Plan Review Details - Permit 01030739
Plan Review Stops For Permit 01030739
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-04 Cont ID  
Sent By mcarsill Date 2001-04-04 Time 09:47 Rev Time 0.00
Received By mcarsill Date 2001-04-04 Time 09:47 Sent To  
Notes
2001-04-04 00:00:00CUT SHEETS FOR SMOKE DETECTORS PROVIDED
 ON APRIL 4, 2001 TO THIS WRITER. TENANT
 SPACE NOT REQUIRED TO HAVE A FIRE ALARM
 SYSTEM. TENANT WANTS TO INSTALL SMOKE
 DETECTORS TO BURGLAR ALARM SYSTEM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-03-27 Cont ID  
Sent By mcarsill Date 2001-03-27 Time 08:23 Rev Time 0.00
Received By mcarsill Date 2001-03-27 Time 08:23 Sent To  
Notes
2001-03-27 00:00:001) PLANS NOT SIGNED AND SEALED. PLAN
 CONTAINS ARCHITECTS TITLE BLOCK.
 2) NO CUT SHEETS PROVIDED FOR SMOKE
 DETECTORS PLANNED FOR INSTALLATION.
 3) PLEASE INDICATE WHAT THE SMOKE
 DETECTORS WILL BE CONNECTED TO.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910