Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-23 Cont ID  
Sent By dpalmer Date 2001-10-23 Time 15:08 Rev Time 0.00
Received By dpalmer Date 2001-10-23 Time 15:08 Sent To  
Notes
2001-10-23 00:00:00******************** UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT PLANS WERE
 SUBMITTED AND ARE FOR "FINAL" "CO".
 PLEASE NOTE THAT THE CODE ART REFERENCED
 FOR GROUNDING ELECTRODE CONDUCTORS,
 ARE UNDER "96 NEC. ART FOR "99" NEC IS
 250-50.
 COLD WATER PIPE ALSO,,,(IF METAL)
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMNET
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. PER 250-122
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW
 BEFORE FINAL.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-04-25 Cont ID  
Sent By dpalmer Date 2001-04-25 Time 17:23 Rev Time 0.00
Received By dpalmer Date 2001-04-25 Time 17:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-05-02 Cont ID  
Sent By mcarsill Date 2001-05-02 Time 12:58 Rev Time 0.00
Received By mcarsill Date 2001-05-02 Time 12:58 Sent To  
Notes
2001-05-02 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
 2) BUILDING ADDRESSES REQUIRED PER CITY
 CODE REQUIREMENTS.
 3) ELECTRIC POWERED SMOKE DETECTORS ARE
 REQUIRED.
 4) PORTABLE FIRE EXTINGUISHERS WITH
 CURRENT SERVICE TAGS ARE REQUIRED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-04-25 Cont ID  
Sent By pkrauss Date 2001-04-25 Time 13:17 Rev Time 1.00
Received By pkrauss Date 2001-04-25 Time 13:17 Sent To  
Notes
2001-04-25 00:00:00MECH PERMIT 01040147

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-04-23 Cont ID  
Sent By kstevens Date 2001-04-23 Time 20:24 Rev Time 0.33
Received By kstevens Date 2001-04-23 Time 20:24 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-05-01 Cont ID  
Sent By jgomez Date 2001-05-01 Time 18:14 Rev Time 1.00
Received By jgomez Date 2001-05-01 Time 18:14 Sent To  
Notes
2001-05-01 00:00:00APPROVED WITH PROVISO:
  
 1-FLOOD ZONE AO. PROVIDE ELEVATION
 CERTIFICATE.
  
 2-PROVIDE PRODUCT APPROVAL FOR:
 -DOUBLE FRENCH DOORS.
 -FRENCH W/ SIDELITES SINGLE ASSEMBLY.
 -WINDOW MULLIONS.
 -UL LISTING AND SPECS FOR BBQ.
  
 3-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS UNDER A SEPARATE PERMIT.
  
 4-PROVIDE ENGINEERED BORINGS AS
 REQUESTED BY DUNKELBERGER ENGINEERING
 ON THEIR PRELIMINARY SOIL TEST REPORT.
  
 5-PROVIDE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM
 COMPLETED BY THE ENGINEER OF RECORD.
  
  
 NOTE:
 THESE COMMENTS APPLY TO THE FOLLOWING
 PERMIT NUMBERS: 01040095, 01040100,
 01040105, 01040107, 01040108, 01040109.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-04-17 Cont ID  
Sent By sgraham Date 2001-04-17 Time 09:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***