQ. FT. OF THE |
| INTERIOR 24'-6" X 81'-9"= 2002.875 SQ FT |
| CALC AREA MEZZANINE: |
| 29'-8"X24'-6"=726' |
| 12'-0"X16'-0"=192' |
| TOTAL SQ FT918 SQ FT |
| |
| ALLOWABLE IF OPEN BELOW: |
| 2002.875'X .33%= 660.948 SQ FT |
| |
| ALLOWABLE AREA ENCLOSED: |
| 40'-6"X24'-6"=992.25X.33%=327.44 SQ FT |
| |
| 2)- DISCREPANCIES: |
| A)- SHEET A-1 MEZZANINE DETAIL: DEPICTS |
| A DOOR ON THE MEZZANINE LEVEL SWING |
| ING FROM AREA BELOW? |
| B)- SHEET A-1 DEPICT 1ST FLOOR UNDER |
| THE PROPOSED MEZZANINE AS FILE |
| STORAGE WHERE AS S-3 FLOOR LOADS |
| INDICATES THE UAS AS A OFFICE. |
| C)- S-3 FLOOR LOADS ALSO INDICATES A |
| CATWALK? |
| D)- S-3 ALSO INDICATES THE MECH. ROOM |
| AS 125 LBS. FLOOR LOAD BUT NOT THE |
| MEZZANINE FLOOR. |
| |
| 3)- THE TYPE OF STORAGE FOR THE PROPOSED |
| MEZZANINE NEEDS TO BE DETERMINED: |
| STORAGE SBC TABLE 204.1 |
| MODERATE HAZARD S1- 3 HR |
| LOW HAZARDS2- 2 HR |
| DEPENDING ON THE TYPE OF MATERIALS TO BE |
| CLASSIFIED (S1/S2), WE MAY NEED TO |
| ADDRESS THE TENANT SEPERATION WALLS, |
| WHAT MATERIALS ARE THEY MADE OF? |
| |
| 4)- ADMINISTRATIVE CODE/ CITY AMENDMENTS |
| 106.4.2 IT SHALL BE THE RESPONSIBLITY OF |
| THE OWNER,AGENT,PROPREITOR OR OCCUPANT |
| OF GROUP S & GROUP F OCCUPANCIES,OR ANY |
| OCCUPANCY WHERE EXCESSIVE FLOOR LOADING |
| IS LIKELY TO OCCUR, TO EMPLOY A COMPE- |
| TANT ARCHITECT OR ENGINEER IN COMPUTING |
| THE SAFE LOAD CAPACITY. ALL SUCH COMPU- |
| TATIONS SHALL BE ACCOMPANIED BY AN AFFI- |
| DAVIT FROM THE ARCHITECT OR ENGINEER |
| STATING THE SAFE FLOOR LOAD ON EACH |
| FLOOR IN POUNDS PER SQUARE FOOT UNIFORM- |
| LY DISTRIBUTED. THE COMPUTATIONS AND AFF |
| IDAVIT SHALL BE FILED AS A PERMANENT |
| RECORD OF THE BUILDING DEPARTMENT. |
| |
| 5)- ADMINISTRATIVE CODE/ CITY AMENDMENTS |
| 106.4.3. IN EVERY BUILDING OR PART OF |
| BUILDING USED FOR STORAGE, THE SAFE |
| FLOOR LOADS, AS REVIEWED BY THE BUILDING |
| OFFICIAL ON THTE PLAN, SHALL BE MARKED |
| ON PLATES OF APPROVED DESIGN WHICH SHALL |
| BE SUPPLIED AND SECURELY AFFIXED BY THE |
| OWNER OF THE BUILDING IN A CONSPICUOUS |
| PLACE IN EACH STORY, TO WHICH THEY RE- |
| LATE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561) 659-8096 EX 8412 |