Plan Review Details - Permit 01040473
Plan Review Stops For Permit 01040473 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2001-06-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-06-05 |
Time |
10:23 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-04-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-04-18 |
Time |
06:34 |
Rev Time |
6.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-04-18 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01040473 | | L DAVIS CONST | | 848-0577 | | | | 1)- THE SURVEY INDICATES THAT THE EAST | | SIDE OF THE BUILDING IS A PROPERTYLINE. | | SBC TABLE 600 0'- 3'-0" FROM THE PROPER- | | TY LINE DOESN'T ALLOW FOR OPENINGS IN | | THE WALL. | | | | 2)- THE EPS CORNICE AND TRIM DEPICTED ON | | SHEET A-4 IS REQUIERED TO MEET THE NON- | | COMBUSTIBLE REQUIREMENTS FOR ARCHITEC- | | TURAL TRIM FOR BUILDINGS LOCATED WITHIN | | A DESIGNATED FIRE DISTRICT. | | | | 3)- FLORIDA ACCESSIBILITY CODE 4.1.3 | | VERTICAL ACCESSIBILITY: | | 4.1.6 (ALTERATIONS) (A) NO ALTERATION | | SHALL BE UNDERTAKEN WHICH DECREASES OR | | HAS THE EFFECT OF DECREASING ACCESIBIL- | | ITY OR USABILITY OF A BUILDING OR | | FACILITY BELOW THE REQUIREMENTS FOR NEW | | CONSTRUCTION AT THE TIME OF ALTERATION. | | | | THE 4TH FLOOR NEEDS TO BE MADE ACCESS- | | IBLE FOR THE HANDICAPPED BY EITHER AN | | ELEVATOR OR APPROVED PLATFORM LIFT. | | SEE 4.10 / ELEVATORS, 4.11 PLATFORM LIFT | | OF FL ACCESSIBILITY CODE. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 EX 8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-04-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-04-17 |
Time |
21:57 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-04-17 |
Time |
21:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-06-01 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-06-01 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-06-01 |
Time |
10:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-04-11 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-04-11 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-04-11 |
Time |
11:35 |
Sent To |
|
|
Notes |
2001-04-11 00:00:00 | 1) FOURTH FLOOR STILL SHOWS ONLY | | ONE MEANS OF EGRESS FROM THAT LEVEL. | | PLEASE EXPLAIN THIS RATIONALE AND WHAT | | CODE SECTION ALLOWS THIS. WHAT OCCUPANCY | | TYPE IS ON THE FOURTH FLOOR. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-06-05 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-06-05 |
Time |
10:19 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-06-05 00:00:00 | PLUMBING PLAN REVIEWPROVISO | | (1) DRINKING FOUNTAIN REQ SPC 94 TAB 407 | | ALSO FACBC 97 SEC 4.1.3(10)(A), THIS IS | | TO BE INCLUDED AS PART OF IST ROUGH AND | | A REVISION BEFORE FINAL. | | END OF COMMENTSPAUL SCHMITZ | | QUESTIONS561-659-8096X8233 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-05-07 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-05-07 |
Time |
19:16 |
Rev Time |
1.00 |
Received By |
jleech |
Date |
2001-05-07 |
Time |
19:16 |
Sent To |
|
|
Notes |
2001-05-07 00:00:00 | DENIED; | | | | 1.DRINKING FOUNTAIN REQUIRED PER 94 SPC | | TABLE 407. | | | | 2.DRINKING FOUNTAIN SHALL COMPLY WITH | | FACBC 4.1.3 (10) AND 4.15. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT.8369 |
|
|
|