Plan Review Details - Permit 01040463
Plan Review Stops For Permit 01040463
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-02 Cont ID  
Sent By jwitmer Date 2001-07-02 Time 19:15 Rev Time 0.33
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-17 Cont ID  
Sent By jwitmer Date 2001-04-17 Time 10:25 Rev Time 4.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-17 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01040463
 515 N FLAGLER SUITE 101
 CONT: LEIGHTON MCGINN
 863-4455
  
 1)- FLORIDA ACCESSIBILITY CODE 4.1.3
 ACCESSIBILE BUILDINGS:
 4.1.3 (NEW) VERTICAL ACCESSIBILITY SHALL
 BE PROVIDED TO ALL LEVELS ABOVE & BELOW
 THE OCCUPIABLE GRADE LEVEL.
 4.1.5. (ADDITIONS) EACH SPACE OR ELEMENT
 ADDED TO THE EXISTING BUILDING OR FACIL-
 ITY SHALL COMPLY WITH THE PROVISIONS OF
 4.1.1 TO 4.1.3, MINIMUM REQUIREMENTS FOR
 NEW CONSTRUCTION.
 4.1.6 ( ALTERATIONS) (A) NO ALTERATION
 SHALL BE UNDERTAKEN WHICH DECREASES OR
 HAS THE EFFECT OF DECREASING ACCESSIBIL-
 ITY OR USABILITY OF A BUILDING OR FACIL-
 ITY BELOW THE REQUIREMENTS FOR NEW
 CONSTRUCTION AT THE TIME OF ALTERATION.
  
 VERTICAL ACCESSIBILITY TO THE MEZZANINE
 WILL BE REQUIRED. THE PROBLEM IS WHEN
 THE VERTICAL ACCESSIBILITY IS FIGURED
 THE LIFT OR ELEVATOR WILL CONNECT TO
 BOTH MEZZANINES MAKING (1) MEZZANINE
 WITH A SQUARE FOOT AREA OF 400 SQ. FT.
  
 2)- SBC 1007.8.2 WILL ONLY ALLOW SPIRAL
 STAIRS AS A MEANS OF EGRESS FOR A
 MEZZANINE WHEN NOT MORE THAN 250 SQ. FT.
  
 A SOLUTION:A SOLUTION TO THE VERTICAL
 ACCESSIBILITY IS TO APPLY FOR A VARIANCE
 TO THE STATE. IF THEY APPROVE THE VARI-
 ANCE THERE WILL REMAIN 2 INDEPENDENT
 SPIRAL STAIRS WHICH WILL NEED TO MEET
 CRITERIA OF 1007.8.2.
  
 3)- SBC 903.1 AUTOMATIC FIRE SPRINKLER
 SYSTEM, LAYOUT OF ALL SPRINKLER, DEVICES
 AND SYSTEM SHALL BE SUBMITTED TO THE
 BUILDING DEPARTMENT.
 4)- BUILDING DATA: NOT TYPE IV BUT
 TYPE I.
  
 5)- PLANS SHALL BE SUBMITTED TO P B CO.
 BUILDING DEPARTMENT FOR IMPACT FEES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-06-15 Cont ID  
Sent By dpalmer Date 2001-06-15 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2001-06-15 Time 15:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-17 Cont ID  
Sent By dpalmer Date 2001-04-17 Time 22:13 Rev Time 0.00
Received By dpalmer Date 2001-04-17 Time 22:13 Sent To  
Notes
2001-04-17 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY GROUNDING OF
 TRANSFORMER. PER 250,450-5
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 AND SHOW COMPLETED KVA LOADS PER 215-5
 ANDART:220 AND SHOW ALL CONTINUOUS
 LOADS AT125% PER 215-2-3,220-4
  
 3)NOTE: PLEASE LABEL TRANSFORMER IN
 ELECROOM, SO THAT ALL REQ`MENTS OF
 240-21 ARE MET.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-06-20 Cont ID  
Sent By lsmith Date 2001-06-20 Time 16:19 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-20 Cont ID  
Sent By mcarsill Date 2001-06-20 Time 14:08 Rev Time 0.00
Received By mcarsill Date 2001-06-20 Time 14:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-12 Cont ID  
Sent By mcarsill Date 2001-04-12 Time 11:08 Rev Time 0.00
Received By mcarsill Date 2001-04-12 Time 11:08 Sent To  
Notes
2001-04-12 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) WHAT WILL THE SPIRAL STAIRS BE USED
 FOR.
 3) WHAT WILL THE TENANT SPACE BE USED
 FOR.
 4) NO FIRE ALARM EQUIPMENT SHOWN ON
 THE FIRST FLOOR.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-03 Cont ID  
Sent By pkrauss Date 2001-07-03 Time 07:46 Rev Time 0.30
Received By pkrauss Date 2001-07-03 Time 07:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-04-24 Cont ID  
Sent By pkrauss Date 2001-04-24 Time 07:56 Rev Time 0.40
Received By pkrauss Date 2001-04-24 Time 07:56 Sent To  
Notes
2001-04-24 00:00:00******************DENIED****************
  
 PLEASE PROVIDE O.A. CALCULATION AS PER
 ASHRAE 62-89.
  
 PLEASE CLARIFY "REMOTE STATUS INDICATOR"
 FOR DUCT SMOKE DETECTOR.WILL THIS BE
 TIED TO A CONSTANTLY ATTENDED LOCATION?
 (NFPA 90A 4-4.4.2)
  
  
 NOTE:CONDENSER WATER PIPING WITH TYPE
 "K" COPPER SHALL BE BRAZED AS
 PER 1997 SMC TABLE 1205.

Review Stop P PLUMBING
Rev No 2 Status N Date 2001-07-02 Cont ID  
Sent By jwitmer Date 2001-07-02 Time 18:59 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-27 00:00:00PLUMBING REVISION OK,PES

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-05-07 Cont ID  
Sent By jleech Date 2001-05-07 Time 19:47 Rev Time 0.50
Received By jleech Date 2001-05-07 Time 19:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-06-20 Cont ID  
Sent By lsmith Date 2001-06-20 Time 16:19 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***