2001-05-15 00:00:00 | ******************* UNSAT ************* |
| |
| 1)NOTE: PLEASE NOTE THAT NO PANEL SCHED- |
| -ULES OR LOAD CALCULATIONS WERE SUBMITT- |
| ED.?? 215-5 |
| - |
| 2)NOTE: PLEASE NOTE THAT NO BRANCH CIR- |
| -CUIT #` S ARE SHOWN ON PLANS.PLEASE |
| SHOW ALL BRANCH CIRCUIT #`S AND CORRE- |
| -LATE WITH PANEL SCHEDULE. |
| |
| 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 4) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD |
| S AT 125% (LIGHTING) ETC. |
| |
| 5)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| SHOWS AN EQUIPMENT GROUNDING CONDUCTOR |
| FROM FPL SERVICE AND FROM METERCAN TO |
| FIRST MEANS OF DISCONNECT. THIS WOULD |
| BE PARRALELLING THE NEUTRAL. AN EQUIP- |
| -MENT GROUND IS ONLY INSTALL AFTER THE |
| FIRST MEANS OF DISCONNECT. |
| |
| 6)NOTE: PLEASE CLARIFY GROUNDING ELEC- |
| -TRODE ATTACHMENT SHOWN ON RISER.? |
| COLD WATER? |
| |
| 7)NOTE: PLEASE NOTE THAT PLANS SHOW TWO |
| SWITCHES IN NEW GARAGE BUT NOT GOING |
| TO ANYTHING? PLEAS CLARIFY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMAITON FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW] |
| 561-659-8096 EXT 8372 |