Plan Review Details - Permit 01030864
Plan Review Stops For Permit 01030864
Review Stop E ELECTRICAL
Rev No 5 Status F Date 2001-10-29 Cont ID  
Sent By dpalmer Date 2001-10-29 Time 22:43 Rev Time 0.00
Received By dpalmer Date 2001-10-29 Time 22:43 Sent To  
Notes
2001-10-29 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT ALL CHANGES
 ON PLANS THAT ARE ON RECORD BY AN ARCH/
 ENGINEER MUST BE THE ONE TO MAKE ALL
 CHANGES TO PLANS/REVISIONS. PLEASE NOTE
 THAT PLANS MUST BE RE-DONE UNDER ADIN
 CODE 104.2/104.2.7
  
 2)NOTE: PLEASE ALSO NOTE THAT PLANS
 MUST BE SIGNED, DATED AND SEALED BY THE
 ARCH OF RECORD. 481.221.
  
 3)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS THREE PANELS, PLEASE SHOW LOCATION
 -S FOR ALL PANELS ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-08-27 Cont ID  
Sent By dpalmer Date 2001-08-27 Time 22:32 Rev Time 0.00
Received By dpalmer Date 2001-08-27 Time 22:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2001-05-29 Cont ID  
Sent By jgomez Date 2001-05-29 Time 15:44 Rev Time 0.00
Received By jgomez Date 2001-05-29 Time 15:44 Sent To  
Notes
2001-05-29 00:00:00CONTRACTOR AGREED TO APPLY FOR SEPARATE
 PERMIT TO EXPEDITE THE REVIEW PROCESS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-05-25 Cont ID  
Sent By dpalmer Date 2001-05-25 Time 06:24 Rev Time 0.00
Received By dpalmer Date 2001-05-25 Time 06:24 Sent To  
Notes
2001-05-25 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FIRST REVIEW COMMENTS WERE
 ADDRESS-ED. 1,3,4,5,6,7.
  
 2)NOTE: PLEASE NOTE THAT SMOKE
 DETECTORSARENOT PERMITTED IN KITCHENS
 PER
 NFPA-72 2-5.1.6. MUST BE 3' FROM KITCHEN
 ENTRY.
  
 3)NOTE: PLEASE CLARIFY KITCHEN
 PENINSULAROUTLET SPACING PER NEC
 210-52-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 INFORMATION FROM FIRST REVIEW. PLEASE
 SEE ORIG NOTES ATTACHED. AGAIN, IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-80969 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-27 Cont ID  
Sent By dpalmer Date 2001-03-27 Time 07:06 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 22:17 Sent To  
Notes
2001-03-27 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE ELECTRICAL LEGEND,
 YOU SHOW THE REQ`D EGRESS LIGHTING AS
 CEILING J-BOXES. PLEASE SEE 210-70 FOR
 THE REQ`D LIGHTING FIXTURES.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 PLEASE NOTE THAT MORETHAN 50% OF THE
 STRUCTURE IS BEING WIRED. NEED TO BRING
 SD REQ`MENTS UP TO CODE.
  
 3) NOTE: PLEASE SHOW ALL OUTLETS
 SERVINGKITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
  
 4)NOTE: PLEASE SUBMIT PANEL SCHEDULE
 WITH THE REQ`D CIRCUITS SHOWN.
 PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC. EXSITING?
  
 6)NOTE: PLEASE SHOW ANY NEW A/C
 EQUIPMENT ON ELECTRICAL DRAWING. PLEASE
 SHOW
 REQ`D GFI 309.1 OF THE MECH CODE AND
 210-63. PLEASE SHOW DISCONNECT(S) PER
 440-11.
  
 7)NOTE: PLEASE PLACE NOTE ON PLANS THAT
 AREA WHERE CLOSET MUST MAINTAIN
 CLEARENCE REQ`D PER 110-26 AND 384-7.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-05-29 Cont ID  
Sent By jgomez Date 2001-05-29 Time 15:45 Rev Time 0.00
Received By jgomez Date 2001-05-29 Time 15:45 Sent To  
Notes
2001-05-29 00:00:00CONTRACTOR AGREED TO APPLY FOR SEPARATE
 PERMIT TO EXPEDITE THE REVIEW PROCESS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-03-26 Cont ID  
Sent By jleech Date 2001-03-26 Time 15:28 Rev Time 0.50
Received By jleech Date 2001-03-26 Time 15:28 Sent To  
Notes
2001-03-26 00:00:00DENIED;
  
 1.LIST CFM'S FOR EACH DROP.
  
