Plan Review Details - Permit 01040584
Plan Review Stops For Permit 01040584
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-05-24 Cont ID  
Sent By hpiskura Date 2001-05-24 Time 10:58 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-05-24 00:00:00SBC 704.5.2 REQUIRES PARAPET WALLS FOR
 THIS CONSTRUCTION TYPE.
  
 CODE INFORMATION IS INCORRECT ON SHEET
 T1.REVISE TO SBC 1997 TERMS.
  
 WHAT WILL THIS BUILDING BE USED FOR?
 SEE SBC 104.1.5.
  
 WILL THE TYPE C2 COLUMN BE ADDED TO THE
 EXISTING WALLS?
  
 AREA SHOWN AS NEW GARAGE MUST COMPLY
 WITH SBC 411.2, AND SBC 411.4 OR 411.5
 AS IS APPLICABLE.
  
 SBC 1997 INVOKES ASCE 7-95 NOT ASCE
 7-93.REVISE AS NECESSARY.
  
 SHOW THE 2 HR FIRE RATED DESIGN NUMBER
 AND THE OPENING PROTECTIVES FOR THE
 EXTERIOR WALLS AS REQUIRED BY SBC TABLE
 600 AND SBC 701.5.1.
  
 SHOW HOW THE BUILDING WILL BE MADE
 HANDICAP ACCESIBLE FROM THE PUBLIC
 RIGHT OF WAY.SEE THE FACBC.
  
 THE 2'-6" FRENCH DOORS DO NOT MEET
 EGRESS WIDTH OR HANDICAP.SEE SBC
 1012.1 AND 4.13.1 (2) FACBC
  
 THE $15500.00 PERMIT VALUATION IS TOO
 LOW FOR THIS SCOPE OF WORK.PROVIDE
 ACOPY OF THE SIGNED CONTRACT AND A
 DETAILED TAKEOFF TO JUSTIFY THE
 VALUATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-05-15 Cont ID  
Sent By dpalmer Date 2001-05-15 Time 11:09 Rev Time 0.00
Received By dpalmer Date 2001-05-15 Time 11:09 Sent To  
Notes
2001-05-15 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT NO PANEL SCHED-
 -ULES OR LOAD CALCULATIONS WERE SUBMITT-
 ED.?? 215-5
 -
 2)NOTE: PLEASE NOTE THAT NO BRANCH CIR-
 -CUIT #` S ARE SHOWN ON PLANS.PLEASE
 SHOW ALL BRANCH CIRCUIT #`S AND CORRE-
 -LATE WITH PANEL SCHEDULE.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 S AT 125% (LIGHTING) ETC.
  
 5)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS AN EQUIPMENT GROUNDING CONDUCTOR
 FROM FPL SERVICE AND FROM METERCAN TO
 FIRST MEANS OF DISCONNECT. THIS WOULD
 BE PARRALELLING THE NEUTRAL. AN EQUIP-
 -MENT GROUND IS ONLY INSTALL AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 6)NOTE: PLEASE CLARIFY GROUNDING ELEC-
 -TRODE ATTACHMENT SHOWN ON RISER.?
 COLD WATER?
  
 7)NOTE: PLEASE NOTE THAT PLANS SHOW TWO
 SWITCHES IN NEW GARAGE BUT NOT GOING
 TO ANYTHING? PLEAS CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW]
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-05-15 Cont ID  
Sent By mcarsill Date 2001-05-15 Time 11:22 Rev Time 0.00
Received By mcarsill Date 2001-05-15 Time 11:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-11 Cont ID  
Sent By jleech Date 2001-05-11 Time 14:47 Rev Time 1.00
Received By jleech Date 2001-05-11 Time 14:47 Sent To  
Notes
2001-05-11 00:00:00DENIED;
  
 1.SHOW DIAMENTIONS FOR BATHROOM.
  
 2.BATHROOM FACILITYS TO COMPLY WITH
 TABLE 407, 94 STANDERD PLUMBING CODE.
 STATE OCCUPANT TYPE. USE 407.1.3 TO
 DETERMINE HABITABLE FLOOR SPACE.
  
 3.GRAB BARS REQUIRED IN HANDICAP
 BATHROOMS.
  
 4.SHOW SANITARY RISER DIAGRAM. SIZE
 PIPES AND SHOW TIE-IN.
  
 5.WATER SUPPLY ; BACKFLOW PREVENTOR
 REQUIRED. ARE THERE ANY HOSE BIBS?
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status P Date 2001-05-04 Cont ID  
Sent By sgraham Date 2001-04-13 Time 15:34 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-04-13 00:00:00SURVEY MUST MATCH PRESENT BLDG