Plan Review Stops For Permit 01040393 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2001-05-03 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-05-03 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2001-05-02 |
Time |
13:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-03-04 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-03-04 |
Time |
18:36 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-03-04 |
Time |
17:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-07-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-07-03 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-07-03 |
Time |
16:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-04-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-04-19 |
Time |
22:06 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-04-19 |
Time |
22:06 |
Sent To |
|
|
Notes |
2001-04-19 00:00:00 | ****************** UNSAT ************* | | | | 1)NOTE: PLEASE SHOW ALL LOAD | | CALCULATIONS, TO INCLUDE AMPERAGES. | | PLEASE NOTE THAT ALL CONTINUOUS AND | | LARGEST MOTOR LOADS NEED TO BE SHOWN AT | | 125%. ALL PER | | 215-5, 215-2, 215-3. | | | | 2)NOTE: PLEASE NOTE FOR GROUPING OF | | MEANS OF DISCONNECT FOR POWER COMING | | FROM | | GENERATOR PER 230-72, 230-76,230-79. | | | | 3)NOTE: PLEASE NOTE THAT UNDER PALM | | BEACH COUNTYWIDE AND CITY OF WEST PALM | | BEACHAMENDMENTS: COLOR CODING IN SPEC | | BOOK FOR 277/480V IS SHOWN B,O,Y. THIS | | NEEDS TO BE BROWN, PURPLE YELLOW. | | ART;215 LOCAL.AMENDMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANYQUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2001-06-26 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-06-26 |
Time |
08:47 |
Rev Time |
2.00 |
Received By |
mamini |
Date |
2001-06-26 |
Time |
08:46 |
Sent To |
|
|
Notes |
2001-06-26 00:00:00 | PASSED: | | 1. RESPONSES TO PREVIOUS REVIEW COMMENTS | | DATED 3-5-01, 5-18-01, 4-12-01 | | SATISFACTORY.PLANS HAVE BEEN REVISED | | PER REVIEW COMMENTS AND CALCULATIONS | | PROVIDED. | | NOTES - THIS PLAN REVIEW APPROVES CIVIL | | PLANS FOR BOTH PERMITS # 01040393 AND | | 01021024. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2001-04-12 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-04-12 |
Time |
08:40 |
Rev Time |
4.00 |
Received By |
mamini |
Date |
2001-04-12 |
Time |
08:40 |
Sent To |
|
|
Notes |
2001-04-12 00:00:00 | FAILED: | | 1. INSUFFICIENT INFORMATION FOR CIVIL | | ENGINEERING REVIEW.PLEASE RESUBMIT | | WHEN CIVIL PLANS ARE DEVELOPED. | | 2. PLEASE PROVIDE DRAINAGE CALCULATIONS | | & PLANS TO JOSE DEL RIO, STORM WATER | | ENGINEER, 100045TH STREEET WEST PALM | | BEACH, FL 33415(561) 659-8040 | | 3. PLEASE PROVIDE PERVIOUS & IMPERVIOUS | | CALCULATION FOR ENTIRE SITE DUE TO | | PROPOSED CHANGES, SIGNED & SEALED BY | | DESIGN ENGINEER.PLEASE SUBMIT THIS | | INFORMATION ON A 8 1/2 X 11 SHEET TO | | MANNY GONZALEZ, PROJECT COORDINATE | | SPECIALIST, 100045TH STREET WEST PALM | | BEACH, FL 33415 (561) 659-8040 | | 4. PERMIT FROM HEALTH DEPARTMENT MUST BE | | OBTAINED FOR RELOCATING THE FIRE HYDRANT | | IF THE DISTANCE FORM MAIN IS MORE THAN | | 50'. | | 5. PLEASE STATE IF GARBAGE IS TO BE | | PICKED UP BY THE CITY OR PRIVATE PICK UP | | ,IF TO BE PICKED UP BY THE CITY, THEN AN | | APPROVAL FROM PUBLIC UTILITIES | | DEPARTMENT, JOHNNY THOMAS, SOLID WASTE | | SUPERINTENDENT IS REQUIRED.THE OPENING | | BETWEEN THE GATE POSTS MAY NOT BE | | ADEQUTE FOR DOUBLE DUMPSTERS AS SHOWN. | | IF ANY QUESTION PLEASE CONTACT 561- 659- | | 8096 EXT. 8492 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2001-07-10 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-10 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-10 |
