Plan Review Details - Permit 01031035
Plan Review Stops For Permit 01031035 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-04-12 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-04-12 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-04-12 00:00:00 | 1 THE EXIT STAIRS ARE REQUIRED TO BE | | ENCLOSED.SEE SBC 1006.1. | | 2 HOW WILL THE ADJACENT BUILDING EGRESS | | BE EFFECTED BY CLOSING THE COMMUNICATING | | OPENING?SBC 104.2 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-04-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-04-05 |
Time |
07:53 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-04-05 |
Time |
07:53 |
Sent To |
|
|
Notes |
2001-04-05 00:00:00 | **************** UNSAT ***************** | | | | 1)NOTE: PLEASE SHOW MIN BRANCH CIRCUIT | | #`S ON PLANS AND CORRELATE CIRCUITS | | WITHPANEL SCHEDULES SUBMITTED. | | | | 2)NOTE: PLEASE NOTE THAT EGRESS | | LIGHTINGIN STAIRWELL IS SHOWN BEING | | SWITCHED. | | EGRESS LIGHTING IN STAIRS NEED TO BE | | POWERED BY CONTINOUS POWER. | | | | 3)NOTE: PLEASE PROVIDE CLARIFICATION FOR | | FEED TO PANELS. 100A DISC SHOWN FEEDING | | TWO 100A PANELS WITH LOADS EXCEEDING | | OVER CURRENT PROTECTION. | | | | 4)NOTE: PLEASE CLARIFY TYPE OF CONDUIT | | PR EQUIPMENT GROUND BETWEEN DISCAND | | PANEL. | | | | PLEASE SUBMIT THE ABOVE INFORMTATION | | FORREVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
|
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-03-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-03-27 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-03-27 |
Time |
14:16 |
Sent To |
|
|
Notes |
2001-03-27 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | WITH PLANS. | | 2) NO FIRE ALARM EQUIPMENT SHOWN ON | | PLANS FOR THE SECOND FLOOR. | | 3) NO INTERIOR FINISH INFOMATION NOTED | | ON PLANS FOR THE WALLS AND CEILINGS OF | | THE TENANT SPACES. | | 4) DOOR CLOSERS REQUIRED ON THE B | | LABELED FIRE DOORS. | | 5) ADDITONAL EMERGENCY LIGHTS REQUIRED | | IN THE TENANT SPACES. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-03-26 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-03-26 |
Time |
15:02 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2001-03-26 |
Time |
15:02 |
Sent To |
|
|
Notes |
2001-03-26 00:00:00 | AS PER NFPA 90A 4-4.4.3, FAN SHUTDOWN BY | | DUCT SMOKE DETECTOR WITH NOTIFICATION | | TO ALARM/STROBE IN NORMALLY OCCUPIED | | AREAS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
|
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
|
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|