Plan Review Details - Permit 01040393
Plan Review Stops For Permit 01040393
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-05-03 Cont ID  
Sent By hpiskura Date 2001-05-03 Time 10:21 Rev Time 0.00
Received By hpiskura Date 2001-05-02 Time 13:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-03-04 Cont ID  
Sent By btrobaug Date 2002-03-04 Time 18:36 Rev Time 0.00
Received By btrobaug Date 2002-03-04 Time 17:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-03 Cont ID  
Sent By dpalmer Date 2001-07-03 Time 16:26 Rev Time 0.00
Received By dpalmer Date 2001-07-03 Time 16:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-19 Cont ID  
Sent By dpalmer Date 2001-04-19 Time 22:06 Rev Time 0.00
Received By dpalmer Date 2001-04-19 Time 22:06 Sent To  
Notes
2001-04-19 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE SHOW ALL LOAD
 CALCULATIONS, TO INCLUDE AMPERAGES.
 PLEASE NOTE THAT ALL CONTINUOUS AND
 LARGEST MOTOR LOADS NEED TO BE SHOWN AT
 125%. ALL PER
 215-5, 215-2, 215-3.
  
 2)NOTE: PLEASE NOTE FOR GROUPING OF
 MEANS OF DISCONNECT FOR POWER COMING
 FROM
 GENERATOR PER 230-72, 230-76,230-79.
  
