Plan Review Details - Permit 01031119
Plan Review Stops For Permit 01031119
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-06 Cont ID  
Sent By jwitmer Date 2001-04-06 Time 13:34 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-03 Cont ID  
Sent By jwitmer Date 2001-04-03 Time 07:33 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-03 00:00:00BUILDING PLAN REVIEW
  
 1)- 1997 FL ACCESSIBILITY CODE 4.13.6:
 MANAUVERING DISTANCES AT DOORS, DOOR 143
 REQUIRES 18" PULL SIDE OF DOORS.
  
 2) 1997 FL ACC CODE 4.13.6: MANAUVERING
 DISTANCES AT DOOR POCKET DOOR REQUIRES
 A MIN. 32" CLEAR, DRAWN 30" LABELED 36".
  
 3)- SHEET A-3 WOOD SUB BUCKS AND WOOD
 BACKING ARE REQUIRED TO BE FIRE TREATED
 WOOD, (SBC 609.2.1).
  
 4)- MINIMUM INTERIOR FINISH SCHEDULE
 (SBC 803.3).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-09 Cont ID  
Sent By dpalmer Date 2001-04-09 Time 12:00 Rev Time 0.00
Received By dpalmer Date 2001-04-09 Time 11:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-03-29 Cont ID  
Sent By dpalmer Date 2001-03-29 Time 21:09 Rev Time 0.00
Received By dpalmer Date 2001-03-29 Time 21:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-06 Cont ID  
Sent By mcarsill Date 2001-04-06 Time 09:55 Rev Time 0.00
Received By mcarsill Date 2001-04-06 Time 09:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-29 Cont ID  
Sent By mcarsill Date 2001-03-29 Time 07:57 Rev Time 0.00
Received By mcarsill Date 2001-03-29 Time 07:57 Sent To  
Notes
2001-03-29 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 WITH PLANS. PLEASE PROVIDE FIRE
 SPRINKLER PLANS.
 2) NO INTERIOR FINISH CLASSIFICATION.
 PLEASE PROVIDE INTERIOR FINISH
 INFORMATION. MATERIALS ON WALLS AND
 CEILINGS MUST BE CLASS A, B, OR C.
 3) SMOKE DETECTOR(S) NOT SHOWN IN
 ELEVATOR LOBBY. THERE SHOULD BE SMOKE
 DETECTORS ALREADY PRESENT TO RECALL
 THE ELEVATORS. IF THEY ARE GOING TO
 BE REMOVED, THEY MUST BE RE-INSTALLED.
 SEPARATE PLANS AND PERMITS REQUIRED FOR
 FIRE ALARM REMODEL.
 4) PLEASE PROVIDE OCCUPANT LOAD FOR
 PROPOSED TENANT SPACE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-06 Cont ID  
Sent By pkrauss Date 2001-04-06 Time 11:29 Rev Time 0.30
Received By pkrauss Date 2001-04-06 Time 11:29 Sent To  
Notes
2001-04-06 00:00:00APPROVED 4/6/01 - RESUBMITTAL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-04-02 Cont ID  
Sent By pkrauss Date 2001-04-02 Time 16:08 Rev Time 0.40
Received By pkrauss Date 2001-04-02 Time 16:08 Sent To  
Notes
2001-04-02 00:00:00*******************DENIED***************
  
 AS PER 1997 SMC 406.2, FAN SHUTDOWN BY
 DUCT SMOKE DETECTOR IS REQUIRED FOR ANY
 UNIT SERVING AN AREA USED FOR MEANS OF
 EGRESS AND SHALL HAVE NOTIFICATION TO
 TO ALARM/STROBE. SHOW COMPLIANCE WITH
 NFPA 90A 4-4.4.2 OR 4-4.4.3.
  
 CONDERSER WATER PIPING DONE IN COPPER
 SHALL BE BRAZED AS PER 1997 SMC 1206.1

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-04-07 Cont ID  
Sent By pschmitz Date 2001-04-07 Time 06:18 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-04-07 00:00:00PLUMBING PLAN REVIEW RE-SUB 4-6-01
 SEE SHT A-1 FOR ADA COMPLIANCE.PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-04-01 Cont ID  
Sent By pschmitz Date 2001-04-01 Time 10:16 Rev Time 1.25
Received By pschmitz Date   Time   Sent To  
Notes
2001-04-01 00:00:00PLUMBING PLAN REVIEWDENIED
 (1) TOILET RM #144 COMPLY W/FACBC 4.23.2
 DOORS SHALL NOT SWING INTO THE FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
 (2) KITCHEN SINK: RM#150 COMPLY W/FACBC
 4.24.1 THRU 4.24.7 HGTH.34",
 KNEE CLEARANCE 27"HIGH,19" DEEP,30"WIDTH
 SINK TO BE CENTERED ON 30"X 48" CLEAR
 FLOOR SPACE.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096 X 8233