Plan Review Details - Permit 01040428
Plan Review Stops For Permit 01040428
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-07-17 Cont ID  
Sent By jwitmer Date 2001-07-17 Time 17:15 Rev Time 1.65
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-07-11 Cont ID  
Sent By lsmith Date 2001-07-11 Time 15:45 Rev Time 0.25
Received By lsmith Date   Time   Sent To  
Notes
2001-07-11 00:00:00RINKER CONCRETE SPECS.ONE COPY TO DON
 OTHER BACK TO CONTRACTOR LS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2001-07-11 Cont ID  
Sent By lsmith Date 2001-07-11 Time 15:44 Rev Time 0.00
Received By lsmith Date 2001-06-29 Time 10:36 Sent To  
Notes
2001-07-11 00:00:00NO ONE POSTED THESE ON COMPUTER LS 7/11
 HAROLD PISKURA APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-06-04 Cont ID  
Sent By hpiskura Date 2001-06-04 Time 13:41 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-30 Cont ID  
Sent By hpiskura Date 2001-04-30 Time 11:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-04-30 00:00:001 THE BUILDING EXCEEDS THE ARE ALLOWED
 BY TABLE 600 FOR GROUP B OR S FOR TYPE
 IV FS CONSTRUCTION.PLEASE REVISE AS
 NECESSARY.
  
 2IMPACT FEES MUST BE PAID TO THE
 CONUTY.CALL 233-5025 FOR MORE
 INFORMATION.
  
 2BLDG WILL BE IN AN A9 FLOOD ZONE BFE
 13.0' NGVD>PROVIDE ELEVATION
 CERTIFICATE.
  
 A RESIDENT INSPECTOR IS REQUIRED FOR
 HTHIS WQORK.CALL DON NEELY 659-8096 X
 8333 FOR MORE INFORMATION.
  
 PROVIDE PRODUCT APPROVALS FOR THE DOORS,
 WINDOWS AND ROFF COVERING.SBC 104.2.
  
 PLEASE PROVIDE A RECENT SURVEY.
  
 SHOW HOW HURRICANE MISSILE IMPACT WILL
 BE ADDRESSED.
  
 SECTION 5/A5.1 IS NOT FOUND ON THE
 PLANS.
 SHEET A5.1 SHOWS COMBUSTIBLE TRIM
 PROJECTING ABOVE THE WALL WHICH IS NOT
 ALLOWED
 BY SBC 1401.1.1.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-11-20 Cont ID  
Sent By dpalmer Date 2001-11-20 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2001-11-20 Time 18:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-11-05 Cont ID  
Sent By dpalmer Date 2001-11-05 Time 18:04 Rev Time 0.00
Received By dpalmer Date 2001-11-05 Time 18:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-10-03 Cont ID  
Sent By dpalmer Date 2001-10-03 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2001-10-03 Time 14:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-07-30 Cont ID  
Sent By dpalmer Date 2001-07-30 Time 08:14 Rev Time 0.00
Received By dpalmer Date 2001-07-30 Time 08:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-07-09 Cont ID  
Sent By dpalmer Date 2001-07-09 Time 07:02 Rev Time 0.00
Received By dpalmer Date 2001-06-29 Time 10:38 Sent To  
Notes
2001-07-09 00:00:00******************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT UNDER F.S, AND
 F.A.C PLANS ARE TO BE SIGNED AND SEALED
 BY THE ARCH/ENGINEER OF RECORD PER
 471.025 AND 481.221.
  
