Plan Review Details - Permit 01031035
Plan Review Stops For Permit 01031035
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-04-12 Cont ID  
Sent By hpiskura Date 2001-04-12 Time 10:04 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-04-12 00:00:001 THE EXIT STAIRS ARE REQUIRED TO BE
 ENCLOSED.SEE SBC 1006.1.
 2 HOW WILL THE ADJACENT BUILDING EGRESS
 BE EFFECTED BY CLOSING THE COMMUNICATING
 OPENING?SBC 104.2

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-04-05 Cont ID  
Sent By dpalmer Date 2001-04-05 Time 07:53 Rev Time 0.00
Received By dpalmer Date 2001-04-05 Time 07:53 Sent To  
Notes
2001-04-05 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW MIN BRANCH CIRCUIT
 #`S ON PLANS AND CORRELATE CIRCUITS
 WITHPANEL SCHEDULES SUBMITTED.
  
 2)NOTE: PLEASE NOTE THAT EGRESS
 LIGHTINGIN STAIRWELL IS SHOWN BEING
 SWITCHED.
 EGRESS LIGHTING IN STAIRS NEED TO BE
 POWERED BY CONTINOUS POWER.
  
 3)NOTE: PLEASE PROVIDE CLARIFICATION FOR
 FEED TO PANELS. 100A DISC SHOWN FEEDING
 TWO 100A PANELS WITH LOADS EXCEEDING
 OVER CURRENT PROTECTION.
  
 4)NOTE: PLEASE CLARIFY TYPE OF CONDUIT
 PR EQUIPMENT GROUND BETWEEN DISCAND
 PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMTATION
 FORREVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-27 Cont ID  
Sent By mcarsill Date 2001-03-27 Time 14:16 Rev Time 0.00
Received By mcarsill Date 2001-03-27 Time 14:16 Sent To  
Notes
2001-03-27 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) NO FIRE ALARM EQUIPMENT SHOWN ON
 PLANS FOR THE SECOND FLOOR.
 3) NO INTERIOR FINISH INFOMATION NOTED
 ON PLANS FOR THE WALLS AND CEILINGS OF
 THE TENANT SPACES.
 4) DOOR CLOSERS REQUIRED ON THE B
 LABELED FIRE DOORS.
 5) ADDITONAL EMERGENCY LIGHTS REQUIRED
 IN THE TENANT SPACES.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-03-26 Cont ID  
Sent By pkrauss Date 2001-03-26 Time 15:02 Rev Time 0.35
Received By pkrauss Date 2001-03-26 Time 15:02 Sent To  
Notes
2001-03-26 00:00:00AS PER NFPA 90A 4-4.4.3, FAN SHUTDOWN BY
 DUCT SMOKE DETECTOR WITH NOTIFICATION
 TO ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS.

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***