 3)NOTE: PLEASE NOTE THAT UNDER PALM
 BEACH COUNTYWIDE AND CITY OF WEST PALM
 BEACHAMENDMENTS: COLOR CODING IN SPEC
 BOOK FOR 277/480V IS SHOWN B,O,Y. THIS
 NEEDS TO BE BROWN, PURPLE YELLOW.
 ART;215 LOCAL.AMENDMENTS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-06-26 Cont ID  
Sent By mamini Date 2001-06-26 Time 08:47 Rev Time 2.00
Received By mamini Date 2001-06-26 Time 08:46 Sent To  
Notes
2001-06-26 00:00:00PASSED:
 1. RESPONSES TO PREVIOUS REVIEW COMMENTS
 DATED 3-5-01, 5-18-01, 4-12-01
 SATISFACTORY.PLANS HAVE BEEN REVISED
 PER REVIEW COMMENTS AND CALCULATIONS
 PROVIDED.
 NOTES - THIS PLAN REVIEW APPROVES CIVIL
 PLANS FOR BOTH PERMITS # 01040393 AND
 01021024.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-04-12 Cont ID  
Sent By mamini Date 2001-04-12 Time 08:40 Rev Time 4.00
Received By mamini Date 2001-04-12 Time 08:40 Sent To  
Notes
2001-04-12 00:00:00FAILED:
 1. INSUFFICIENT INFORMATION FOR CIVIL
 ENGINEERING REVIEW.PLEASE RESUBMIT
 WHEN CIVIL PLANS ARE DEVELOPED.
 2. PLEASE PROVIDE DRAINAGE CALCULATIONS
 & PLANS TO JOSE DEL RIO, STORM WATER
 ENGINEER, 100045TH STREEET WEST PALM
 BEACH, FL 33415(561) 659-8040
 3. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 CALCULATION FOR ENTIRE SITE DUE TO
 PROPOSED CHANGES, SIGNED & SEALED BY
 DESIGN ENGINEER.PLEASE SUBMIT THIS
 INFORMATION ON A 8 1/2 X 11 SHEET TO
 MANNY GONZALEZ, PROJECT COORDINATE
 SPECIALIST, 100045TH STREET WEST PALM
 BEACH, FL 33415 (561) 659-8040
 4. PERMIT FROM HEALTH DEPARTMENT MUST BE
 OBTAINED FOR RELOCATING THE FIRE HYDRANT
 IF THE DISTANCE FORM MAIN IS MORE THAN
 50'.
 5. PLEASE STATE IF GARBAGE IS TO BE
 PICKED UP BY THE CITY OR PRIVATE PICK UP
 ,IF TO BE PICKED UP BY THE CITY, THEN AN
 APPROVAL FROM PUBLIC UTILITIES
 DEPARTMENT, JOHNNY THOMAS, SOLID WASTE
 SUPERINTENDENT IS REQUIRED.THE OPENING
 BETWEEN THE GATE POSTS MAY NOT BE
 ADEQUTE FOR DOUBLE DUMPSTERS AS SHOWN.
 IF ANY QUESTION PLEASE CONTACT 561- 659-
 8096 EXT. 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-07-10 Cont ID  
Sent By mcarsill Date 2001-07-10 Time 08:39 Rev Time 0.00
Received By mcarsill Date 2001-07-10 Time 08:39 Sent To  
Notes
2001-07-10 00:00:00ON JUNE 9, 2001, WRITER RECEIVED
 DOCUMENTATION FROM THE WEITZ COMPANY.
 WITH REGARDS TO SECTION 5-12, THIS
 SECTION WAS LOCATED IN LATER EDITIONS
 OF THE LIFE SAFETY CODE AND IT APPEARED
 THAT IS WAS NOT PRESENT IN THE 1985
 EDITION OF THE CODE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-06-25 Cont ID  
Sent By mcarsill Date 2001-06-25 Time 09:37 Rev Time 0.00
Received By mcarsill Date 2001-06-25 Time 09:37 Sent To  
Notes
2001-06-25 00:00:001) ACCORDING TO WEITZ PERSONNEL, THE
 EXISTING GATE LOCATED ON JEFFERSON ROAD
 IS EXISTING AND NOT EQUIPPED WITH ANY
 PROVISIONS FOR OPENING IT WHEN LOSS OF
 POWER OCCURS. IT WAS REPORTED THAT THE
 GATES ARE FAIL SECURE. THE FDC AND THE
 HYDRANT SHOULD BE LOCATED ON THE SAME
 SIDE OF THE SECURITY FENCE. IF THE
 PRESENT SECURITY FENCE IS NOT MODIFIED
 THEN THESE DEVICES SHOULD BE LOCATED
 OUTSIDE OF IT.
 2) COULD NOT LOCATE CODE SECTION 5-12
 REGARDING SINGLE EXIT AND TRAVEL
 DISTANCE OF 100 FEET. PLEASE PROVIDE
 APPLICABLE CODE SECTION.
 3) EIGHTEEN FEET MUST BE PROVIDED FROM
 FIRE HYDRANTS TO ANY OBSTRUCTIONS PER
 CITY CODE REQUIREMENTS.
 4) PLEASE PROVIDE MORE DETAILS ON
 EMERGENCY GENERATOR.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-04-12 Cont ID  
Sent By mcarsill Date 2001-04-12 Time 09:23 Rev Time 0.00
Received By mcarsill Date 2001-04-12 Time 09:23 Sent To  
Notes
2001-04-12 00:00:001) BOLLARDS SHOWN ON PAGE C1 ARE NOT
 TO INTERFERE WITH OPERATION OF THE
 FIRE HYDRANT.
 2) ANY ROOM CONTAINING FLAMMABLE OR
 COMBUSTIBLE LIQUIDS MUST BE SEPARATED
 FROM OTHER PARTS BY AT LEAST A TWO
 HOUR FIRE SEPARATION. OPENINGS ARE TO
 BE PROTECTED BY B LABELED (1 1/2 HOUR)
 FIRE DOORS WITH CLOSERS. ADEQUATE
 VETILATION IS TO BE PROVIDED.
 3) STAIRS TO COMPLY WITH NEW STAIRS
 PER NFPA 101, THE LIFE SAFETY CODE,
 1985 EDITION.
 4) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION.
 5) THE FIRE DEPARTMENT CONNECTION SHOWN
 ON PAGE FP1.1B IS TO BE WITHIN 150 FEET
 OF A FIRE HYDRANT. THE REMOVAL AND
 RE-INSTALLATION OF THE FIRE PUMP SHALL
 BE GIVEN THE HIGHEST PRIORITY FOR
 COMPLETION.
 6) EMERGENCY LIGHTING REQUIRED IN FIRE
 PUMP ROOM.
 7) PLEASE EXPLAIN RATIONALE FOR EXITING
 FROM THE SECOND FLOOR. EXIT STAIR # 6
 IS LOCATED IN A STORAGE ROOM AND
 TERMINATES IN A STORAGE ROOM.
 8) PROVIDE MORE DETAILS ON EMERGENCY
 GENERATOR AND APPURTENANT EQUIPMENT.
 9) PLEASE INDICATE REFRIGERANT PLANNED
 FOR USE. PLEASE INDICATE EMERGENCY
 WARNING EQUIPMENT, SIGNS, AND SELF
 CONTAINED BREATHING APPARATUS USED IN
 THE EVENT OF A REFRIGERANT LEAK.
 10) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE ALARM REMODEL. CUT SHEETS,
 WIRING DIAGRAM, AND BATTERY CALCULATIONS
 ARE REQUIRED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-10 Cont ID  
Sent By pkrauss Date 2001-07-10 Time 11:27 Rev Time 0.50
Received By pkrauss Date 2001-07-10 Time 11:27 Sent To  
Notes
2001-07-10 00:00:00*******************PROVISO**************
  