 2.SIZE AND ROUTE OF DUCT BOARD IS
 UNCLEAR. COMPLY WITH COUNTY WIDE
 AMENDMENTS 104.2.
  
 3.MASTER BEDROOM SUITE REQUIRED A R/A IF
 SUPPLY AIR IS 300 CFM'S OR MORE.
  
 A/C PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-03-26 Cont ID  
Sent By jleech Date 2001-03-26 Time 15:36 Rev Time 0.33
Received By jleech Date 2001-03-26 Time 15:36 Sent To  
Notes
2001-03-26 00:00:00PROVISO;
  
 BUILDING SEWER SHALL INCREASE TO 4"AFTER
 RECEIVING THE DISCHARGE OF 3 TOILETS.
 TABLE 714.1 NOTE #3.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-07-10 Cont ID  
Sent By jgomez Date 2001-07-10 Time 15:25 Rev Time 0.50
Received By jgomez Date 2001-07-10 Time 15:25 Sent To  
Notes
2001-07-10 00:00:00TRUSS DRAWINGS CHECKLIST:
  
 1- ARCHITECT TO SPECIFY CONNECTORS TO
 SUPPORT NEW ROOF TRUSSES AT EXISTING
 GARAGE STRUCTURE. GENERAL CONNECTOR H-10
 SPECIFIED ON SHEET A-8 DOESN'T APPLY TO
 ROOF TRUSSES SITTING ON CONCRETE TIE BM.
  
 2-ARCH. TO SPECIFYCONNECTOR TO RESIST
 THE UPLIFT LOADS CALCULATED ON THE
 ENGINEERED TRUSSES FOR THE FOLLOWING
 TRUSSES: H7, H9, H11, H13, H15, H17, T1
 AND V34.
  
 3-ARCHITECT'S ROOF FRAMING PLAN AND
 TRUSS LAYOUT ARE SLIGHTLY DIFFERENT BY
 THE GARAGE AREA. SPECIFY CONNECTORS
 TO RESIST THE UPLIFT LOADS AT TRUSSES
 H7A.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-05-29 Cont ID  
Sent By jgomez Date 2001-05-29 Time 11:56 Rev Time 4.00
Received By jgomez Date 2001-05-29 Time 11:56 Sent To  
Notes
2001-05-29 00:00:00APPROVED WITH PROVISO:
  
 1-DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM:
 -ARCHITECT NEEDS TO WRITE DOWN HIS
 INFORMATION AS REQUIRED BY CHAPTER
 481 OF FLORIDA STATUTES.
 2-SPECIFY UPLIFT CONNECTORS FOR NEW ROOF
 TRUSSES AT GARAGE AREA (TO BE ATTACHED
 TO EXISTING CONCRETE TIE BEAM).
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 4-PROVIDE 2 SETS OF PRODUCT APPROVALS:
 A)AWNING WINDOWS.
 B)WINDOW MULLIONS.
 5-SEE PLANS FOR ADDITIONAL INFORMATION
 REQUIRED.
  
  
  
  
  