Time |
08:39 |
Sent To |
|
|
Notes |
2001-07-10 00:00:00 | ON JUNE 9, 2001, WRITER RECEIVED | | DOCUMENTATION FROM THE WEITZ COMPANY. | | WITH REGARDS TO SECTION 5-12, THIS | | SECTION WAS LOCATED IN LATER EDITIONS | | OF THE LIFE SAFETY CODE AND IT APPEARED | | THAT IS WAS NOT PRESENT IN THE 1985 | | EDITION OF THE CODE. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2001-06-25 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-06-25 |
Time |
09:37 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-06-25 |
Time |
09:37 |
Sent To |
|
|
Notes |
2001-06-25 00:00:00 | 1) ACCORDING TO WEITZ PERSONNEL, THE | | EXISTING GATE LOCATED ON JEFFERSON ROAD | | IS EXISTING AND NOT EQUIPPED WITH ANY | | PROVISIONS FOR OPENING IT WHEN LOSS OF | | POWER OCCURS. IT WAS REPORTED THAT THE | | GATES ARE FAIL SECURE. THE FDC AND THE | | HYDRANT SHOULD BE LOCATED ON THE SAME | | SIDE OF THE SECURITY FENCE. IF THE | | PRESENT SECURITY FENCE IS NOT MODIFIED | | THEN THESE DEVICES SHOULD BE LOCATED | | OUTSIDE OF IT. | | 2) COULD NOT LOCATE CODE SECTION 5-12 | | REGARDING SINGLE EXIT AND TRAVEL | | DISTANCE OF 100 FEET. PLEASE PROVIDE | | APPLICABLE CODE SECTION. | | 3) EIGHTEEN FEET MUST BE PROVIDED FROM | | FIRE HYDRANTS TO ANY OBSTRUCTIONS PER | | CITY CODE REQUIREMENTS. | | 4) PLEASE PROVIDE MORE DETAILS ON | | EMERGENCY GENERATOR. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-04-12 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-04-12 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-04-12 |
Time |
09:23 |
Sent To |
|
|
Notes |
2001-04-12 00:00:00 | 1) BOLLARDS SHOWN ON PAGE C1 ARE NOT | | TO INTERFERE WITH OPERATION OF THE | | FIRE HYDRANT. | | 2) ANY ROOM CONTAINING FLAMMABLE OR | | COMBUSTIBLE LIQUIDS MUST BE SEPARATED | | FROM OTHER PARTS BY AT LEAST A TWO | | HOUR FIRE SEPARATION. OPENINGS ARE TO | | BE PROTECTED BY B LABELED (1 1/2 HOUR) | | FIRE DOORS WITH CLOSERS. ADEQUATE | | VETILATION IS TO BE PROVIDED. | | 3) STAIRS TO COMPLY WITH NEW STAIRS | | PER NFPA 101, THE LIFE SAFETY CODE, | | 1985 EDITION. | | 4) HANDRAILS AND GUARDS TO COMPLY WITH | | NFPA 101, THE LIFE SAFETY CODE, 1985 | | EDITION. | | 5) THE FIRE DEPARTMENT CONNECTION SHOWN | | ON PAGE FP1.1B IS TO BE WITHIN 150 FEET | | OF A FIRE HYDRANT. THE REMOVAL AND | | RE-INSTALLATION OF THE FIRE PUMP SHALL | | BE GIVEN THE HIGHEST PRIORITY FOR | | COMPLETION. | | 6) EMERGENCY LIGHTING REQUIRED IN FIRE | | PUMP ROOM. | | 7) PLEASE EXPLAIN RATIONALE FOR EXITING | | FROM THE SECOND FLOOR. EXIT STAIR # 6 | | IS LOCATED IN A STORAGE ROOM AND | | TERMINATES IN A STORAGE ROOM. | | 8) PROVIDE MORE DETAILS ON EMERGENCY | | GENERATOR AND APPURTENANT EQUIPMENT. | | 9) PLEASE INDICATE REFRIGERANT PLANNED | | FOR USE. PLEASE INDICATE EMERGENCY | | WARNING EQUIPMENT, SIGNS, AND SELF | | CONTAINED BREATHING APPARATUS USED IN | | THE EVENT OF A REFRIGERANT LEAK. | | 10) SEPARATE PLANS AND PERMITS REQUIRED | | FOR THE FIRE ALARM REMODEL. CUT SHEETS, | | WIRING DIAGRAM, AND BATTERY CALCULATIONS | | ARE REQUIRED. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-07-10 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-07-10 |
