2001-04-17 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT# 01040463 |
| 515 N FLAGLER SUITE 101 |
| CONT: LEIGHTON MCGINN |
| 863-4455 |
| |
| 1)- FLORIDA ACCESSIBILITY CODE 4.1.3 |
| ACCESSIBILE BUILDINGS: |
| 4.1.3 (NEW) VERTICAL ACCESSIBILITY SHALL |
| BE PROVIDED TO ALL LEVELS ABOVE & BELOW |
| THE OCCUPIABLE GRADE LEVEL. |
| 4.1.5. (ADDITIONS) EACH SPACE OR ELEMENT |
| ADDED TO THE EXISTING BUILDING OR FACIL- |
| ITY SHALL COMPLY WITH THE PROVISIONS OF |
| 4.1.1 TO 4.1.3, MINIMUM REQUIREMENTS FOR |
| NEW CONSTRUCTION. |
| 4.1.6 ( ALTERATIONS) (A) NO ALTERATION |
| SHALL BE UNDERTAKEN WHICH DECREASES OR |
| HAS THE EFFECT OF DECREASING ACCESSIBIL- |
| ITY OR USABILITY OF A BUILDING OR FACIL- |
| ITY BELOW THE REQUIREMENTS FOR NEW |
| CONSTRUCTION AT THE TIME OF ALTERATION. |
| |
| VERTICAL ACCESSIBILITY TO THE MEZZANINE |
| WILL BE REQUIRED. THE PROBLEM IS WHEN |
| THE VERTICAL ACCESSIBILITY IS FIGURED |
| THE LIFT OR ELEVATOR WILL CONNECT TO |
| BOTH MEZZANINES MAKING (1) MEZZANINE |
| WITH A SQUARE FOOT AREA OF 400 SQ. FT. |
| |
| 2)- SBC 1007.8.2 WILL ONLY ALLOW SPIRAL |
| STAIRS AS A MEANS OF EGRESS FOR A |
| MEZZANINE WHEN NOT MORE THAN 250 SQ. FT. |
| |
| A SOLUTION:A SOLUTION TO THE VERTICAL |
| ACCESSIBILITY IS TO APPLY FOR A VARIANCE |
| TO THE STATE. IF THEY APPROVE THE VARI- |
| ANCE THERE WILL REMAIN 2 INDEPENDENT |
| SPIRAL STAIRS WHICH WILL NEED TO MEET |
| CRITERIA OF 1007.8.2. |
| |
| 3)- SBC 903.1 AUTOMATIC FIRE SPRINKLER |
| SYSTEM, LAYOUT OF ALL SPRINKLER, DEVICES |
| AND SYSTEM SHALL BE SUBMITTED TO THE |
| BUILDING DEPARTMENT. |
| 4)- BUILDING DATA: NOT TYPE IV BUT |
| TYPE I. |
| |
| 5)- PLANS SHALL BE SUBMITTED TO P B CO. |
| BUILDING DEPARTMENT FOR IMPACT FEES. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561) 659-8096 EX 8412. |