  
 NOTE: IF YOU HAVE ANY QUESTIONS, PLEASE
 CALL JULIO GOMEZ, BUILDING PLANS
 EXAMINER, AT 659-8096 EXT 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-04-27 Cont ID  
Sent By jgomez Date 2001-04-27 Time 09:59 Rev Time 3.00
Received By jgomez Date 2001-04-27 Time 09:59 Sent To  
Notes
2001-04-27 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-NOTICE OF COMMENCEMENT DESCRIPTION OF
 WORK DOESN'T MATCH THE SCOPE OF WORK
 DECLARED ON THIS PERMIT APPLICATION.
 3-SPECIFY DESIGN PRESSURES CALCULATED
 FOR THE EXTERIOR OPENINGS AS PER
 SECTION 1606 SBC 1997.
 4-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 SBC 1997.
 5-COMPLETE FLOOR AND FOUNDATION PLANS
 SHOWING THE OUTSIDE STEPS.
 NOTE: A LANDING IS REQUIRED @ EXTERIOR
 DOORS. SEE PLANS AND SECTION 1012.1.6
 OF SBC 1997.
 6-PROVIDE ATTIC ACCESS AT GARAGE AND
 SECOND FLOOR ROOF. SEC 2309.6 SBC 1997
 7-PROVIDE COMPLETE DESIGN CERTIFICATION
 FOR BUILDING CODE COMPLIANCE FORM.
 ATTACHED (PROVIDE TWO COPIES).
 8-OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS (PROVIDE 2 COPIES)
 9-SPECIFY BEAMS AND CONNECTORS.
 SEC 104.2.2 CITY AMENDMENTS TO SBC/97
 10-SPECIFY ALL COLUMNS AND TOP AND BOTT.
 CONNECTORS. SEC 104.2.2 CITY AMENDMENT
 11-SPECIFY CALCULATED UPLIFT LOADS AND
 PROVIDE ANCHOR SCHEDULE. SEC 1606 SBC
 12-PROVIDE COMPLETE SECTION DETAIL THRU
 BALCONY. SPECIFY CONSTRUCTION, ANCHORS
 AND MATERIALS TO BE USED.SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 13-NEED SECOND FLOOR FRAMING PLAN.
 NOTE: EXISTING RAFTERS WERE DESIGNED
 TO CARRY A ROOF LOAD. FLOOR LOADS ARE
 DIFFERENT. SEE SECTIONS 1603 AND 1604
 OF SBC 1997. PROVIDE COMPLETE
 STRUCTURAL ANALYSIS AND WOOD SPECS IF
 USING THE EXISTING FRAMING TO CARRY
 THE NEW LOADS.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 14-PROVIDE COMPLETE CONSTRUCTION DETAILS
 AND SPECS FOR CONSTRUCTION OF PERGOLA.
 SEC. 104.2.2 CITY AMENDMENTS.
 15-PROVIDE SMOKE DETECTORS AT FIRST AND
 SECOND FLOOR. SEC 905.2 SBC 1997.
 16-SPECIFY ATTIC VENTILATION. SECTION
 2309.7 SBC 1997.
 17-PROVIDE AREA TABULATION
 18-STORM SHUTTERS:
 A)PROVIDE KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE AS PER CITY
 SAMPLE ATTACHED.
 B)CLEARLY MARK ON STORM PANELS DRAWINGS
 THE SPECIFIC MOUNTING CONDITIONS AND
 ANCHOR TYPE TO BE USED ACCORDING TO
 THE MEAN ROOF HEIGHT,DESIGN PRESSURES,
 PANEL SPAN, EDGE DISTANCE, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO
 (CONCRETE BLOCK OR WOOD).
 19-TRUSS DRAWINGS:
 A)ARCHITECT OF RECORD TO REVIEW ALL
 TRUSS DRAWINGS PRIOR TO SUBMITTAL.
 B)ENGINEER TO SIGN, SEAL AND DATE THE
 TRUSS LAYOUT AS REQUIRED BY CHAPTER
 471 OF FLORIDA STATUTES.
 C)TRUSS LAYOUT AND ARCHITECT'S ROOF
 FRAMING PLANS ARE DIFFERENT. REVISE
 EITHER ONE TO MATCH.
 D)TRUSS LAYOUT HAVE THE WRONG ADDRESS
 AND OWNER OF THIS HOUSE.
 E)UPDATE TRUSS DESIGN CRITERIA TO ASCE
 7-95 FOR 145MPH OR SBC 1997 FOR 110MPH
 ACCORDING TO THE DESIGN CRITERIA USED
 BY THE ARCHITECT OF RECORD.
 F)PROVIDE COMPLETE SETS OF ENGINEERED
 TRUSSES (REVIEWED BY THE ARCHITECT)
 20-PROVIDE 2 COPIES OF PRODUCT APPROVALS
 A)ENTRY DOOR.
 B)SINGLE HUNG WINDOWS.
 C)GARAGE DOOR (IF REPLACED)
 D)WINDOW MULLIONS.
 E)FRENCH DOORS.
 F)GARAGE SWING DOOR.
 G)AWNING WINDOWS.
 21-SEE PLANS FOR ADDITIONAL COMMENTS
 AND PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS, IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.
 22-PROVIDE STRUCTURAL BUCK DETAILS FOR
 DOORS AND WINDOWS. ALSO, FOR GARAGE
 DOOR IF IT'S GOING TO BE REPLACED.
 SEC. 104.2.2 CITY AMENDMENTS.
  
 NOTE: SURVEY SAYS FLOOD ZONE B. ACTUAL
 FLOOD ZONE IS C.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ, BUILDING PLAN REVIEWER, AT
 659-8096 EXT. 8232.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-23 Cont ID  
Sent By sgraham Date 2001-03-23 Time 12:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***