Time |
11:27 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2001-07-10 |
Time |
11:27 |
Sent To |
|
|
Notes |
2001-07-10 00:00:00 | *******************PROVISO************** | | | | BREATHING APPARATUS AND ALARMS SHALL BE | | INDENTIFIED ON THE PLAN. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2001-04-24 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-04-24 |
Time |
10:51 |
Rev Time |
3.00 |
Received By |
pkrauss |
Date |
2001-04-23 |
Time |
15:17 |
Sent To |
|
|
Notes |
2001-04-24 00:00:00 | *******************DENIED*************** | | | | PLEASE PROVIDE FOLLOWING INFORMATION | | WITH MECHANICAL PERMIT APPLICATION. | | | | 1.SIGN SHALL BE POSTED ON MACHINERY | | ROOM DOOR PROHIBITING ACCESS OF | | UNAUTHORIZED PERSONNEL. | | | | 2.EXHAUST OUTLETS SHALL BE LOCATED | | 10 FT FROM ANY DOOR, WINDOW OR AIR | | INTAKE AND AT LEAST 10 FT ABOVE THE | | ADJOINING GRADE LEVEL. 1997 SMC | | 506.1 - (H1.1B). | | | | 3.AS PER 1997 SMC 1105.8, AT LEAST | | ONE APPROVED SELF-CONTAINED | | BREATHING APPARATUS, SUITABLE | | FOR THE REGRIGERANT USED, SHALL BE | | AVAILABLE TO AUTHORIZED PERSONNEL | | AT A LOCATION CONVENIENT TO THE | | MACHINERY ROOM. | | | | 4.DRAWING E2.1B INDICATES ONE | | REFRIGERANT LEAK DETECTOR WILL THIS | | SUFFICE FOR THREE CHILLERS?ALSO, | | IS THIS TIED INTO THE AUDIBLE/ | | VISUAL ALARM? | | | | 5.ARE THERE TO BE ANY ALARMS LOCATED | | OUTSIDE THE DOORS OF THE CHILLER | | ROOM IN CASE OF A REFRIGERANT LEAK. | | | | 6.DRAWING H1.2B, (3) 2" CHILLER | | REFIEF RISERS TERMINATE 15' ABOVE | | ROOF, SHALL ALSO BE NOT LESS THAN | | 20' FROM ANY VENTILATION OPENING IN | | REFERENCE TO INTAKE LOUVER TO THE | | CHILLED WATER PUMP ROOM. | | | | 7.PLEASE PROVIDE LOCATION OF THE | | BOILERS AND ALSO PROVIDE DETAILS | | OF PIPING AND VENTILAITON FOR | | THE BOILER ROOM. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-07-09 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-07-09 |
Time |
18:14 |
Rev Time |
2.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-07-09 00:00:00 | PLUMBING PLAN REVIEW,PROVISO: | | SEE SHT P1.1B F/D REQ, SHOWERE STALL TO | | BE H/C ACCESSIBLE,FACBC-97 SEC4.21 | | END OF COMMENTS PAUL SCHMITZ | | 561 659-8096X8233 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-04-30 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-04-30 |
Time |
19:03 |
Rev Time |
2.00 |
Received By |
pschmitz |
Date |
2001-04-30 |
Time |
19:03 |
Sent To |
|
|
Notes |
2001-04-30 00:00:00 | DENIED; | | | | 1.SUBMIT SANITARY, WATER, AND RAIN WATER | | RISER DIAGRAMS. | | | | 2.HORIZONTAL DRY VENTS ARE NOT PERMITED. | | (VENTS FOR FLOOR DRAINS). | | | | 3.SHOW DETAIL OF HANDICAP BATHROOM WITH | | MESUREMENTS TO COMPLY WITH 97 FACBC. | | | | 4.3" FLOOR DRAIN, WITH TRAP PRIMER | | REQUIRED IN BATHROOM. | | | | 5.BACKFLOW PROTECTION REQUIRED ON MAKE | | UP WATER SUPPLY AT CHILLER. | | | | 6.WHERE DO THE RAIN WATER LEADERS GO | | AFTER LEAVING THE BUILDING? | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8369 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-07-11 |
|
|
Cont ID |
|
Sent By |
aneil |
Date |
2001-07-11 |
Time |
16:01 |
Rev Time |
1.00 |
Received By |
aneil |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-07-11 00:00:00 | PASSED PER SHIRLE 7-10-01 AN |
|
|