 BREATHING APPARATUS AND ALARMS SHALL BE
 INDENTIFIED ON THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-04-24 Cont ID  
Sent By pkrauss Date 2001-04-24 Time 10:51 Rev Time 3.00
Received By pkrauss Date 2001-04-23 Time 15:17 Sent To  
Notes
2001-04-24 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 1.SIGN SHALL BE POSTED ON MACHINERY
 ROOM DOOR PROHIBITING ACCESS OF
 UNAUTHORIZED PERSONNEL.
  
 2.EXHAUST OUTLETS SHALL BE LOCATED
 10 FT FROM ANY DOOR, WINDOW OR AIR
 INTAKE AND AT LEAST 10 FT ABOVE THE
 ADJOINING GRADE LEVEL. 1997 SMC
 506.1 - (H1.1B).
  
 3.AS PER 1997 SMC 1105.8, AT LEAST
 ONE APPROVED SELF-CONTAINED
 BREATHING APPARATUS, SUITABLE
 FOR THE REGRIGERANT USED, SHALL BE
 AVAILABLE TO AUTHORIZED PERSONNEL
 AT A LOCATION CONVENIENT TO THE
 MACHINERY ROOM.
  
 4.DRAWING E2.1B INDICATES ONE
 REFRIGERANT LEAK DETECTOR WILL THIS
 SUFFICE FOR THREE CHILLERS?ALSO,
 IS THIS TIED INTO THE AUDIBLE/
 VISUAL ALARM?
  
 5.ARE THERE TO BE ANY ALARMS LOCATED
 OUTSIDE THE DOORS OF THE CHILLER
 ROOM IN CASE OF A REFRIGERANT LEAK.
  
 6.DRAWING H1.2B, (3) 2" CHILLER
 REFIEF RISERS TERMINATE 15' ABOVE
 ROOF, SHALL ALSO BE NOT LESS THAN
 20' FROM ANY VENTILATION OPENING IN
 REFERENCE TO INTAKE LOUVER TO THE
 CHILLED WATER PUMP ROOM.
  
 7.PLEASE PROVIDE LOCATION OF THE
 BOILERS AND ALSO PROVIDE DETAILS
 OF PIPING AND VENTILAITON FOR
 THE BOILER ROOM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-07-09 Cont ID  
Sent By pschmitz Date 2001-07-09 Time 18:14 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-07-09 00:00:00PLUMBING PLAN REVIEW,PROVISO:
 SEE SHT P1.1B F/D REQ, SHOWERE STALL TO
 BE H/C ACCESSIBLE,FACBC-97 SEC4.21
 END OF COMMENTS PAUL SCHMITZ
 561 659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-04-30 Cont ID  
Sent By jleech Date 2001-04-30 Time 19:03 Rev Time 2.00
Received By pschmitz Date 2001-04-30 Time 19:03 Sent To  
Notes
2001-04-30 00:00:00DENIED;
  
 1.SUBMIT SANITARY, WATER, AND RAIN WATER
 RISER DIAGRAMS.
  
 2.HORIZONTAL DRY VENTS ARE NOT PERMITED.
 (VENTS FOR FLOOR DRAINS).
  
 3.SHOW DETAIL OF HANDICAP BATHROOM WITH
 MESUREMENTS TO COMPLY WITH 97 FACBC.
  
 4.3" FLOOR DRAIN, WITH TRAP PRIMER
 REQUIRED IN BATHROOM.
  
 5.BACKFLOW PROTECTION REQUIRED ON MAKE
 UP WATER SUPPLY AT CHILLER.
  
 6.WHERE DO THE RAIN WATER LEADERS GO
 AFTER LEAVING THE BUILDING?
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2001-07-11 Cont ID  
Sent By aneil Date 2001-07-11 Time 16:01 Rev Time 1.00
Received By aneil Date   Time   Sent To  
Notes
2001-07-11 00:00:00PASSED PER SHIRLE 7-10-01 AN