Plan Review Stops For Permit 01031119 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2001-04-06 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-04-06 |
Time |
13:34 |
Rev Time |
0.50 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-04-03 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-04-03 |
Time |
07:33 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-04-03 00:00:00 | BUILDING PLAN REVIEW | | | | 1)- 1997 FL ACCESSIBILITY CODE 4.13.6: | | MANAUVERING DISTANCES AT DOORS, DOOR 143 | | REQUIRES 18" PULL SIDE OF DOORS. | | | | 2) 1997 FL ACC CODE 4.13.6: MANAUVERING | | DISTANCES AT DOOR POCKET DOOR REQUIRES | | A MIN. 32" CLEAR, DRAWN 30" LABELED 36". | | | | 3)- SHEET A-3 WOOD SUB BUCKS AND WOOD | | BACKING ARE REQUIRED TO BE FIRE TREATED | | WOOD, (SBC 609.2.1). | | | | 4)- MINIMUM INTERIOR FINISH SCHEDULE | | (SBC 803.3). | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-04-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-04-09 |
Time |
12:00 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-04-09 |
Time |
11:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-03-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-03-29 |
Time |
21:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-03-29 |
Time |
21:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-04-06 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-04-06 |
Time |
09:55 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-04-06 |
Time |
09:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-03-29 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-03-29 |
Time |
07:57 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-03-29 |
Time |
07:57 |
Sent To |
|
|
Notes |
2001-03-29 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED | | WITH PLANS. PLEASE PROVIDE FIRE | | SPRINKLER PLANS. | | 2) NO INTERIOR FINISH CLASSIFICATION. | | PLEASE PROVIDE INTERIOR FINISH | | INFORMATION. MATERIALS ON WALLS AND | | CEILINGS MUST BE CLASS A, B, OR C. | | 3) SMOKE DETECTOR(S) NOT SHOWN IN | | ELEVATOR LOBBY. THERE SHOULD BE SMOKE | | DETECTORS ALREADY PRESENT TO RECALL | | THE ELEVATORS. IF THEY ARE GOING TO | | BE REMOVED, THEY MUST BE RE-INSTALLED. | | SEPARATE PLANS AND PERMITS REQUIRED FOR | | FIRE ALARM REMODEL. | | 4) PLEASE PROVIDE OCCUPANT LOAD FOR | | PROPOSED TENANT SPACE. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-04-06 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-04-06 |
Time |
11:29 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2001-04-06 |
Time |
11:29 |
Sent To |
|
|
Notes |
2001-04-06 00:00:00 | APPROVED 4/6/01 - RESUBMITTAL |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-04-02 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-04-02 |
Time |
16:08 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2001-04-02 |
Time |
16:08 |
Sent To |
|
|
Notes |
2001-04-02 00:00:00 | *******************DENIED*************** | | | | AS PER 1997 SMC 406.2, FAN SHUTDOWN BY | | DUCT SMOKE DETECTOR IS REQUIRED FOR ANY | | UNIT SERVING AN AREA USED FOR MEANS OF | | EGRESS AND SHALL HAVE NOTIFICATION TO | | TO ALARM/STROBE. SHOW COMPLIANCE WITH | | NFPA 90A 4-4.4.2 OR 4-4.4.3. | | | | CONDERSER WATER PIPING DONE IN COPPER | | SHALL BE BRAZED AS PER 1997 SMC 1206.1 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-04-07 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-04-07 |
Time |
06:18 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-04-07 00:00:00 | PLUMBING PLAN REVIEW RE-SUB 4-6-01 | | SEE SHT A-1 FOR ADA COMPLIANCE.PES |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-04-01 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-04-01 |
Time |
10:16 |
Rev Time |
1.25 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-04-01 00:00:00 | PLUMBING PLAN REVIEWDENIED | | (1) TOILET RM #144 COMPLY W/FACBC 4.23.2 | | DOORS SHALL NOT SWING INTO THE FLOOR | | SPACE REQUIRED FOR ANY FIXTURE. | | (2) KITCHEN SINK: RM#150 COMPLY W/FACBC | | 4.24.1 THRU 4.24.7 HGTH.34", | | KNEE CLEARANCE 27"HIGH,19" DEEP,30"WIDTH | | SINK TO BE CENTERED ON 30"X 48" CLEAR | | FLOOR SPACE. | | END OF COMMENTSPAUL SCHMITZ | | QUESTIONS561-659-8096 X 8233 |
|
|