 PLEASE SUBMIT REVISIONS FOR REVIEW
 AFTER BEING SIGNED, DATED AND SEALED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-04-27 Cont ID  
Sent By dpalmer Date 2001-04-27 Time 07:18 Rev Time 0.00
Received By dpalmer Date 2001-04-27 Time 07:17 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2001-07-19 Cont ID  
Sent By mamini Date 2001-07-19 Time 08:20 Rev Time 0.00
Received By mamini Date 2001-07-19 Time 08:20 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-05-16 Cont ID  
Sent By mamini Date 2001-05-16 Time 15:27 Rev Time 2.00
Received By mamini Date 2001-05-16 Time 15:21 Sent To  
Notes
2001-05-16 00:00:00PASSED:
 1. RESPONSES TO PREVIOUS REVIEW COMMENTS
 DATED 4-24-01 SATISFACTORY.PLANS
 REVISED PER REVIEW COMMENTS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-04-24 Cont ID  
Sent By mamini Date 2001-04-24 Time 13:06 Rev Time 4.00
Received By mamini Date 2001-04-24 Time 11:21 Sent To  
Notes
2001-04-24 00:00:00FAILED:
 1. PERVIOUS & IMPERVIOUS CALCULATIONS
 MUST BE SHOWN ON PAVING AND DRAINAGE
 PLAN, THE TOTAL AMOUNT MUST EQUAL 100 %
 OF TOTAL SITE ACRES OR S.F.PLEASE
 STATE EITHER ADDRESSES OR PROPERTY
 CONTROL NUMBER.STORM WATER CHARGES
 WILL BE CALCULATED FROM THESE.
 2. PLEASE PROVIDE STORM WATER
 CALCULATION FOR OUR REVIEW IF YOU HAVE
 NOT SUBMITTED TO JOSE DEL RIO, STORM
 WATER ENGINEER, 1000 45TH STREET WEST
 PALM BEACH, FL 33407. PLEASE SEE
 ATTACHED
 3. ONCE REVISED, TWO SETS OF PLANS MUST
 BE SUBMITTED TO PUBLIC UTILITIES
 ENGINEERING SERVICES FOR THIER REVIEW
 AND ACTUAL SERVICE CONNECTIONS.
 4. WORK PERFORMED ALONG PUBLIC R.O.W
 REQUIRES A PERMIT THROUGH CITY ENGINEERS
 OFFICE, RICHARD PITTMAN.
 1000 45TH STREET WEST PALM BEACH, FL
 33407
 5. PLEASE VERIFY SECTION A-A AS SHOWN ON
 SHEET 5 OF 10.IS THERE A 10' UTILITY
 EASEMENT ON THAT SIDE? IF SO,PLEASE SHOW
 6. PLEASE COORDINATE WITH PUBLIC
 UTILITIES ENGINEERING SEVICES DEPARTMENT
 FOR CONNECTION OF SERVICES (WATER,
 SANITARY).PERHAPS YOU COULD ELIMINATE
 THE 30' U.E IN PARKING AREA BY OTHER
 ALTERNATIVE SUCH AS INSTALLING 8" DIP
 AND SANITARY ALONG BRISTOL DRIVE GOING
 SOUTH AND THEN CONNECTING TO THE
 EXISTINGS ON SOUTHSIDE OF PROPERTY.
 THIS WILL LOCATE THE BACKFLOW PREVENTERS
 ON BACK OF SIDEWALK AND PROPERTY LINES.
 A MEETING WITH PUBLIC UTILITIES
 ENGINEERING SERVICES IS RECOMMENDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-07-18 Cont ID  
Sent By rturnque Date 2001-07-18 Time 11:16 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
2001-07-18 00:00:00FIRE HYDRANT SHALL LOCATED WITHIN 150
 FEET OF FIRE DEPARTMENT CONNECTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-04-20 Cont ID  
Sent By mcarsill Date 2001-04-20 Time 13:39 Rev Time 0.00
Received By mcarsill Date 2001-04-20 Time 13:38 Sent To  
Notes
2001-04-20 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS.
 2) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE FIRE
 SPRINKLER SYSTEM.
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE FIRE ALARM
 SYSTEM.
 4) A KNOX-BOX RAPID ENTRY SYSTEM WILL
 BE REQUIRED FOR FIRE RESCUE PURPOSES.
 APPLICATIONS CAN BE OBTAINED FROM FIRE
 RESCUE, 835-2910.
 5) NO EMERGENCY LIGHTING FIXTURES
 SHOWN.
 6) PLANS ARE TO BE SUBMITTED FOR TENANT
 REMODEL PRIOR TO BEGINNING WORK.
 7) DUCT SMOKE DETECTORS ARE REQUIRED IN
 AIR HANDLING SYSTEMS OVER 2000 CFM. WHEN
 ACTIVATED, THEY ARE TO SHUT DOWN AIR
 HANDLING EQUIPMENT AND ACTIVATE THE
 BUILDINGS FIRE ALARM SYSTEM.
 8) DURING CONSTRUCTION, FIRE HYDRANTS
 AND SUITABLE ROADS TO ACCESS THE
 PROPERTY ARE TO BE PROVIDED DURING
 CONSTRUCTION.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-07-10 Cont ID  
Sent By pkrauss Date 2001-07-05 Time 14:53 Rev Time 0.45
Received By pkrauss Date 2001-07-05 Time 14:53 Sent To  
Notes
2001-07-05 00:00:00*******************PROVISO**************
  
  
  
 THIS IS FOR "SHELL" ONLY.
  
 NOTE:EXHAUST FANS SHALL BE A MINIMUM
 OF 10' FROM ANY FRESH AIR INTAKES
  
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-06-08 Cont ID  
Sent By pkrauss Date 2001-06-08 Time 07:35 Rev Time 0.35
Received By pkrauss Date 2001-06-08 Time 07:35 Sent To  
Notes
2001-06-08 00:00:00MECHANICAL PERMIT 01051534
  
 **********NOTE***************
  
 THIS PERMIT IS FOR SHELL ONLY.
  
 INTERIOR BUILD-OUT UNDER PERMIT 01040869
  
 CHANGE OF CONTRACTOR FOR BOTH PERMITS.
 6/7/01.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-05-14 Cont ID  
Sent By pkrauss Date 2001-05-14 Time 11:34 Rev Time 0.25
Received By pkrauss Date   Time   Sent To  
Notes
2001-05-14 00:00:00PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-05-11 Cont ID  
Sent By pkrauss Date 2001-05-11 Time 13:20 Rev Time 0.35
Received By pkrauss Date 2001-05-11 Time 13:19 Sent To  
Notes
2001-05-11 00:00:00*******************DENIED***************
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.
  
 PLEASE PROVIDE EQUIPMENT INFORMATION,
 OUTSIDE AIR CALCULATIONS (AS PER ASHRAE
 62-89), AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2, AND
 LAYOUT OF DUCTWORK & AIR DISTRIBUTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-07-30 Cont ID  
Sent By jleech Date 2001-07-30 Time 15:20 Rev Time 1.50
Received By jleech Date 2001-07-30 Time 15:20 Sent To  
Notes
2001-07-30 00:00:00REVISION; FLOOR SINKS DELETED.

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-07-29 Cont ID  
Sent By jleech Date 2001-07-29 Time 09:52 Rev Time 1.50
Received By jleech Date 2001-07-29 Time 09:52 Sent To  
Notes
2001-07-29 00:00:00DENIED;
 1.THIS PLAN IS FOR THE SHELL, REVISIONS
 REQUIRED ARE FOR TENENT IMPROVMENT.
 2.EYEWASH AND SHOWERS NOT SHOWN. NEED
 LOCATIONS. ONLY ONE FLOOR SINK SHOWN
 ON PLAN SHOULD BE THREEINSIDE AND
 ONE OUTSIDE.
 3.WATER RISER DIAGRAM DOES NOT SHOW
 EYEWASH AND SHOWER DROPS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-06-30 Cont ID  
Sent By jleech Date 2001-06-30 Time 13:03 Rev Time 1.00
Received By jleech Date 2001-06-30 Time 13:03 Sent To  
Notes
2001-06-30 00:00:00PLUMBING REVISION DENIED;
  
 PERMIT IS FOR SHALL ONLY. SAND INTER-
 CEPTOR IS NOT PART OF SHELL.
 REVISIONS ON PLUMBING PAGE HAD NO CLOUD
 OR TRIANGLE 3 OR DATE OF JUNE 8TH FOR
 LAST ADDITION. WAS THIS AN OVERSIGHT?
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-05-27 Cont ID  
Sent By pschmitz Date 2001-05-27 Time 16:34 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-27 00:00:00PLUMBING PLAN REVIEWPROVISO
 PREVIOUS COMMENTS NOT ADDRESSED
 THIS PERMIT FOR SHELL ONLY, NO TENNANT
 IMPROVMENTS.
 END ON COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-05-10 Cont ID  
Sent By pschmitz Date 2001-05-10 Time 11:02 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-05-10 00:00:00PLUMBING PLANA REVIEWDENIED
 SHT P-2 APPLICATION FOR THIS PERMIT IS
 FOR SHELL ONLY,DOES NOT INCLUDE TENANT
 IMPROVEMENTS.
 IF YOU WOULD LIKE TO INCLUDE THE TENANT
 IMPROVEMENT ON THIS PLAN, WE NEED
 ADDITONAL INFORMATION ON THE OCCUPANCY,
 WITH CALCULATIONS,FOR MINIMUM FACILITIES
 SPC 94 TAB 407.
 ALSO,ADDITONAL FEES BASED ON VALUE OF
 WORK ADDED.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233

Review Stop Z ZONING
Rev No 2 Status P Date 2001-06-25 Cont ID  
Sent By sgraham Date 2001-06-25 Time 15:19 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-05-15 Cont ID  
Sent By sgraham Date 2001-05-15 Time 09:20 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-05-15 00:00:00CONTRACTOR MUST PROVIDE DOCUMENTS
 SHOWING ADANDONMENT OF EASEMENT BEFORE
 ZONING APPROVAL. CONTRACTOR WAS INFORMED
 ON 5-14-01 WHEN HE RESUBMITTED THESE
 PLANS SG
2001-05-14 00:00:00PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.